HEVAC CONTROL AGENCIES PTY LTD.  7/54 HOWLEYS RD. 

NOTTINGHILL,  VIC.  95627888 

www.hevac.com.au

  

 

06/11

/19

R5 FAN CONTROL METHOD

15/2

8

Another update with this latest version of the ENDEAVOUR is the ability to choose, whilst this air 
conditioning system is enabled to run (whether that be "ON BY" : Time Switch, Run Timer or set to 
operate by Manual on/off switch), that the fan relay - R5, can be set to remain ON continuously 
(default) during the ON running period of the system 

or

 for the fan (R5) be set to cycle on & off when a 

relay programmed as a heating or cooling temperature control stage enables. To set the fan control 
method of R5, press the fascia button labeled “

ENTER

” and scroll down through the menu tree until “ 

R5 

FAN CONTROL METHOD

 ” is displayed. Press the “

ENTER

” button to open this menu. The existing 

method is displayed. The fan cycle method is a typical mode of fan operation in a domestic installation to 
save on power & noise but in commercial buildings typically regulations call for the fan to remain on 
continuously whilst the building is occupied to meet minimum building ventilation requirements, if 
however minimum ventilation is achieved by some other means, it may be preferable to have the fan 
cycle with the heating or cooling as required to reduce drafts & noise when the temperature is 
comfortable.

To set or edit the two analogue outputs (Y1 & Y2) for mode of operation and output characteristics, 

Press the fascia button labeled “

ENTER

” to have the LCD display jump to the 1st menu item in the

 

menu

tree..“

SET 

CLOCK

”, scroll down through the menu tree with the “

DOWN

” arrow button until

“Y1 & Y2 ANALOGUE PROGRAMMING

” is displayed. Press the “

ENTER”

 

button to open this menu. A 

summary screen is then displayed for Analogue output Y1, The other analogue output Y2 summary 
screen can be seen by simply scrolling down this sub menu using the “

DOWN

” arrow button. To edit the 

parameters for a particular analogue output, whilst at its summary screen press the “

ENTER

” button to 

display its 1st item to edit which is “

MODE

” of operation -: the analogue outputs can be set as a

HEATING ONLY

COOLING ONLY

, “

BOTH

” mode output or 

DISABLED

. Both means the analogue 

output will function as both a heating and a cooling output with its parameters mirrored to operate on 
either side of the controller’s setpoint: if for example the deadband is set to 1 degree, then the analogue 
output will start to produce a DC output voltage from 1 degree above and 1 degree below setpoint. If an 
analogue output is not needed it can be set to “DISABLED”. If both Y1 & Y2 are both disabled they will 
not appear in the scrolling running display screens. It is also now possible to set each Y outputs min & max 
O/P values, but note the minimum value is overridden and set to 0v when the controller is in the OFF mode.

Y1 & Y2 ANALOG

UE

 (OUTPUTS) PROGRAMMING

 

Summary of Contents for ENDEAVOUR V2

Page 1: ...4 ADJUSTABLE MIN MAX SETTINGS FOR Y1 Y2 0 10v O P s 5 SUPPLY AIR TEMPERATURE SENSOR MONITORING INPUT 6 EXTERNAL A C FAULT D3 AUX I P D4 BMS MONITORING INPUTS 7 ACTIVE 0 10vdc SENSORS NOW SCALABLE 8 AD...

Page 2: ...CONFIGURATION 8 MODBUS SETUP MEMORY MAP 17 FACTORY DEFAULTS also see page 25 22 23 HEVAC CONTROL AGENCIES PTY LTD 7 54 HOWLEYS RD NOTTINGHILL VIC 95627888 www hevac com au 28 11 19 PAGE TYPICAL CONNE...

Page 3: ...ated A C fault monitoring input D4 is a general purpose on off status input that could be used for example to monitor prove supply air fan running operation via a mechanical pressure switch Remote Sys...

Page 4: ...as RS485 MODBUS Outputs X7 can be set to ground via a 100 ohm resistor for use as a comms shield connection if not used as a CO2 sensor connection ANALOG INPUTS X1 Main Temperature Sensor Input config...

Page 5: ...M Signal ground Y1 Analog Modulating Output 0 10 vDC Y2 Analog Modulating Output 0 10 vDC X1 Main Temperature Sensor Input Passive or Active X2 Remote S P input Passive or Active Optional connection...

Page 6: ...he UP DOWN arrow buttons to scroll through the menus pressing ENTER to open a particular menu to edit The relay assignments are user programmable and as such the relay use identifier text box above ea...

Page 7: ...PROGRAM R5 FAN TO CYCLE WITH HEAT COOL CALL OR CONTINUOUS Y1 Y2 ANALOGUE PROGRAMMING SET MODE SETTINGS FOR THE 2 PROGRAMMABLE ANALOGUE Y1 Y2 O P s X1 SENSOR CONFIGURATION SET MAIN CONTROL SENSOR WHIC...

Page 8: ...nu item in the menu tree SET CLOCK Press the ENTER button to check and edit the controllers time date and day light saving enable or disable settings Daylight saving if enabled starts on the 1st Sunda...

Page 9: ...em Switch or external interlock wired in parallel with the 2 sensor wires connected to our passive temperature sensor or alternatively shorting the controllers D1 M terminals which has the same affect...

Page 10: ...te at any time day s and set as a switching ON event or OFF event Typically the switching events would be programmed in the order of ON events with common days time followed by an OFF event with match...

Page 11: ...time leave as for disabled days After Sunday is entered the display will jump to the ON time setting screen use the UP DOWN buttons to set the ON time then press ENTER The controller will then ask sh...

Page 12: ...e UP or DOWN buttons scroll through calendar dates until the required 1st HOLIDAY START date is displayed press ENTER to then also program the 1st HOLIDAY END date which can either be the same as the...

Page 13: ...the LCD display jump to the 1st menu item in the menu tree SET CLOCK scroll down through the menu tree with the DOWN arrow button until RELAY PROGRAMMING is displayed Press the ENTER button to open t...

Page 14: ...relay stage turns on after exceeding the deadband setting RELAY SUMMARY SCREEN EXAMPLES R M RELAY 1 4 MODE OF OPERATION H C B 0 TIME SW2 D_B DEADBAND 0 25c S_D SWITCHING DIFFERENTIAL 0 1 20c Tdly TIME...

Page 15: ...ortable To set or edit the two analogue outputs Y1 Y2 for mode of operation and output characteristics Press the fascia button labeled ENTER to have the LCD display jump to the 1st menu item in the me...

Page 16: ...DEADBAND 0 25c P_B PROPOTIONAL BAND 1 25c P I INTEGRAL TIME 1 60min or P only HEVAC CONTROL AGENCIES PTY LTD 7 54 HOWLEYS RD NOTTINGHILL VIC 95627888 www hevac com au 07 11 19 OR OR USE UP DOWN BUTTON...

Page 17: ...ble from 5 to 5c for 0v adjustable upto 100c for 10v HEVAC CONTROL AGENCIES PTY LTD 7 54 HOWLEYS RD NOTTINGHILL VIC 95627888 www hevac com au 21 10 19 17 28 LAST STATE DISPLAYED Note if active sensor...

Page 18: ...h the DOWN arrow button until X3 O AIR TEMP CONFIGURATION is displayed Press the ENTER button to open this menu and the existing status is displayed If DISABLED is displayed press the DOWN arrow butto...

Page 19: ...also necessary to reposition a physical input select jumper on the controller s bottom pcb Remove screws holding the lid to base and hinge lid to the right locate the row of red jumpers located under...

Page 20: ...fascia button labeled ENTER to have the LCD display jump to the 1st menu item in the menu tree SET CLOCK using the DOWN arrow button scroll down the menu until X7 CO2 SENSOR CONFIGURATION is displayed...

Page 21: ...cycle dampers connected to analog output Y1 to reposition to the full fresh air mode These output states are maintained until the room temperature drops to a settable temperature difference in relatio...

Page 22: ...7 isnt used for CO2 measurement X7 can be set as ground source for the modbus shield connection by setting input pin CN4 to the C position otherwise the shield wire needs to be connected to a good ear...

Page 23: ...to a minimum value even in time switch only mode for use as a time switch controlled fixed analogue output module OTHER NOTABLE FACTORY SOFTWARE DEFAULT SETTINGS CONTROLLER SET AS STANDARD TEMP MODE...

Page 24: ...NSOR ON OFF SWITCH C W SETPOINT POT C W S P ON OFF SW DUCT TEMPERATURE SENSOR OUTSIDE AIR SENSOR PASSIVE OUTSIDE AIR SENSOR ACTIVE ROOM CO2 SENSOR 3 WIRE 3 WIRE HCRW5 ROOM TEMP CO2 SENSOR 4 WIRE OPERA...

Page 25: ...tch on period BOTH 3 0 1 0 3 00 COMPRESSOR 3 BOTH 2 0 0 5 2 00 COMPRESSOR 2 BOTH 1 0 0 3 1 00 COMPRESSOR 1 HEAT 0 5 0 4 0 10s rev valve HEAT Y1 Y2 ANALOGUE OUTPUT ASSIGNMENTS ANALOG O P I MODE IDEADBA...

Page 26: ...ME _____ _____ ACTION ON OFF TIME _____ _____ ACTION ON OFF TIME _____ _____ ACTION ON OFF TIME _____ _____ ACTION ON OFF TIME _____ _____ ACTION ON OFF TIME _____ _____ ACTION ON OFF TIME _____ _____...

Page 27: ...PI MAX O PI NOTES X ANALOGUE INPUT CONFIGURATIONS X I P I PURPOSE IActive PassiveI OFFSET I 10v I PCB JUMPER POS I NOTES X1 I MAIN TEMP SENSOR __I I I I I X2 I REMOTE SETPOINT I I I I I X3 I OUTSIDE A...

Reviews: