10
Fault reports and their corrections
66
No. Fault report
Cause of fault
Fault correction
011
HOT WATER TANK
SENSOR
Sensor break; Value outside the
measuring
range
(-10 - 120°C)
Check sensor, replace as renew
Check plug, replace as renew
Check wiring incl. connections,
replace as renew
✆
- contracting party
012
CIRCULATION SENSOR
Sensor break; Value outside the
measuring
range
(-10 - 120°C)
Check sensor, replace as renew
Check plug, replace as renew
Check wiring incl. connections,
replace as renew
✆
- contracting party
013
HC-FLOW SENSOR
Sensor break; Value outside the
measuring
range
(-10 - 120°C)
Check sensor, replace as renew
Check plug, replace as renew
Check wiring incl. connections,
replace as renew
✆
- contracting party
014
HC-BACK FLOW
SENSOR
Sensor break; Value outside the
measuring
range
(-10 - 120°C)
Check sensor, replace as renew
Check plug, replace as renew
Check wiring incl. connections,
replace as renew
✆
- contracting party
015
HC-ROOM SENSOR
Sensor break; Value outside the
measuring
range
(3 - 40°C)
Check sensor, replace as renew
Check plug, replace as renew
Check wiring incl. connections,
replace as renew
✆
- contracting party
016
HC-ROOM CORR.
Sensor break; Value outside the
measuring
range
(-5 - +5)
Check sensor, replace as renew
Check plug, replace as renew
Check wiring incl. connections,
replace as renew
✆
- contracting party
017
HC-OUTSIDE SENSOR
Sensor break; Value outside the
measuring
range
(-10 - 120°C)
Check sensor, replace as renew
Check plug, replace as renew
Check wiring incl. connections,
replace as renew
✆
- contracting party
018
SENSOR COLLECTOR
Sensor break; Value outside the
measuring
range
(-50 - 200°C)
Check sensor, replace as renew
Check plug, replace as renew
Check wiring incl. connections,
replace as renew
✆
- contracting party
019
SENSOR COLLECTOR
BACK FLOW
Sensor break; Value outside the
measuring
range
(-50 - 120°C)
Check sensor, replace as renew
Check plug, replace as renew
Check wiring incl. connections,
replace as renew
✆
- contracting party
020
SENSOR SOLAR TANK 1
Sensor break; Value outside the
measuring
range
(-100 - 120°C)
Check sensor, replace as renew
Check plug, replace as renew
Check wiring incl. connections,
replace as renew
✆
- contracting party
Summary of Contents for firematic CONDENSATION 30
Page 1: ...OPERATING INSTRUCTIONS Wood chips pellets heating system firematic CONDENSATION 30 40 ...
Page 83: ...Annex 15 83 15 ANNEX 15 1 Additional boiler module Hydraulic recommendation 1 ...
Page 84: ...15 Annex 84 Hydraulic recommendation 2 ...
Page 85: ...Annex 15 85 15 2 Solar module Program 1 ...
Page 86: ...15 Annex 86 Program 2 ...
Page 87: ...Annex 15 87 Program 3 ...
Page 88: ...15 Annex 88 Program 4 ...
Page 89: ...Annex 15 89 Program 5 ...
Page 90: ...15 Annex 90 Program 6 ...
Page 91: ...Notes 16 91 16 NOTES ...