Part n° 890-00487 rev.00
Evolution Bird Scale Controller
9
3.
INSTALLATION
3.1 Mounting Instructions
Open the latch and lift the cover. Remove the black caps located on each
of the four mounting holes. Mount the enclosure on the wall using four
screws. Be sure the electrical knockouts are at the bottom of the enclo-
sure in order to prevent water from entering the controller. Insert the
screws in the mounting holes and tighten. Fasten the four black caps
provided with the controller onto the four mounting holes. The enclosure
must be mounted in a location that will allow the cover to be completely
opened right up against the wall.
3.2 Connections
To connect the controller, refer to the wiring diagram enclosed with this
user's manual. Use the electrical knockouts provided at the bottom of the
enclosure. Do not make additional holes in the enclosure, particularly on
the side of the enclosure when using a computer communications module.
Refer to the wiring diagram enclosed with this user's manual to connect
the controller. Use the electrical knockouts provided at the bottom of the
enclosure. Do not make additional holes in the enclosure, particularly on
the side of the enclosure when using a computer communication module.
All wiring must be done by an authorized electrician and must
comply with applicable codes, laws and regulations. Be sure
power is off before doing any wiring to avoid electrical shocks
and equipment damage.
Do not install rigid conduit into electrical knockouts. Only nylon
cable glands are permitted for cable or wire fastening.
The controller has no power-on switch. An external switch or
circuit breaker shall be included in the building installation to
interrupt power to L and N electric power lines. It shall be in
close proximity to the equipment and within easy reach of the
operator. It shall be marked as the disconnecting device for the
equipment.