UNITS INSTALLATION
12
/21
12.8
RAS (OUTDOOR UNIT)
12.8.1
INSTALLATION LOCATION (5 TO 10 HP)
n
Installation Place
§
Install the outdoor unit in a place where there is
adequate space around the unit for operating and
maintenance as shown below.
*
Add the half of dimension h1 to 300mm for air intake space of rear
side, when the wall of rear side is higher than 500mm.
*
Add the half of dimension h2 to 1500 for air intake space of front
side when the wall front side is higher than 1500 mm
§
Install the outdoor unit where a good ventilation is
available.
§
Install the outdoor unit where it is in the shade or it will
not be exposed to direct sunshine or direct radiation
from high temperature heat source.
§
Install the outdoor unit where the falling ice from the
unit will not create a hazard, as in the case of
installation on top of a building where ice may fall
down on the pedestrians.
§
Install the outdoor unit where the sound or discharge
air from the outdoor unit does not affect neighbors or
environment.
§
Check to ensure that the foundation is flat and
sufficiently strong.
§
Do not install the outdoor unit where dust or other
contamination could block the outdoor heat
exchanger.
§
When installing the outdoor unit in snow-covered
areas, mount the field-supplied hoods on the top of the
outdoor unit and the inlet side of the heat exchanger.
§
Do not install the outdoor unit where there are high-
levels of oil mist, salty air or aggressive gases such as
sulfur.
§
Do not install the outdoor unit where electromagnetic
waves are directly radiated to the electrical box and
inverter components.
§
Install the outdoor unit as far as practical at least 3
meters from the electromagnetic wave radiation, as
electronic noise can cause miss-operation of the unit.
?
NOTE:
In certain cases, a fuse may be blown and the system
my stop in high electro-magnetic turbulence
environment.
In certain cases, the system can get an alarm in high
electro-magnetic turbulence environment. In such
case, stop and start the system to clear the alarm.
&
CAUTION:
Aluminum fins have very sharp edges. Pay attention
to the fins to avoid any injury.
?
NOTE:
Install the outdoor unit on a roof or in an area where
people except service engineers can not touch the
outdoor unit.
■
Basic Space
12.8.2
INSTALLATION SPACE FOR SINGLE UNIT
§
In case that the front side and either of the sides are
open.
Rear Side Intake Space
Front Side Intake Space
(Top View)
(mm)
Air Intake
Side View
No Limit to Wall Height
(mm)
Front
Side
Summary of Contents for FSG Series
Page 2: ......
Page 4: ......
Page 13: ...3 57 7 1 7 ...
Page 14: ......
Page 110: ......
Page 116: ......
Page 146: ......
Page 160: ...9 14 CONTROL SYSTEM n Cooling Operation FSG FSG1 cont ...
Page 162: ...9 16 CONTROL SYSTEM n Cooling mainly Cooling Operation FXG FXG1 cont ...
Page 163: ...CONTROL SYSTEM 9 17 9 6 3 DRY OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Page 164: ...9 18 CONTROL SYSTEM n Dry Operation FSG FSG1 cont ...
Page 165: ...CONTROL SYSTEM 9 19 9 6 4 DRY OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Page 166: ...9 20 CONTROL SYSTEM n Dry Operation FXG FXG1 cont ...
Page 167: ...CONTROL SYSTEM 9 21 9 6 5 HEATING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Page 168: ...9 22 CONTROL SYSTEM n Heating Operation FSG FSG1 cont ...
Page 170: ...9 24 CONTROL SYSTEM n Heating mainly Heating Operation FXG FXG1 cont ...
Page 171: ...CONTROL SYSTEM 9 25 n Defrosting Operation Control ...
Page 173: ...CONTROL SYSTEM 9 27 9 7 2 GAS BYPASS CONTROL 9 7 3 OVER HEATING PROTECTION CONTROL ...
Page 176: ...9 30 CONTROL SYSTEM 9 7 6 CONTROL FOR AUTO COOL HEAT OPERATION ...
Page 228: ......
Page 229: ...3 57 167 7 21 7 ...
Page 230: ......
Page 324: ......
Page 344: ......
Page 376: ......
Page 423: ......