![Hitachi FSG Series Technical Catalogue Download Page 48](http://html.mh-extra.com/html/hitachi/fsg-series/fsg-series_technical-catalogue_139455048.webp)
2
/14
GENERAL DATA
2.3.7.
OUTDOOR HEAT EXCHANGER AND FAN (FSG/FSG1)
Model Outdoor Unit
RAS-5FSG
RAS-8FSG
RAS-10FSG
RAS-16FSG
RAS-20FSG RAS-24FSG1 RAS-30FSG1
Heat Exchanger Type
Multi-Pass Cross Finned Tube
Material
Copper Tube
Outer Diameter
Ø mm
9.53
9.53
9.53
9.53
9.53
9.53
9.53
Rows
2
2
2
2
2
2
2
Tube
Number of Tube/Coil
112
112
112
112
112
168
168
Material
Aluminium
Fin
Pitch
mm
2
2
2
2
2
2
2
Maximum Operating Pressure
MPa
3.3/3.0
3.3/3.0
3.3/3.0
3.3/3.0
3.3/3.0
3.3
3.3
Total Face Area
m²
1.20
1.65
2.03
3.30
4.06
4.95
6.09
Heat Exc
h
an
ger
Number of Coil / Unit
1
1
1
2
2
3
3
Type
Propeller Fan
Number/Unit
1
1
1
2
2
3
3
Outer Diameter
mm
540
640
640
640
640
644
644
Revolution
rpm
775/825
740/780
820/850
740/804
817/880
840/700/840
860/700/860
840/770/840
860/770/860
Fan
Nominal Air Flow/Fan
m
3
/min
87
138
172
278
344
426
531
Type
Drip-Proof Type Enclosure
Starting Method
Permanent Split Capacitor
Nominal Output
W
160
275
275
275/350
275/350
275/275/275* 275/275/275*
Quantity
1
1
1
2
2
3
3
Fan U
n
it
Fan
Motor
Insulation Class
E
E
E
E
E
E
E
*) R: Right, C: Center, L: Left
In case of the Outdoor Unit for m220V/60Hz, the nominal output of Fan Motor is 275/380/275
2.3.8.
OUTDOOR HEAT EXCHANGER AND FAN (FXG/FXG1)
Model Outdoor Unit FXG
RAS-8FXG
RAS-10FXG
RAS-20FXG1
RAS-30FXG1
Heat Exchanger Type
Multi-Pass Cross Finned Tube
Material
Copper Tube
Outer Diameter
Ø mm
9.53
9.53
9.53
9.53
Rows
2
2
2
2
Tube
Number of Tube/Coil
112
112
112
168
Material
Aluminium
Fin
Pitch
mm
2
2
2
2
Maximum Operating Pressure
MPa
3.3
3.3
3.3
3.3
Total Face Area
m²
1.65
2.03
4.06
6.09
Heat Exc
h
an
ger
Number of Coil / Unit
1
1
2
3
Type
Propeller Fan
Number/Unit
1
1
2
2
Outer Diameter
mm
540
640
644
644
Fan
Nominal Air Flow/Fan
m
3
/min
138
172
344
531
Type
Drip-Proof Type Enclosure
Starting Method
Permanent Split Capacitor
Nominal Output
W
275
275
275
275
Quantity
1
1
2
3
Fan U
n
it
Fan
Motor
Insulation Class
E
E
E
E
2.3.9.
COMPRESSOR
Model
G402DHV G402DHVM G401DHM G501DHM G601DHM G404DHD
G603DH
G750EH
G1200EH
Compressor type
Hermetic Scroll Type
Discharge
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
Air Tight
Pressure
Suction
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
Starting
Method
Inverter-Driven (I.D.)
Direct-on-Line
3~ Synchronous
Motor (I.D.)
Three-Phase Induction Motor
D.O.L.
Poles
2
2
2
2
2
2
2
2
2
Motor Type
Insulation
Class
E
E
E
E
E
E
E
E
E
Com
p
ressor
Oil Type
FVB68DX3
FVB68D
Summary of Contents for FSG Series
Page 2: ......
Page 4: ......
Page 13: ...3 57 7 1 7 ...
Page 14: ......
Page 110: ......
Page 116: ......
Page 146: ......
Page 160: ...9 14 CONTROL SYSTEM n Cooling Operation FSG FSG1 cont ...
Page 162: ...9 16 CONTROL SYSTEM n Cooling mainly Cooling Operation FXG FXG1 cont ...
Page 163: ...CONTROL SYSTEM 9 17 9 6 3 DRY OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Page 164: ...9 18 CONTROL SYSTEM n Dry Operation FSG FSG1 cont ...
Page 165: ...CONTROL SYSTEM 9 19 9 6 4 DRY OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Page 166: ...9 20 CONTROL SYSTEM n Dry Operation FXG FXG1 cont ...
Page 167: ...CONTROL SYSTEM 9 21 9 6 5 HEATING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Page 168: ...9 22 CONTROL SYSTEM n Heating Operation FSG FSG1 cont ...
Page 170: ...9 24 CONTROL SYSTEM n Heating mainly Heating Operation FXG FXG1 cont ...
Page 171: ...CONTROL SYSTEM 9 25 n Defrosting Operation Control ...
Page 173: ...CONTROL SYSTEM 9 27 9 7 2 GAS BYPASS CONTROL 9 7 3 OVER HEATING PROTECTION CONTROL ...
Page 176: ...9 30 CONTROL SYSTEM 9 7 6 CONTROL FOR AUTO COOL HEAT OPERATION ...
Page 228: ......
Page 229: ...3 57 167 7 21 7 ...
Page 230: ......
Page 324: ......
Page 344: ......
Page 376: ......
Page 423: ......