10 Troubleshooting
Troubleshooting procedure
SMGB0091 rev.2 - 11/2015
212
Alarm code
05
Code abnormal operation of picking up phase signal
This alarm is displayed when the main power source phase is reversely connected or one phase is not connected.
Correctly connect each
phase of the power source
Yes
Reverse phase connection
No
Yes
No
Correctly connect each
phase of the power source
Faulty PCB1 or other cause
(see below)
PCB1 is normal
PCB1 is normal
Is there any phase which is
not connected?
Voltage for unit to
be suspended
Running voltage:
342 to 456V
Setting voltage:
Less than 323V
Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
Activation of
reverse phase
sensor in the
RASC unit
Reverse or single phase
Check it according to
the electrical wiring
Replacing wires, repair,
tightening screws or correct
wiring
Faulty RASC unit PCB
-
Replace PCB if faulty