16/2
8
MODE
DEADBAND
: Y output used as a Heating O/P, a Cooling O/P or set to act as BOTH a Heating &
Cooling O/P.
: The temperature gap from the controller’s setpoint till the Y produces an O/P
PROB
(portional)
BAND
: The change of temperature over which the Y O/P would increase to 10volts
INT
(egral)
TIME
: Time in minutes that the integral action adds the P only output to itself over the
integral time setting. Note P+I action starts as the output produced by proportional
only O/P exceeds 10%.
EXAMPLE OF ANALOGUE SUMMARY SCREEN
Y
= ANALOGUE O/P # (Y1 or Y2)
M
= MODE OF OPERATION (H,C or B)
D_B
= DEADBAND (0-25c)
P_B
= PROPOTIONAL BAND (1-25c)
P+I
= INTEGRAL TIME (1-60min or
-
P
-
only)
HEVAC CONTROL AGENCIES PTY LTD. 7/54 HOWLEYS RD.
NOTTINGHILL, VIC. 95627888
www.hevac.com.au
0
7
/11
/19
OR
OR
USE UP & DOWN BUTTONS
TO EDIT VALUE THEN
PRESS ENTER
P only or upto 60 mins.
OR
SELECT
Y OUTPUT
TO EDIT
MODE
Y1 & Y2 ANALOG
UE
(OUTPUTS) PROGRAMMING
..
.CONTINUED
Another possible alternative use for the Y1 & Y2 analogue outputs could be for use as an EC FAN time switch
controlled run & speed setting module, the controller could be set to time switch only mode but
with
Y1
(
as
an example
) set
to a
minimum
output
of
50% (which is still
accessible
even in time switch only mode). When
the time switch 1 is ON, Y1 would produce 5v
(EC fan ~ 50%) and
when the time switch turns off the Y1
output w
ould
return
to
0v output.