System variables
S
1)
Description
Data type
Systemtick HIGH
Systemtick LOW
Y
Revolving millisecond counter (64-bit).
UDINT
Temperature State [1]…[2]
N
Bit-
coded temperature state of processor modules 1…2:
Bit no.
State when the bit is set.
0
Temperature threshold 1 exceeded.
1
Temperature threshold 2 exceeded.
2
Incorrect temperature value.
BYTE
Remaining Global Force
Duration [ms]
Y
Time in ms until the time limit set for global forcing
expires.
DINT
Watchdog Time [ms]
Y
Maximum permissible duration of a RUN cycle in ms
(dependent on the controller family).
UDINT
Cycle Time, last [ms]
Y
Current cycle time.
UDINT
Cycle Time, max [ms]
N
Maximum cycle time in milliseconds.
UDINT
Cycle Time, min [ms]
N
Minimum cycle time in milliseconds.
UDINT
Cycle Time, average [ms]
N
Average cycle time in milliseconds.
UDINT
1)
The operating system handles the system parameter in a safety-related manner, yes (Y) or no (N).
Table 27: System Parameter for Input Variables