7.3
Online Diagnosis
The online view in the SILworX Hardware Editor is used to diagnose failures in the HIQuad X
modules. Failed modules are signalized by a color change:
Red indicates severe failures, e.g., that the module is not inserted.
Yellow indicates less severe failures, e.g., that the temperature limit has been exceeded.
Point to a module to display a tooltip providing the following state information on the module:
Information
Representatio
n
Range of values
Description
SRS
Decimals
System: 0...65 535
Rack: 0...16
Slot: 1...18
Module identification: System, Rack, Slot
Name
Text
Designation of the information , here always: Online
MODULE Information.
Module state
Text
RUN, STOP, NOT
CONNECTED,
Unknown, ...
State in which the I/O processing module is
operating.
Plugged Module
Type
Text
Permissible
module types
Type of module which is plugged into the rack.
Configured Module
Type
Text
Permissible
module types
Type of module which is configured and loaded in the
controller.
Module Type in
Project
Text
Permissible
module types
Type of module which is being projected as the
digital depiction.
Connection Status
of the Protocol
Hexadecimal
value
16#00...0F
Status of the connection between each of the
processor modules (max. of 2) and the I/O
processing module. Each of the bits 0...3 shows the
connection to the processor module with the
corresponding index.
Bit x = 0: Not connected.
Bit x = 1: Connected.
Interface Send
Status
Hexadecimal
value
16#0000...FFFF
Every two bits represent the state of one interface
identified with an index 0...16. Bits 0 and 1 apply to
interface 0, and so on.
Value
Description
00
No message has been received or sent
yet, unknown status.
01
OK, no faults.
10
Last data received or sent was defective.
11
No faults during last
reception/transmission, one fault occurred
before.
Summary of Contents for HIQuad H41X
Page 1: ...Manual HIQuad X System Manual...
Page 109: ......