Fault reports and their corrections
10
67
No. Fault report
Cause of fault
Fault correction
021
SENSOR SOLAR TANK 2
Sensor break; Value outside the
measuring
range
(-10 - 120°C)
Check sensor, replace as renew
Check plug, replace as renew
Check wiring incl. connections,
replace as renew
✆
- contracting party
022
SENSOR SOLAR RES.
Sensor break; Value outside the
measuring
range
(-10 - 120°C)
Check sensor, replace as renew
Check plug, replace as renew
Check wiring incl. connections,
replace as renew
✆
- contracting party
023
ADDITIONAL BOILER
SENSOR
Sensor break; Value outside the
measuring
range
(-10 - 120°C)
Check sensor, replace as renew
Check plug, replace as renew
Check wiring incl. connections,
replace as renew
✆
- contracting party
024
MODUL SENSOR
Sensor break; Value outside the
measuring
range
(-10 - 120°C)
Check sensor, replace as renew
Check plug, replace as renew
Check wiring incl. connections,
replace as renew
✆
- contracting party
025
OVERHEAT BOILER MAX
boiler temperature over 92,5°C or
104,5°C increase
Check settings
Check back flow mixer
Check back flow pump
026
OVERHEAT
boiler temperature over 98°C or
108°C increase
Check settings
Check back flow mixer
Check back flow pump
027
SOLAR OVERHEATING
Fault is shown, if collector
temperature exceeds 140 °C
Check solar pump
Check solar tank level
028
SOLAR MAX. LOADING
Collector temperature exceeds 120
°C
Check solar pump
Check solar tank level
029
ANTIFREEZE BOILER
Boiler flow or back flow sensor
under 7°C
Check or increase the room
temperature in the boiler room.
030
ANTIFREEZE BUFFER
Sensor value below 7°C
Check or increase the room
temperature in the boiler room.
031
ANTIFREEZE HOT
WATER TANK
Sensor value below 7°C
Check or increase the room
temperature in the boiler room.
032
ANTIFREEZE HEATING
CIRCUIT
Flow or return sensor below 7 ° C;
Room temp. sensor below 5 ° C
Check or increase the room
temperature in the boiler room.
033
ANTIFREEZE SOLAR
Collector temperature under set up
antifreeze temperature
-
034
ANTIFREEZE MODULE
Sensor value below 7°C
Check or increase the room
temperature
036
ANTIFR. ADD. BOILER
Sensor value below 7°C
-
037
HOT WATER TANK
LOADING
Hot water tank didn´t reach set
temperature during loading time; hot
water tank loading gets blocked till
fault correction
Adapt loading time
Activate hot water tank priority
Hot water tank settings (min. / must)
038
Maintenance
when exceeding the set inspection
interval
Conduct maintenance according to
maintenance schedule
Fault has to be receipted manually:
Summary of Contents for firematic CONDENSATION 30
Page 1: ...OPERATING INSTRUCTIONS Wood chips pellets heating system firematic CONDENSATION 30 40 ...
Page 83: ...Annex 15 83 15 ANNEX 15 1 Additional boiler module Hydraulic recommendation 1 ...
Page 84: ...15 Annex 84 Hydraulic recommendation 2 ...
Page 85: ...Annex 15 85 15 2 Solar module Program 1 ...
Page 86: ...15 Annex 86 Program 2 ...
Page 87: ...Annex 15 87 Program 3 ...
Page 88: ...15 Annex 88 Program 4 ...
Page 89: ...Annex 15 89 Program 5 ...
Page 90: ...15 Annex 90 Program 6 ...
Page 91: ...Notes 16 91 16 NOTES ...