10 Troubleshooting
Troubleshooting in check mode
SMGB0091 rev.2 - 11/2015
265
10
Protection control code on 7-segment display
1
Protection control code is displayed on 7-segment when a protection control is activated.
2
Protection control code is displayed while function is working, and goes out when released.
3
When several protection control are activated, code number with higher priority will be indicated (see below for the
priority order).
a.
Higher priority is given to protection control related to frequency control than the other. Priority order:
High-pressure increase protection
Over current protection
Cold draft protection
b.
In relation to retry control, the latest retrial will be indicated unless a protection control related to frequency control
is indicated.
Priority
Protection control
Code
1
Pressure ratio control
p1
2
High-pressure increase protection
p2
3
Inverter current protection
p3
4
Inverter fin temperature increase prevention
P4
5
Discharge gas temperature increase protection
p5
6
Demand current control (running current limit control)
pA
7
High-pressure decrease protection
p9
?
N O T E
The protection control code being indicated on 7-segment display is changed to an alarm code when the abnormal operation occurs. Also,
the same alarm code is indicated on the remote control switch.