background image

www.hi-velocity.com

© 1995-2020 Energy Saving Products Ltd.

© 1995-2020 Energy Saving Products Ltd.

Heat Pumps

Traditionally, SDHV systems have been charged to special 

guidelines when used in conjunction with heat pumps. This 

charging procedure involved charging the units to normal 

cooling capacities and reviewing the operation in heating mode. 

If head pressures were found to be impinging on the high head 

pressure limits, a small amount of refrigerant was removed to 

prevent the unit from shutting down. The cause of high head 

pressures in heating mode is due to the disparity in sizes of the 

indoor and outdoor coils, along with the lower airflow rates of 

SDHV systems.

The  RBM  coil  can  operate  at  a  level  that  is  different  from 

most other conventional system coils. Typically, superheat levels 

are slightly lower at 6-10°F (1 - 3°C) of superheat. Adjustment 

of the valve also differs somewhat. Rather than having a large 

effect on the range of superheat, adjustment of the valve has 

a larger effect on the system pressures; superheat maintaining 

a fairly constant point. Opening the valve will increase suction 

pressures and decrease liquid pressures, while closing the valve 

will decrease suction pressures and raise liquid pressures.

Bi-Flow Receiver

The  Bi-Flow  Receiver  is  designed 

for use with heat pump systems, 

up to 5 tons, and with any typical 

refrigerants. The receiver provides 

a location for the storage of excess 

refrigerant during the heating cycle, 

minimizing head pressures. During 

cooling mode, the receiver is empty, 

allowing the full refrigerant charge to 

be utilized for cooling.

The receiver is a horizontal tank with a pair of dip tubes 

extending to the bottom of the tank. These two tubes allow for 

liquid refrigerant to be drawn from the tank regardless of the 

direction of flow. For this reason, the receiver must be mounted 

so that the inlet/outlets of the tank come out of the top of the 

unit. Mounting brackets are located at the base of the unit for 

secure mounting. The receiver is to be located on the liquid line 

of the system, anywhere between the indoor and outdoor coils. 

As the unit is of a bi-flow design, it does not matter which end 

faces towards the indoor coil.

The  inlet/outlet  ports  are  constructed  of  steel  and  require 

the use of a 35-45% Silver Solder and Flux for brazing. The use 

of  standard  copper  to  copper  solders  may  result  in  difficulty 

brazing and the potential for a failure at the weld. Ensure 

that the tank is protected from overheating while brazing and 

that  any  remaining  flux  is  cleaned  from  the  unit.  If  installing 

outdoors, ensure that the receiver is insulated and protected 

from the elements.

With the introduction of newer, larger heat pumps, this issue 

is more likely to be experienced. While some heat pump units 

may still be charged in the traditional method, the amount of 

refrigerant that is required to be removed for heating mode may 

leave the system drastically undercharged for cooling mode. For 

this reason it is highly recommended that a Bi-Flow Receiver be 

used with heat pump applications.

Charging (Continued)

Typical Operating Ranges

Saturated Suction Temperature

34 - 40°F (1 - 4°C)

Suction Line Temperature

38 - 44°F (3 - 7°C)

Superheat

6 - 10°F (1 - 3°C)

Suction Line Pressure (R-410A)

110-124 psig (7.5-8.5 bar)

Liquid Line Pressure (R-410A)

250-300 psig (17-20.5 bar)

Return Air

When designing the return air for a Hi-Velocity System, there 

are a few things to consider. It is common to use centralized 

return air with systems that have rooms that are within a 

common area. Separate floors or rooms that have high loads 

and require a large amount of supply air flow should have their 

own return air, or be tied into the centralized return air to allow 

the air to return back to the fan coil. Rooms or areas that cannot 

be tied into the return air should have an air transfer grill to 

allow the air to escape the room and flow back to a centralized 

return air. 

-8-

-8-

Important:  Return Air must be filtered 

before entering the cooling module.

Module RBM

RBM Refrigerant Base Module Installation

Summary of Contents for RBM-100

Page 1: ...e Installation 052020 RBM Refrigerant Base Module Installation Manual Small Duct High Velocity Heating Cooling and Home Comfort Systems RBM 50 1 5 2 Tons RBM 70 2 5 3 Tons RBM 100 3 5 5 Tons Includes Pre Piped TXV Freeze Stat Service Access Ports T Mounting Brackets Double Sided Mounting Tape Hole Plugs 2 ...

Page 2: ......

Page 3: ...es can be used on any R 410A condenser if R 410A refrigerant components are used All Energy Saving Products R Series modules come standard with R 410A refrigerant components 3 3 The RBM module can be installed as a stand return air base for the fan coil or as a side mounted coil When the desired air inlet side has been determined the module can be adapted The module comes ready as left to up right...

Page 4: ...e unit 90 deg clockwise Fig 07 Fig 07 6 Replace the drain pan in new bottom location Fig 09 Fig 09 Fig 06 3 Slide out the air flow deflector plate Fig 06 Fig 08 5 Slide the air flow deflector plate back into the section it was removed from in the new orientation Fig 08 Fig 10 7 Remove round knock outs on the door to fit drain lines Plug previously used drain holes with provided plugs Fig 10 Insert...

Page 5: ... should always be used to make the first cut For this first cut do not use a saw blade longer than 5 125mm or damage to the coil can occur Return Air Cutouts Mounting Brackets Fig 12 TO AVOID DAMAGE After the first initial cut using the return air knockout s a metal shear must be used to make the return air cutout opening match more closely to the filter or return air ducting size to maximize flow...

Page 6: ...ring needs arise in which the outdoor unit is controlled through another means of wiring the Freeze Stat should be connected in series on the input side of the control wiring Refrigerant Bypass All RBM coils come with a pre installed check valve ready TX valve used for AC only or heat pump condensing units Third party TX valves may require a bypass check valve Fig 14 Bypass check valve 6 6 Freeze ...

Page 7: ...eck local codes Run the proper size copper wires to the unit and connect as per the manufacturer s recommendations Ensure that the unit is setup for a TX system If not a hard start kit may be required Evacuating The system must be brazed under a nitrogen purge to prevent oxidation of the pipe during the brazing process After the piping is installed and all components have been brazed together a va...

Page 8: ...ing brackets are located at the base of the unit for secure mounting The receiver is to be located on the liquid line of the system anywhere between the indoor and outdoor coils As the unit is of a bi flow design it does not matter which end faces towards the indoor coil The inlet outlet ports are constructed of steel and require the use of a 35 45 Silver Solder and Flux for brazing The use of sta...

Page 9: ...HV 70 71 LV 70 HE Z HE P HE B HE HV 100 101 Part Number 41090300050 41090300070 41090300100 Tons 1 1 5 2 0 5 3 7 0 kW 2 5 3 0 8 8 10 6 kW 3 5 5 0 12 3 17 6 kW Refrigerant Type R 410A R 410A R 410A TX Cooling MBH 2 18 24 5 3 7 0 kW 30 36 8 8 10 6 kW 42 60 12 3 17 6 kW Latent Cooling MBH 6 8 8 9 2 0 2 6 kW 11 7 13 7 3 4 4 0 kW 16 0 22 2 4 7 6 5 kW Fin Material Aluminum Aluminum Aluminum Tubing Mater...

Page 10: ...ain Conn Refrigerant Modules B C A D E F RBM 50 14 1 2 368mm 18 1 4 464mm 18 1 4 464mm 3 8 o d 7 8 o d 3 4 M CPVC RBM 70 19 1 2 495mm 18 1 4 464mm 18 1 4 464mm 3 8 o d 7 8 o d 3 4 M CPVC RBM 100 25 1 2 648mm 18 1 4 464mm 18 1 4 464mm 3 8 o d 7 8 o d 3 4 M CPVC RBM Series Sizing A B C D E F 10 10 Module RBM RBM Refrigerant Base Module Installation ...

Page 11: ...and other products or materials furnished by the installer TERMS CONDITIONS Any repair performed under warranty must be approved by Energy Saving Products Ltd for this warranty to be valid This warranty replaces all other warranties expressed or implied www hi velocity com Should there be multiple consecutive failures of a single part warranty will not be considered unless a contractor has contact...

Page 12: ...b Energy Saving Products prides itself on Customer Service and provides design services and contractor support For all of your Heating Cooling and Indoor Air Quality needs the Hi Velocity System is the right choice for you Phone 780 453 2093 Fax 780 453 1932 Toll Free 1 888 652 2219 www hi velocity com Hi Velocity HE Z Fan Coils Hi Velocity HE Z Fan Coils Green Green Technology Technology Build Sm...

Reviews: