INSTALLATION OF OPTIONAL REMOTE CONTROLLER
16
/29
16.8.3
ELECTRICAL WIRING
1. Turn OFF the main power switch connected to the wire of
HARC-BX E and the surrounding equipment to connect
wire.
2. Wiring work should be conducted according to the table
described below. The “No.” showing in the table indicates
the wire of “Wiring Method”.
n
Electrical Wiring
Section
No.
Wiring Method
Remarks
1~220/240V
power
Source
HARC-BX E
¡
Power Line
Earthling
Wire
¢
Upper
System
Monitoring
Equip.
HARC-BX E
£
Non-polar
Control Circuit
HARC-BX E
Package Air
Conditioner
¤
Non-polar
16.8.4
ARRANGEMENT OF THE INSTALLATION
OF PCB AND H-LINK TERMINALS
As described in the figure below, 8 PCBs which are built into
HARC-BX E and H-LINK Terminals correspond to the both
sides of the same numbers, 1 to 8 within
and
respectively.
In order that PCB would be able to communicate with unit it
must be connected to same H-LINK than unit.
16.8.5
MAINTENANCE AND SERVICE
n
Self-Inspection for HARC-BX E
Self-Inspection to identify the abnormality of HARC-BX E
can be conducted by the following procedures.
1. Turn OFF all the pins for DSW S201 and DSW S202
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
8 Pins DSW (S201)
8 Pins DSW (S202)
2. Turn ON power supply.
The 7-Segment shows “
88
” and is lit OFF).
3. Turn ON only No. 1 pin of DSW S201
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
8 Pins DSW (S201)
8 Pins DSW (S202)
With this setting, communication between HARC PCB and
LONWORKS is performed,
7-Segment Display
Results are the
following:
-
OK
Abnormal
In case of abnormality either there is some problem with
LONWORKS network or HARC PCB is damaged.
4. Turn OFF No. 1 pin of 8-pin DSW S201, and turn ON
only No. 2 pin
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
8 Pins DSW (S201)
8 Pins DSW (S202)
7-Segment Display
Results are the
following:
-
OK
Abnormal
In case of abnormality either there is some problem with
H-Link line (incorrect wiring or incorrect end resistance
setting) or HARC PCB is damaged.
5. Turn OFF No. 2 pin of 8-pin DSW S201, and turn ON
only No. 3 pin.
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
8 Pins DSW (S201)
8 Pins DSW (S202)
With this setting, checking of DSW S202 Pins Nos. 1 to 5 is
performed. Number is showing the number of pins set to
ON.
Results are the following:
! ! ! ! ! ! " ! #
0 pin
1 pin
2 pin
3 pin
4 pin
5 pin
In case of abnormality, HARC PCB is damaged.
Summary of Contents for FSG Series
Page 2: ......
Page 4: ......
Page 13: ...3 57 7 1 7 ...
Page 14: ......
Page 110: ......
Page 116: ......
Page 146: ......
Page 160: ...9 14 CONTROL SYSTEM n Cooling Operation FSG FSG1 cont ...
Page 162: ...9 16 CONTROL SYSTEM n Cooling mainly Cooling Operation FXG FXG1 cont ...
Page 163: ...CONTROL SYSTEM 9 17 9 6 3 DRY OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Page 164: ...9 18 CONTROL SYSTEM n Dry Operation FSG FSG1 cont ...
Page 165: ...CONTROL SYSTEM 9 19 9 6 4 DRY OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Page 166: ...9 20 CONTROL SYSTEM n Dry Operation FXG FXG1 cont ...
Page 167: ...CONTROL SYSTEM 9 21 9 6 5 HEATING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Page 168: ...9 22 CONTROL SYSTEM n Heating Operation FSG FSG1 cont ...
Page 170: ...9 24 CONTROL SYSTEM n Heating mainly Heating Operation FXG FXG1 cont ...
Page 171: ...CONTROL SYSTEM 9 25 n Defrosting Operation Control ...
Page 173: ...CONTROL SYSTEM 9 27 9 7 2 GAS BYPASS CONTROL 9 7 3 OVER HEATING PROTECTION CONTROL ...
Page 176: ...9 30 CONTROL SYSTEM 9 7 6 CONTROL FOR AUTO COOL HEAT OPERATION ...
Page 228: ......
Page 229: ...3 57 167 7 21 7 ...
Page 230: ......
Page 324: ......
Page 344: ......
Page 376: ......
Page 423: ......