12-13
Display
(Function mode 1)
(Function mode 2)
Setting, change
sequence
Function
Function
Initialization display
Initialization
contents
Setting contents
No.
name
contents
30
F-37
Monitor
MONITOR
A-F
A-F
A-F/A/T/D-F
• The FM terminal monitor
signal
signal output is selected.
selection
A-F: Analog frequency
T: Torque monitor
A: Current monitor
D-F: Digital frequency
31
F-38
Trip history
INIT TCNT
CNT
CNT
CNT/CLR
• Trip count deletion selection
Initiali-
count clear
CNT: Trip counting is
zation
continued.
CLR: The trip count is cleared.
Debug
INIT DEBG
OFF
OFF
ON/OFF
• Debug mode setting ON or
mode
OFF
display
OFF: The debug mode is
selection
turned off.
NOTE 1
ON: The debug mode is turned
on.
Digital
INIT DOPE
FWD
FWD
FWD/REV
• The digital operator running
operator
direction is set.
rotation
FWD: Forward run
direction
REV: Reverse run
selection
Selection of
INIT RESET
ON
ON
ON/OFF
ON: Alarm release when reset
reset
on
performance
OFF:Alarm release when reset
off
32
F-39
Encode
OP P
01024 pulse
1024
255 to 65535
Effective with option board
Option
pulse
(J-FB)
setting
number
setting
Control
OP MODE
ASR
ASR
ASR/APR
mode
selection
Ro-To
OP RO-TO
OFF
OFF
OFF/ON
Keep OFF. (No use)
option
selection
33
F-40
Stop
OR POS
IN
IN
IN/OUT
Effective with option board
Orientation position
(J-FB)
setting
setting
switching
Stop
OR P
00000 pulse
0
0 to 4095
position
setting
Speed setting
OR FC
0005.0 Hz
5.0 Hz
0 to 400 Hz
Direction
OR TURN
FWD
FWD
FWD/REV
setting
Completion
OR L
00005 pulse
5
0 to 10000
range setting
Completion
OR TW
0.00 s
0
0 to 9.99
delay time
setting
NOTE 1 : Keep debug mode " OFF " , this is factory use only.