GENERAL DATA
2
/3
2.1.2.
RCD - 2-WAY-CASSETTE TYPE
MODEL RCD
Units
RCD-1.0
RCD-1.5
RCD-2.0
RCD-2.5
RCD-3.0
RCD-4.0
RCD-5.0
Nominal Cooling Capacity
W
2 800
4 300
5 600
7 100
8 400
11 200
14 200
Nominal Heating Capacity
W
3 300
4 900
6 500
8 100
9 600
13 000
16 300
Air Flow Rate (Hi/Me/Lo)
m
3
/min
8/7/6
12/10/8.5
15/13/11/11
18/15.5/13.5
22/19/16
30/26/23
32/29/25
Fan Motor
W
35
35
35
55
55
35x2
35x2
Sound Pressure Level
(Overall A Scale)
dB (A)
34/32/30
35/32/30
35/32/30
38/34/31
40/36/33
40/36/33
43/40/36
Height
mm
298
298
298
298
298
298
298
Width
mm
860
860
860
860
860
1420
1420
Outer Dimensions
Depth
mm
620
620
620
620
620
620
620
Net Weight
kg
27
27
27
30
30
48
48
Refrigerant
R407C (Nitrogen Charged in Factory for Corrosion-Resistance)
Connections
Refrigerant Piping
Flare-nut Connection (With Flare-Nuts)
Liquid Line
mm (in.)
6.35 (1/4)
6.35 (1/4)
6.35 (1/4)
9.53 (3/8)
9.53 (3/8)
9.53 (3/8)
9.53 (3/8)
Gas Line
mm (in.)
12.7 (1/2)
12.7 (1/2)
15.88 (5/8)
15.88 (5/8)
15.88 (5/8)
19.05 (3/4)
19.05 (3/4)
Condensate Drain
mm
Ø32 OD
Ø32 OD
Ø32 OD
Ø32 OD
Ø32 OD
Ø32 OD
Ø32 OD
Packing Measurements
m
3
0.23
0.23
0.23
0.23
0.23
0.37
0.37
Standard accessories
-
Suspension Brackets
Adaptable Air Panel Model
P-G23DWA1
P-G46DWA1
Color (Munsell Code)
Silky White
Height
mm
30+10
30+10
30+10
30+10
30+10
30+10
30+10
Width
mm
1100
1100
1100
1100
1100
1660
1660
Outer Dimensions
Depth
mm
710
710
710
710
710
710
710
Net Weight
kg
6
6
6
6
6
8
8
Packing Measurements
m
3
0.10
0.10
0.10
0.10
0.10
0.15
0.15
Optional Accessories
-
Remote Control Switch PC-P1HE or PC-2H2
OD: Outer Diameter
?
NOTE:
1. The nominal cooling and heating capacity is the
combined capacity of the HITACHI standard split
system, and are based on the JIS 158616.
Operation Conditions
Cooling
Heating
DB
27.0 °C
20.0 °C
Indoor Air Inlet Temperature
WB
19.0 °C
DB
35.0 °C
7.0 °C
Outdoor Air Inlet Temperature
WB
6.0 °C
Piping Length
: 7.5 meters;
Piping Lift
: 0 meter
DB
: Dry Bulb;
WB
: Wet Bulb
2. The Sound Pressure Level is based on the following
conditions:
– 1.5 meters beneath the Unit
– Voltage of the power source for the indoor fan motor
is 220V.
The above data was measured in an anechoic chamber
so that reflected sound should be taken into
consideration when installing the unit.
3. For more information about capacities, see chapter 4.
4. Panels P-G23DWA1 and P-G46WA1 are equipped with
an automatic swing louver system.
Summary of Contents for FSG Series
Page 2: ......
Page 4: ......
Page 13: ...3 57 7 1 7 ...
Page 14: ......
Page 110: ......
Page 116: ......
Page 146: ......
Page 160: ...9 14 CONTROL SYSTEM n Cooling Operation FSG FSG1 cont ...
Page 162: ...9 16 CONTROL SYSTEM n Cooling mainly Cooling Operation FXG FXG1 cont ...
Page 163: ...CONTROL SYSTEM 9 17 9 6 3 DRY OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Page 164: ...9 18 CONTROL SYSTEM n Dry Operation FSG FSG1 cont ...
Page 165: ...CONTROL SYSTEM 9 19 9 6 4 DRY OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Page 166: ...9 20 CONTROL SYSTEM n Dry Operation FXG FXG1 cont ...
Page 167: ...CONTROL SYSTEM 9 21 9 6 5 HEATING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Page 168: ...9 22 CONTROL SYSTEM n Heating Operation FSG FSG1 cont ...
Page 170: ...9 24 CONTROL SYSTEM n Heating mainly Heating Operation FXG FXG1 cont ...
Page 171: ...CONTROL SYSTEM 9 25 n Defrosting Operation Control ...
Page 173: ...CONTROL SYSTEM 9 27 9 7 2 GAS BYPASS CONTROL 9 7 3 OVER HEATING PROTECTION CONTROL ...
Page 176: ...9 30 CONTROL SYSTEM 9 7 6 CONTROL FOR AUTO COOL HEAT OPERATION ...
Page 228: ......
Page 229: ...3 57 167 7 21 7 ...
Page 230: ......
Page 324: ......
Page 344: ......
Page 376: ......
Page 423: ......