SET CONTROL APPLICATION
FACTORY DEFAULTS
The Endeavour controller can now be set to operate in a time switch only mode inhibiting
most
other control functions other then time switches & timers. Functions enabled : Time Switch 1,
Time Switch 2 , Run Timer & AUTO /OFF / ON system overrides modes. Under this menu select
"STANDARD TEMP. APPLICATION"
or
"TIME SWITCH ONLY" mode.
NOTE : Y1 & Y2 can still be set to a minimum value
even in time switch only mode for use as a
time switch controlled fixed analogue output module.
OTHER
NOTABLE
FACTORY
(SOFTWARE)
DEFAULT SETTINGS
CONTROLLER SET AS STANDARD (TEMP.) MODE CONTROLLER
X3 (O/A), 4 (S/A) & 7 (CO2) DISABLED
X1, 2, 3 & 4 SET AS PASSIVE RESISTANCE INPUTS
X5 & 6 (MODBUS ) SOFTWARE DISABLED
TIME SWITCH 2 DISABLED
HOLIDAY DATES EMPTY
DAY LIGHT SAVINGS AUTO TIME CORRECTION DISABLED
RELAY 5 (FAN CONTROL) SET TO ON (NOT CYCLE)
NIGHT PURGE MODE DISABLED
Y1
SET AS COOL
& Y2
AS BOTH,
&
SET FOR FULL 0-10v RANGE
X3 (O/A) IF
USED
, LOW LIMIT L/O = 16 & MUST BE
0.5c < X1 TEMP. FOR Y1 TEMP. ENABLE
Also see as programmed
table on page 25
**
CYCLE POWER OFF & ON
TO
LOAD
&
TRIGGER THIS
NEW
APPLICATION**