10 Troubleshooting
Initial troubleshooting
SMGB0091 rev.2 - 11/2015
195
10
Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
RASC fan does not operate
when the compressor
operates
Obstacle at the RASC fan
Check the obstacles
Remove the obstacles
Watching condition for the heating
process
Wait for the switching of the
4-way valve (1 ~ 3 minutes)
If the 4-way valve does not
switch, check for insufficient
refrigerant
Indoor fan does not operate
when the compressor
operates
Discharge pressure does not
increase higher than 1.5 MPa due
to the insufficient refrigerant
Check the operation pressure Add the refrigerant
Disconnected wiring for
the indoor fan
Check the wiring
Connect the wiring correctly