6 Optional functions
Optional functions
SMGB0091 rev.2 - 11/2015
115
6
Element
Optional function
Individual
setting
Settings
Setting conditions
Description
H4
PC-ART: Operating
modes for the
ventilation unit
with energy / heat
recovery
O
00
Air conditioning only
This function allows to select the operation
mode for KPI units.
(Only available for KPI units)
01
Ventilation only
02
Air condit
ventilation
PC-ARF: Not
available
–
00
Not available
–
01
(Used as 00 conditions)
H5
PC-ART: Central
control available after
forced stoppage
O
00
Not available
This function allows the central control
after the forced stoppage of the unit.
01
Available
PC-ARF: Not
available
–
–
Not available
(Used as 00 conditions) –
J1
(*8)
Temperature
indication
X
00
Not available
This function is used to display the sensor
temperature on the remote control switch.
This temperature depends on the setting
value of optional function (C8) and on the
use of remote sensor (THM4)
(Displayed on PC-ARF only)
01
Available
J2
Not available
–
–
Not used
(Displayed on PC-ARF only)
J3
Run indicator colour
X
00
Green
This function allows to select the colour of
run indicator between green and red.
(Displayed on PC-ARF only)
01
Red
J4
Not available
–
00
Not available
(Displayed on PC-ARF only)
01
(Used as 00 conditions)
02
J5
Not available
X
00
Not available
(Displayed on PC-ARF only)
01
(Used as 00 conditions)
J6
Error sound
X
00
Once
(Displayed on PC-ARF only)
01
Sequence
J7
Not available
–
00
Not available
(Displayed on PC-ARF only)
01
(Used as 00 conditions)
J8
(*9)
Eco-operation
X
00
Not activated function
When this function is activated, the setting
temperature returns to the selected cooling
(F5) or heating (F6) temperature values
by restarting the operation using the RUN/
STOP button on the remote control switch.
This function provides energy-saving.
(Displayed on PC-ARF only)
01
Activated function
J9
Not available
–
00
Not available
(Displayed on PC-ARF only)
01
(Used as 00 conditions)
JA
Not available
–
00
Not available
(Displayed on PC-ARF only)
01
(Used as 00 conditions)
Jb
Not available
–
00
Not available
(Displayed on PC-ARF only)
01
(Used as 00 conditions)
K1
Not available
X
–
Not used
(Displayed on PC-ARF only)
K2
Not available
X
–
Not used
(Displayed on PC-ARF only)
K3
Not available
X
–
Not used
(Displayed on PC-ARF only)
K4
Not available
–
00~03
Not used
(Displayed on PC-ARF only)