background image

www.hi-velocity.com

© 1995-2020 Energy Saving Products Ltd.

© 1995-2020 Energy Saving Products Ltd.

Piping the RBM

Only  refrigerant  grade  pipe  and  fittings  are  to  be  used  with 

the RBM Module. Plumbing fittings may contain wax or other 

contaminants which are detrimental to the proper operation of 

the system. Insulate the suction line with a minumum of 3/8” 

insulation. In high heat areas, a minimum of 1/2” insulation may 

be needed. If the lines are run in an area where temperatures 

could exceed 120°F or runs longer than 50’, then the liquid line 

may need to be insulated as well. Support the pipe every 5 feet, 

or whatever local code states.

Run the pipes in the most direct route possible, taking into 

account structural integrity, building details and local building 

codes. If the evaporator is located above the condenser, slope 

any horizontal runs toward the condenser. If the condenser is 

located above the evaporator, a P-trap must be installed at the 

bottom of the vertical riser. For long vertical risers, additional 

P-traps must be installed for every twenty feet. For lines running 

over 50’, a suction line accumulator must be installed. Lines 

running over 100’ are not recommended.

Pipe Sizing

Tables 01 and 02 contain line sizing information for the liquid 

and suction lines.

The sizes given in the above tables are only for general reference, if the 

condenser manufacture requires a different size than specified in 

Table 01

 

and

 Table 02

, their sizing shall be used whenever a discrepancy occurs.

Table 01 – Liquid Line sizes

Tons

Distance

1

1

1

2

2

2

1

2

3

3

1

2

4

5

1’–25’

1

4

1

4

5

16

3

8

3

8

3

8

3

8

1

2

26’–50’

5

16

5

16

3

8

3

8

1

2

1

2

1

2

1

2

51’–75’

3

8

3

8

3

8

1

2

1

2

1

2

1

2

1

2

76’–100’

3

8

3

8

1

2

1

2

1

2

1

2

1

2

1

2

Table 02 – Suction Line sizes

Tons

Distance

1

1

1

2

2

2

1

2

3

3

1

2

4

5

1’–25’

5

8

5

8

3

4

3

4

3

4

7

8

7

8

1

26’–50’

5

8

3

4

3

4

3

4

7

8

7

8

1

1

8

1

1

8

51’–75’

3

4

3

4

7

8

7

8

1

1

8

1

1

8

1

1

8

1

1

8

76’–100’

3

4

7

8

7

8

1

1

8

1

1

8

1

1

8

1

1

8

1

1

8

Outdoor Unit Installation

Locate the outdoor unit in a suitable location, as close as 

possible to the fan coil. Maintain the clearances recommended 

by the manufacturers of the outdoor unit, to ensure proper 

airflow. The outdoor unit must be installed level, in a properly 

supported location. A liquid line filter/drier is recommended to 

be installed.

Wiring – Outdoor Unit

Make all connections to the outdoor unit with rain tight 

conduit  and  fittings.  Most  building  codes  require  a  rain  tight 

disconnect switch at the outdoor unit as well (always check 

local codes). Run the proper size copper wires to the unit, and 

connect as per the manufacturer’s recommendations.

Ensure that the unit is setup for a TX system. If not, a hard 

start kit may be required.

Evacuating

The system must be brazed under a nitrogen purge to 

prevent oxidation of the pipe during the brazing process.  After 

the piping is installed and all components have been brazed 

together, a vacuum pump must be used to properly evacuate 

the system from both of the access ports to 1500 microns, to 

ensure system is free of contaminants.  Add refrigerant to the 

system to bring the pressure above zero psig. After allowing 

the refrigerant to absorb moisture, repeat the above procedure. 

Evacuate the system to 500 microns on the second evacuation, 

and ensure that the system holds at the vacuum pressure. If not, 

check for leaks and evacuate again. If the vacuum holds, add 

refrigerant to raise the pressure to 2 psig. At this point open 

service valves on pre-charged condensing units.

The use of an electronic leak detector is recommended, as it is 

more sensitive to small leaks under the low pressures.

Once the system has been determined clean and ready for 

charging, refrigerant can be added. The service valves on the 

condenser must be open at this point. Never leave the system 

unattended when charging. With the system running, slowly 

add refrigerant. The typical operating point of an RBM coil is 

that of a saturated suction temperature of 34-40°F at 100-115 

psig (1-4°C at 7-8 bar) and a suction line temperature of 38-

44°F  at  114-128  psig  (3-7°C  at  8-9  bar).  In  order  to  prevent 

overcharging during this stage, refrigerant should be added in 

steps. This will allow time for the system to settle and prevent 

‘overshooting’ the ideal charge. Condenser pressures and 

temperatures remain similar to those in a conventional forced 

air system.  It is recommended that the coil be charged on a 

high load day at the compressor’s highest speed.

Charging

Most  system  start  ups  require  only  an  adjustment  to  the 

refrigerant  level  of  the  system.  Should  further  refinement 

be  required,  the  TXV  may  be  adjusted.  A  clockwise  turn  of 

the superheat adjustment stem (the direction in which the 

cap is screwed on) will result in a closing of the valve while a 

counterclockwise turn (the direction in which the cap was 

unscrewed) will result in opening of the valve. Always note 

system conditions before adjusting the valve and allow 5 minutes 

for the system to settle before making any further adjustments. 

Never adjust the TXV more than one quarter turn at a time.

-7-

-7-

Important:

  

Failure  to  follow  the  proper 

evacuating  and  charging  procedures  may 

void warranty.

Module RBM

RBM Refrigerant Base Module Installation

Summary of Contents for RBM-100

Page 1: ...e Installation 052020 RBM Refrigerant Base Module Installation Manual Small Duct High Velocity Heating Cooling and Home Comfort Systems RBM 50 1 5 2 Tons RBM 70 2 5 3 Tons RBM 100 3 5 5 Tons Includes Pre Piped TXV Freeze Stat Service Access Ports T Mounting Brackets Double Sided Mounting Tape Hole Plugs 2 ...

Page 2: ......

Page 3: ...es can be used on any R 410A condenser if R 410A refrigerant components are used All Energy Saving Products R Series modules come standard with R 410A refrigerant components 3 3 The RBM module can be installed as a stand return air base for the fan coil or as a side mounted coil When the desired air inlet side has been determined the module can be adapted The module comes ready as left to up right...

Page 4: ...e unit 90 deg clockwise Fig 07 Fig 07 6 Replace the drain pan in new bottom location Fig 09 Fig 09 Fig 06 3 Slide out the air flow deflector plate Fig 06 Fig 08 5 Slide the air flow deflector plate back into the section it was removed from in the new orientation Fig 08 Fig 10 7 Remove round knock outs on the door to fit drain lines Plug previously used drain holes with provided plugs Fig 10 Insert...

Page 5: ... should always be used to make the first cut For this first cut do not use a saw blade longer than 5 125mm or damage to the coil can occur Return Air Cutouts Mounting Brackets Fig 12 TO AVOID DAMAGE After the first initial cut using the return air knockout s a metal shear must be used to make the return air cutout opening match more closely to the filter or return air ducting size to maximize flow...

Page 6: ...ring needs arise in which the outdoor unit is controlled through another means of wiring the Freeze Stat should be connected in series on the input side of the control wiring Refrigerant Bypass All RBM coils come with a pre installed check valve ready TX valve used for AC only or heat pump condensing units Third party TX valves may require a bypass check valve Fig 14 Bypass check valve 6 6 Freeze ...

Page 7: ...eck local codes Run the proper size copper wires to the unit and connect as per the manufacturer s recommendations Ensure that the unit is setup for a TX system If not a hard start kit may be required Evacuating The system must be brazed under a nitrogen purge to prevent oxidation of the pipe during the brazing process After the piping is installed and all components have been brazed together a va...

Page 8: ...ing brackets are located at the base of the unit for secure mounting The receiver is to be located on the liquid line of the system anywhere between the indoor and outdoor coils As the unit is of a bi flow design it does not matter which end faces towards the indoor coil The inlet outlet ports are constructed of steel and require the use of a 35 45 Silver Solder and Flux for brazing The use of sta...

Page 9: ...HV 70 71 LV 70 HE Z HE P HE B HE HV 100 101 Part Number 41090300050 41090300070 41090300100 Tons 1 1 5 2 0 5 3 7 0 kW 2 5 3 0 8 8 10 6 kW 3 5 5 0 12 3 17 6 kW Refrigerant Type R 410A R 410A R 410A TX Cooling MBH 2 18 24 5 3 7 0 kW 30 36 8 8 10 6 kW 42 60 12 3 17 6 kW Latent Cooling MBH 6 8 8 9 2 0 2 6 kW 11 7 13 7 3 4 4 0 kW 16 0 22 2 4 7 6 5 kW Fin Material Aluminum Aluminum Aluminum Tubing Mater...

Page 10: ...ain Conn Refrigerant Modules B C A D E F RBM 50 14 1 2 368mm 18 1 4 464mm 18 1 4 464mm 3 8 o d 7 8 o d 3 4 M CPVC RBM 70 19 1 2 495mm 18 1 4 464mm 18 1 4 464mm 3 8 o d 7 8 o d 3 4 M CPVC RBM 100 25 1 2 648mm 18 1 4 464mm 18 1 4 464mm 3 8 o d 7 8 o d 3 4 M CPVC RBM Series Sizing A B C D E F 10 10 Module RBM RBM Refrigerant Base Module Installation ...

Page 11: ...and other products or materials furnished by the installer TERMS CONDITIONS Any repair performed under warranty must be approved by Energy Saving Products Ltd for this warranty to be valid This warranty replaces all other warranties expressed or implied www hi velocity com Should there be multiple consecutive failures of a single part warranty will not be considered unless a contractor has contact...

Page 12: ...b Energy Saving Products prides itself on Customer Service and provides design services and contractor support For all of your Heating Cooling and Indoor Air Quality needs the Hi Velocity System is the right choice for you Phone 780 453 2093 Fax 780 453 1932 Toll Free 1 888 652 2219 www hi velocity com Hi Velocity HE Z Fan Coils Hi Velocity HE Z Fan Coils Green Green Technology Technology Build Sm...

Reviews: