10 Troubleshooting
Troubleshooting procedure
SMGB0091 rev.2 - 11/2015
209
10
?
N O T E
• *1) In the case that the end terminal resistance (DSW5-1) is set to OFF for H-LINK connection, set the end terminal resistance to ON
when CN8 is disconnected. Set the end terminal resistance to OFF when CN8 is reconnected.
• *2) Transmission Setting (SW1)
Item
Setting Position
SW1
• *3)
PCB1 output voltage
Voltage
Vcc 12 – GND2
12 VDC
Vcc 05 – GND1
5 VDC
Vcc 12 – GND1
12 VDC
Vcc 15 – GND1
15 VDC
Vcc 24 – GND1
24 VDC
Vcc 12T– GND1
12 VDC
• *4) The rotary switch (RSW2) is not available depending on the indoor unit model.
• *6) Refer to section
“Self-checking procedure of PCB by means of the remote control switch”