12-8
Display
(Function mode 1)
(Function mode 2)
Setting, change
sequence
Function
Function
Initialization display
Initialization
contents
Setting contents
No.
name
contents
13
F-20
DC braking
DCB SW
OFF
OFF
ON/OFF
• DC braking
DC
selection
ON: DC braking available
injection
OFF: DC braking unavailable
braking
DC braking
DCB KIND
LVL
LVL
LVL/EDG
• DC braking method selection
type
LVL: Level operation
selection
EDG: Edge operation
DC braking
DCB F
0000.5 Hz
0.5 Hz
0 to 400.0 Hz
• The frequency at which the
frequency
DC braking starts is set.
selection
DC braking
DCB V-STA
00
0
0 to 20
• The DC braking force at start
force selec-
is set.
tion (at start)
DC braking
DCB V-STP
00
0
0 to 20
• The DC braking force at stop
force selec-
is set.
tion (at stop)
DC braking
DCB T-STA
000.0 s
0 s
0 to 600.0
• The DC braking time at start
time selec-
is set.
tion (at start)
DC braking
DCB T-STP
000.0 s
0 s
0 to 600.0
• The DC braking time at stop
time selec-
is set.
tion (at stop)
DC braking
DCB STOP-T
0.00 s
0 s
0 to 5.00
The output frequency is
output cut-
lowered to the DC braking
off time
frequency and the free run
adjustment
time during execution of DC
braking is set.
14
F-21
Dynamic
BRD-%ED
001.5%
1.5%
0 to 100.0
• The allowable usage ratio of
braking
the braking resistor for 100
setting
seconds is set. (NOTE 1)
15
F-22
Allowable
IPS TIME
1.0 s
1.0 s
0.3 to 25 s
• When an instantaneous power
The
instantaneous
failure occurs, the allowable
allowable
power failure
time until the power failure is
usage
time setting
recovered is set.
ratio of
Reclosing
IPS WAIT
001.0 s
1.0 s
0.3 to 100.0 s
• The waiting time until the
the
standby after
rerunning starts after an
braking
instantaneous
instantaneous power failure
resistor
power failure
occurs and is recovered is set.
for 100
recovered
seconds
Instantaneous
IPS POWR
ALM
ALM
ALM/FTP/
ALM: Alarm output
is set.
power failure
RST/ZST
ZST: 0 Hz start retry
restart
FTP: Retry after frequency
selection
matching is stopped
RST: Rerunning start retry
Trip selection
IPS TRIP
OFF
OFF
ON/OFF
When an instantaneous power
during stop
failure occurs:
at under
ON: Trip
voltage
OFF: Non-trip
16
F-23
Electronic
E-THM CHAR
SUB
SUB
CRT/SUB/FRE
• Electronic thermal characteris-
Electronic thermal
tic setting CRT: Constant
thermal
characteristic
torque characteristic
selection
SUB: Reduced torque charac-
teristic
FRE: Free characteristic
Electronic
E-THM LEVEL
100%
100%
20 to 120%
thermal level
setting
NOTE 1: Initial setting of usage ratio
1.5%
055-075L/HF
0%
110-550L/HF