5-12
5.6
Control Circuit Terminals
Forward
Reverse
SWF
SWR
ON
ON
SWR
CM1 PLC P24 FW
8
1
•••••
SWF
ON
ON
ON
ON
ON
ON
ON
CM1
Fourth (FS)
speed
Third
speed
Second
speed
First
speed
Frequency
(Hz)
Switch
SW1
SW2
SWF
Time
PLC P24 FW 8
7
6
SWF
SW1 SW2
(Source type)
• When setting frequency,
connect P24 and 6 or 7
and set with digital
operator or .
1
2
1 to 8
Terminal symbol
Terminal name
Description
FM
Monitor terminal
Analog: Output frequency, current, torque
Digital: Output frequency x frequency converted value
(Set in the remote operator monitor mode), max. pulse: 3.6 kHz
CM1
Common terminal 1
Common terminal for the monitor terminal
PLC
Internal
interface
common
Common terminal for the external power source of the sequencer
P24
Input signal power source
Internal power source for the contact input terminal and frequency
monitor terminal, 24 VDC.
Common for the FW terminal and intelligent input terminals
FW
Forward
run/stop
terminal
OUTPUT frequency
REV
Reverse run/stop
CF1
SW1
CF2
Multistage speed
SW2
CF3
SW3
(NOTE 1)
JG
Jogging
Jogging run
DB
External DC braking
DC braking input signal
STN
Initialization
Initialization (shipment status at factory) input
SET
2nd function
The output frequency setting, base and maximum frequencies,
control method, motor constant, acceleration or deceleration time,
manual torque boost setting, and electronic thermal setting are
changed in batch.
CH1
Two-stage acceleration
The acceleration or deceleration time or selection of two-stage
or deceleration
accration or deceleration is changed by turning the contact ON.
FRS
Free run stop
The inverter stops and the motor stops free run
FRS functions when the contact is opened. (European version)
EXT
External trip
External trip input signal (The contact is open.)
USP
Power-ON restart
Restart prevention when the power is turned on in the RUN
prevention
state (The contact is open.)
CS
Commercial power source
Switch signal from the commercial power source to inverter
switching
drive (Note: When the terminal is used, a trip is also conceled.)
SFT
Terminal software lock
The data of all funcitons except for output frequency setting is
locked. See 12-9 [F-25].
AT
Analog input command
Analog input voltage-current switching (When the contact is ON,
current input signal to OI-L is acrive.)
RS
Reset
Trip or alarm signal is reset.
UP
Remote control function,
When the contact is turned ON, the operation is accelerated.
acceleration
(Available only when the frequency command is sent
to the operator.)
DWN
Remote control function,
When the contact is turned ON, the operation is decelerated.
deceleration
(Available the frequency command is sent to the operator.)