![Hioki CM3286-50 Instruction Manual Download Page 88](http://html1.mh-extra.com/html/hioki/cm3286-50/cm3286-50_instruction-manual_2137248088.webp)
82
Specifications
Range (minimum
resolution)
AC current
600.0 A
(0.1 A)
60.00 A
(0.01 A)
6.000 A
(0.001 A)
AC voltage
600.0 V (0.1 V)
Accuracy input range
Input of 1% of range or greater for each order
Crest factor
3 or less for the 6 A and 60 A current ranges
1.6 or less for the 600 A current range and the 600 V voltage range
Data refresh
5 s (reference value)
Measurement accuracy
Harmonic level
(RMS value)
Order
Accuracy
1 to 10
±5.0% rdg ±10 dgt
11 to 20
±10% rdg ±10 dgt
21 to 30
±20% rdg ±10 dgt
Harmonic content
percentage
±1 dgt for calculations performed using measured values
Total harmonic
distortion
±1 dgt for calculations performed using measured values