7
WARNING
Safety precautions
17.
Competence of service personnel
Information and training
The training should include the substance of the following:
Information about the explosion potential of flammable refrigerants to show that flammables may be dangerous
when handled without care.
Information about potential ignition sources, especially those that are not obvious, such as lighters, light
switches, vacuum cleaners, electric heaters.
Information about the concept of sealed components and sealed enclosures according to IEC 60079-15:2010.
Information about the correct working procedures:
a) Commissioning
• Ensure that the floor area is sufficient for the refrigerant charge or that the ventilation duct is assembled in a
correct manner.
• Connect the pipes and carry out a leak test before charging with refrigerant.
• Check safety equipment before putting into service.
b) Maintenance
• Portable equipment shall be repaired outside on in a workshop specially equipped for servicing units with
flammable refrigerants.
• Ensure sufficient ventilation at the repair place.
• Be aware that malfunction of the equipment may be caused by refrigerant loss and a refrigerant leak is possible.
• Discharge capacitors in a way that won't cause any spark. The standard procedure to short circuit the capacitor
terminals usually creates sparks.
• Reassemble sealed enclosures accurately If seals are worn, replace them.
• Check safety equipment before putting into service.
c) Repair
• Portable equipment shall be repaired outside or in a workshop specially equipped for servicing units with
flammable refrigerants.
• Ensure sufficient ventilation at the repair place.
• Be aware that of the equipment may be caused by refrigerant loss and a refrigerant leak is possible.
• Discharge capacitors in a way that won't cause any spark.
• When brazing is required the following procedures shall be carried out in the right order.
- Remove the refrigerant. If the refrigerant is not required by national regulations, drain the refrigerant to the
outside. Take care that the drained refrigerant will not cause any danger. In doubt, one person should guard the
outlet. Take special care that drained refrigerant will not float back into the building.
- Evacuate the refrigerant circuit.
- Purge the refrigerant circuit with nitrogen for 5 min .
- Evacuate again (not required for A2L refrigerants)
- Remove parts to be replaced by cutting, not by flame.
- Purge the braze point with nitrogen during the brazing procedure.
- Carry out a leak test before charging with refrigerant.
● Reassemble sealed enclosures accurately. If seals are worn, replace them.
● Check safety equipment before putting into service.
d) Decommissioning
• If the safety is affected when the equipment is putted out of service. the refrigerant charge shall be removed
before decommissioning.
• Ensure sufficient ventilation at the equipment location.
• Be aware that malfunction of the equipment may be caused by refrigerant loss and a leak is possible.
• Discharge capacitors in a way that won't cause any spark.
• Remove the If the recovery is not required by national regulations, drain the refrigerant to the outside. Take
care that the drained refrigerant will not cause any danger. In doubt, one person should guard the outlet .Take
special care that drained refrigerant will not float back into the building.
e) Disposal
• Ensure sufficient ventilation at the working place.
• Remove the refrigerant. If the recovery is not required by national regulations, drain the refrigerant to the outside.
Take care that the drained refrigerant will not cause any danger. In doubt, one person should guard the outlet.
Take special care that drained refrigerant will not float back into the building.
• Evacuate the refrigerant circuit
• Purge the refrigerant circuit with nitrogen for 5min.
• Evacuate again.
• Cut out the compressor and drain the oil.