81
Specifications
Harmonic measurement specifications (with Z3210 connected)
All operations are performed by the GENNECT Cross application software. The following specifications apply
only to use of the GENNECT Cross’s harmonic analysis functionality. Perform sampling of data by instrument
and harmonic analysis calculations by GENNECT Cross.
Measurement
conditions
Fundamental frequency 50 Hz/60 Hz
Measurement
functionality
AC current/AC voltage (controlled by application software)
Analysis window width
1 cycle (50 Hz/60 Hz)
Window type
Rectangular
Number of data points
analyzed
256
Orders analyzed
1st to 30th
Items analyzed
Harmonic level
(RMS values for current harmonics [A]
,
RMS values for voltage harmonics [V])
Harmonic content percentage
(content percentages for current harmonics [%]
,
content percentages for voltage
harmonics [%])
Total harmonic distortion
(THD-F and THD-R for current [%]
,
THD-F and THD-R for voltage [%])
HIOKI CM3286C961-00