4. TROUBLESHOOTING [Protective Device]
■
Others
LCD Indication
What and How to Detect
Failure
Light
Detector Shutdown
What Actions to Take
How to
Reset
History
code
Error
code
Heading
Trouble Description
PROBLEM
Battery out (BATTERY OUT)
Battery voltage low
ALARM
Blinks
CPU
No
Disconnect the power and replace the
battery with a new one.
9.4 (12)
.
Press
RESET
button.
64
E0.64
Scheduling operation error
(SCHEDULE SET ERR)
Start/stop time not set
yet
ALARM
Blinks
CPU
No
See
3.3.5 (4)
Press
RESET
button.
62
E0.62
Lead/lag operation error
(MULTI-U SET ERR)
Setting error
ALARM
Blinks
CPU
No
Check the wire and the operation setting
on the instrument panel.
Press
RESET
button.
5B
E0.5B
RS-485 port error
(COM.ERR STOP) NOTE 3
Setting error
SHUTDOWN
Blinks
Thermistor
Yes
Check the wire and the operation setting.
Press
RESET
button.
63 65
〜
68
E0.63 65
〜
68
RS-485 port error
(COM.ERR ALM) NOTE 3
Setting error
ALARM
Blinks
Pressure
sensor
Yes
Check the wire and the operation
setting.
Press
RESET
button.
63 65
〜
68
E0.63 65
〜
68
FAILURE
PCB error
(PCB ERR)
(ROM1) (RAM1) main
board memory error
SHUTDOWN
Blinks
CPU
Yes
Disconnect the power and then reconnect the
power. If problem is persists, change the PCB.
Press
RESET
button.
43
47, 48
E0.43
47, 48
(ROM2) (RAM2) LCD
board memory error
SHUTDOWN
Blinks
CPU
Yes
Disconnect the power and then reconnect the
power. If problem is persists, change the PCB.
Press
RESET
button.
41, 42
46
E0.41,
42 46
Interstage pressure sensor error
(PRESS. SNSR ERR 1)
PS1 disconnected
SHUTDOWN
Blinks
CPU
Yes
Disconnect the power and check the
pressure sensor wire for tightness.
Press
RESET
button.
33
E0.33
Discharge pressure sensor error
(PRESS. SNSR ERR 2)
PS2 disconnected
SHUTDOWN
Blinks
CPU
Yes
Press
RESET
button.
34
E0.34
Oil pressure sensor error
(PRESS. SNSR ERR 4)
PS4 disconnected
SHUTDOWN
Blinks
CPU
Yes
Press
RESET
button.
39
E0.39
2nd stage inlet
temperature sensor error
(TEMP. SNSR ERR 2)
TH2 disconnected
SHUTDOWN
Blinks
CPU
Yes
Press
RESET
button.
32
E0.32
1st stage outlet
temperature sensor error
(TEMP. SNSR ERR 3)
TH3 disconnected
SHUTDOWN
Blinks
CPU
Yes
Disconnect the power and check the
thermistor sensor wire for tightness.
Press
RESET
button.
35
E0.35
2nd stage outlet
temperature sensor error
(TEMP. SNSR ERR 4)
TH4 disconnected
SHUTDOWN
Blinks
CPU
Yes
Press
RESET
button.
36
E0.36
Oil temperature sensor error
(TEMP. SNSR ERR 5)
TH5 disconnected
SHUTDOWN
Blinks
CPU
Yes
Press
RESET
button.
37
E0.37
NOTES:
(1) Depends on the specification, reverse phase relay is used.
(2) The air compressor using reverse phase relay, such as for 460 V/60 Hz, indicates a phase-lacking connection as reversal phase.
(3) Communication error details:
Port 1(65) =Main circuit communication (Vtype), Port 2 (66)=Fan inverter communication (Air-cooled model)
Port 3 (67)= LCD communication, Port 4 (68)= Multiple unit control communication, Port 5 (63)= External communication
■
During Operation
LCD Indication
What and How to Detect
Failure
Light
Detector Shutdown
What Actions to Take
How to Reset
History
code
Error
code
Heading
Trouble Description
ALARM
Clogging of air intake filter
(AIR FILTER)
Pressure differential of -0.72
psi 4.98 kPa or more
ALARM
Blinks
Pressure
differential
sensor
No
9.4
Press
RESET
button.
21
E0.21
1st stage discharge air
temperature (DIS. TEMP. 1)
About 428 [410]
℉
220 [210]
℃
or higher
ALARM
Blinks
Thermistor
No
4.2
Automatically
reset.
25
E0.25
1st stage discharge air
temperature (DIS. TEMP. 1)
The temperature detected at
1st stage rises above the below
settings.
ALARM
Blinks
Thermistor
No
4.2
Automatically
reset.
25
E0.25
100 psi model
0.69MPa model
about 437
℉
[
about 410
℉
]
about 225
℃
[
about 210
℃
]
125 psi model
0.86MPa model
2nd stage discharge air
temperature (DIS. TEMP. 2)
●
For working pressure of
100psi 0.69MPa model
: About
437 [419]
℉
225 [215]
℃
or higher
●
For working pressure of
125psi 0.86MPa model : About
491 [473]
℉
255[245]
℃
or higher
ALARM
Blinks
Thermistor
No
4.2
Automatically
reset.
26
E0.26
2nd stage suction air
temperature (2ND-S. TEMP)
154 [149]
℉
68 [65]
℃
or higher
ALARM
Blinks
Thermistor
No
4.2
Automatically
reset.
2B
E0.2B
Oil temperature (OIL TEMP)
154 [149]
℉
68 [65]
℃
or higher
ALARM
Blinks
Thermistor
No
4.2
Automatically
reset.
26
E0.26
[Fixed Speed type]
Oil pressure (LOW O.P.)
15 psi 0.10MPa or lower
ALARM
Blinks
Pressure
sensor
No
4.2
Automatically
reset.
2C
E0.2C
Load/unload cycle time
over (L COUNT OVER)
1,000,000 cycles
ALARM
Blinks
CPU
No
Replace suction throttle valve
consumable parts and Blow
off solenoid valves
Hold down the
REMOTE
and
press the
SELECT/WIDE
button for 7
seconds or more.
59
E0.59