T-CONTROL
9
31
Term
Description
Unit
Here the maximum boiler output is limited depending on the outside
temperature. Therefore, according to the example, the maximum boiler
output at outdoor temperatures < 0°C at the set output at Temp. 1
(100%). At outside temperatures > 20°C the maximum boiler output is the
set output at Temp. 2 (50%). A linear interpolation takes place in
between.
-
Settings
1 2
3
4
Barrier time burner
cleaning
Setting the barrier times (1-4) for burner cleaning.
00:00-
23:59
Overview of work / pause in tabular form
-
Settings
1 2 3
4
ID-fan correction
nominal load
Correction of the ID fan in nominal-load operation with the aid of the
induced ID fan (observe air correction of the lambda sensor).
-75-+75 %
ID fan correction part
load
Correction of the ID fan in part-load operation with the aid of the
induced ID fan (observe air correction of the lambda sensor).
-75-+75 %
Mat. correction part
load
Correction of the amount of material in part load operation by using the
stoker screw (observe material correction of the lambda probe).
-95-+95 %
Mat. correction
nominal load
Correction of the amount of material in nominal load operation by
using the stoker screw (observe material correction of the lambda
probe)
-95-+95 %
Overview of work / pause / suction in tabular form
-
Menu
"inputs / outputs" (system-specific)
In-/Outputs
1
2 3 4 5 6 7
Grate cleaning
Indicates the state of the grate cleaning:
If switch on green
➔
Output active.
-
Ash door opened
Indicates the state of the ash door.
If the indicator lamp lights up, the ash door is opened.
-
BFP flap open
Displays the condition of the BFP flap Open:
If switch on green
➔
Output active.
-
Motor protection
Discharge
Display of the status of the motor protection discharge: If the control
lamp is lit, the discharge motor protection input has triggered.
-
End switch room
discharge
Display of the status of the end switch room discharge: If the control
lamp is lit, the end switch room discharge input has triggered.
-
Discharge
Display of the status of the discharge:
If switch on green
➔
Output active.
-
Release Stoker screw
Indicates the state of the grate cleaning:
If switch on green
➔
Output active.
-
Summary of Contents for firematic CONDENSATION 30
Page 1: ...OPERATING INSTRUCTIONS Wood chips pellets heating system firematic CONDENSATION 30 40 ...
Page 83: ...Annex 15 83 15 ANNEX 15 1 Additional boiler module Hydraulic recommendation 1 ...
Page 84: ...15 Annex 84 Hydraulic recommendation 2 ...
Page 85: ...Annex 15 85 15 2 Solar module Program 1 ...
Page 86: ...15 Annex 86 Program 2 ...
Page 87: ...Annex 15 87 Program 3 ...
Page 88: ...15 Annex 88 Program 4 ...
Page 89: ...Annex 15 89 Program 5 ...
Page 90: ...15 Annex 90 Program 6 ...
Page 91: ...Notes 16 91 16 NOTES ...