GENERAL DATA
2
/7
2.1.6.
RPK - WALL TYPE
MODEL RPK
Units
RPK-1.0
RPK-1.5
RPK-2.0
RPK-2.3
Nominal Cooling Capacity
W
2 800
4 300
5 600
6 500
Nominal Heating Capacity
W
3 300
4 900
6 500
7 500
Indoor Fan
Air Flow Rate (Hi/Me/Lo)
m³/min
12/10/8
14/12/10
15/13/11
16/14/12
Fan Motor
W
15
15
15
15
Sound Pressure Level
(Overall A Scale) (Hi/Me/Lo)
dB (A)
37-34-31
41-37-34
42-38-36
43-39-37
Outer Dimensions
Height
mm
298
298
298
298
Width
mm
1,090
1,090
1,090
1,090
Depth
mm
193
193
193
193
Net Weight
kg
14
14
14
14
Color (Munsell Code)
Pearl White (N9.25)
Refrigerant
R407C (Nitrogen-Charged for Corrosion-Resistance)
Connections
Flare-Nut Connection (With Flare Nuts)
Refrigerant Piping
Liquid Line
mm
(in.)
Ø6.35
(1/4)
Ø6.35
(1/4)
Ø6.35
(1/4)
Ø6.35
(1/4)
Gas Line
mm
(in.)
Ø12.7
(1/2)
Ø12.7
(1/2)
Ø15.88
(5/8)
Ø15.88
(5/8)
Condensate Drain
Ø26 OD
Ø26 OD
Ø26 OD
Ø26 OD
Approximate
Packing Measurement
m³
0.12
0.12
0.12
0.12
Optional Accessories
Remote Control Switch PC-P1HE
OD: Outer Diameter
?
NOTE:
1. The nominal cooling and heating capacity is the
combined capacity of the HITACHI standard split
system, and are based on the JIS 158616.
Operation Conditions
Cooling
Heating
DB
27.0 °C
20.0 °C
Indoor Air Inlet Temperature
WB
19.0 °C
DB
35.0 °C
7.0 °C
Outdoor Air Inlet Temperature
WB
6.0 °C
Piping Length
: 7.5 meters;
Piping Lift
: 0 meter
DB
: Dry Bulb;
WB
: Wet Bulb
2. The Sound Pressure Level is based on the following
conditions:
– 1 meter beneath the Unit
– Voltage of the power source for the indoor fan motor
is 220V.
The above data was measured in an anechoic chamber
so that reflected sound should be taken into
consideration when installing the unit.
3. For more information about capacities, see chapter 4.
Summary of Contents for FSG Series
Page 2: ......
Page 4: ......
Page 13: ...3 57 7 1 7 ...
Page 14: ......
Page 110: ......
Page 116: ......
Page 146: ......
Page 160: ...9 14 CONTROL SYSTEM n Cooling Operation FSG FSG1 cont ...
Page 162: ...9 16 CONTROL SYSTEM n Cooling mainly Cooling Operation FXG FXG1 cont ...
Page 163: ...CONTROL SYSTEM 9 17 9 6 3 DRY OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Page 164: ...9 18 CONTROL SYSTEM n Dry Operation FSG FSG1 cont ...
Page 165: ...CONTROL SYSTEM 9 19 9 6 4 DRY OPERATION FXG FXG1 I U Indoor Unit O U Outdoor Unit ...
Page 166: ...9 20 CONTROL SYSTEM n Dry Operation FXG FXG1 cont ...
Page 167: ...CONTROL SYSTEM 9 21 9 6 5 HEATING OPERATION FSG FSG1 I U Indoor Unit O U Outdoor Unit ...
Page 168: ...9 22 CONTROL SYSTEM n Heating Operation FSG FSG1 cont ...
Page 170: ...9 24 CONTROL SYSTEM n Heating mainly Heating Operation FXG FXG1 cont ...
Page 171: ...CONTROL SYSTEM 9 25 n Defrosting Operation Control ...
Page 173: ...CONTROL SYSTEM 9 27 9 7 2 GAS BYPASS CONTROL 9 7 3 OVER HEATING PROTECTION CONTROL ...
Page 176: ...9 30 CONTROL SYSTEM 9 7 6 CONTROL FOR AUTO COOL HEAT OPERATION ...
Page 228: ......
Page 229: ...3 57 167 7 21 7 ...
Page 230: ......
Page 324: ......
Page 344: ......
Page 376: ......
Page 423: ......