Safety precautions
·
Perform grounding
Does not connect the earth wire to a gas pipe, water pipe, lightning rod or telephone earth wire.
Defective grounding could cause an electric shock.
·
Do not install the unit in a place where an inflammable gas leaks.
If gas leaks and accumulates in the area surrounding the unit, it could cause an explosion.
·
Fasten a flare nut with a torque wrench as specified in this manual.
When fastened too tight, a flare nut may break after a long period and cause a leakage of refrigerant.
·
Install an earth leakage breaker depending on the installation place (where it is humid).
If an earth leakage breaker is not installed, it could cause an electric shock.
·
Perform the drainage/ piping work securely according to the installation manual.
·
If there is a defect in the drainage/piping work, water could drops from the unit and household goods
could be wet and damaged.
C
AUTION
2
·
Do not let air enter the refrigeration system or discharge refrigerant when moving the air conditioner.
·
The installation instructions for appliances that are intended to be permanently connected to fixed
wiring, and have a leakage current that may exceed 10mA, shall state that the installation of a
residual current device (RCD) having a rated residual operating current not exceeding 30mA is
advisable.
·
This appliance can be used by children aged from 8 years and above and persons with reduced
physical, sensory or mental capabilities or lack of experience and knowledge if they have been given
supervision or instruction concerning use of the appliance in a safe way and understand the hazards
involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be
made by children without supervision.
·
If the supply cord is damaged, it must be replaced by the factory or its service department to avoid
danger.
·
Servicing shall only be performed as recommended by the equipment manufacturer.
·
Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under
the supervision of the person competent in the use of flammable refrigerants.
·
Means for disconnection, which can provide full disconnection in all poles, must be incorporated in
the fixed wiring in accordance with the wiring rules.
·
It is necessary to allow the disconnection of the appliance from the supply after installation. Make
sure the disconnection of the appliance from the supply when service and maintenance, a
disconnection with a locking system in the isolated position shall be provided.
·
The method of connection of the appliance to the electrical supply and interconnection of separate
components, and the wiring diagram with a clear indication of the connections and wiring to external
control devices and supply cord are detailed below.
·
Power connection and interconnection between outdoor unit and indoor unit should be conducted with
the power cord of the H07RN-F type or the electrically equivalent type. The size of the power cord is
detailed in outdoor unit manual below.
·
Type and rating of circuit breakers / ELB are detailed below.
·
The information on dimensions of the space necessary for correct installation of the appliance
including the minimum permissible distances to adjacent structures is detailed below.
·
This appliance is intended to be used by expert or trained users in shops, in light industry and on
farms, or for commercial use by lay persons.
·
In order to avoid a hazard due to inadvertent resetting of the thermal cut-out, this appliance must not
be supplied through an external switching device, such as a timer, or connected to a circuit that is
regularly switched on and off by the utility.
·
Instructions on additional charging of refrigerants are detailed below.
Safety instructions