Product Description
System
Page 54 of 110
HI 803 211 E Rev. 1.01.00
The processor module is reset to
the factory settings (SRS,
network settings, etc.).
Connecting the supply voltage to the processor
module while the mode switch is set to Init.
Processor module stopped: A
valid configuration is available in
the memory.
Stopping the processor module using SILworX.
Autostart is disabled in the project
Mode switch is set to Stop and the
processor module starts by itself.
Processor module stopped: No
valid configuration is available in
the memory.
Processor module stopped: The
operating system is loaded in the
non-volatile memory.
Loading the operating system using SILworX.
From the STOP/VALID CONFIGURATION
state: SILworX command.
Applying the supply voltage, the following
conditions must be met:
A valid project configuration is loaded.
Autostart is enabled in the project
The mode switch is not set to Init.
The mode switch is set to Run if the
processor module starts by itself.
From the STOP/VALID CONFIGURATION
state: SILworX command SILworX.
Table 18 provides an overview of the operating system states and indicates the conditions for
entering them.