Configuring and using the fieldbus node
162/258
2. Opening the PROFINET configuration
Ø
Click the square to the right of Fieldbus interface.
Ê
The dialog box
Edit fieldbus interface node
opens.
Figure 108: Dialog “Edit fieldbus interface config node”
Ø
Configure the behaviour of the output signals of the fieldbus node
during the deploy process:
Select
Clear output signals on deploy
, if during deploy the fieldbus
node should set the output data received by the master to 0. In this
case, the Edge Gateway can signal 'no valid data' to the master.
If this option is cleared, the output data hold their last state during
deploy. In this case, the master has no information that the Edge
Gateway does not process the received data anymore.
Ø
Click
Open fieldbus configurator
.
Figure 109: Button Open fieldbus configurator