9
T-CONTROL
58
The T-Control is connected to the repeater or router via Ethernet (LAN). The repeater or router must be
configured so that it communicates with the Internet router via WLAN.
After setting up the repeater or router, the network settings must be made in the T-Control.
9.11.2
Modbus
– settings
Navigation:
Screen:
By pressing the button:
active
Modbus TCP activated (green) or deactivated (black).
Port
Setting up the TCP port number.502 is reserved for Modbus-TCP.
Timeout
Setting up the time delay of the data transfer
RX / TX Buffer
Setting up the buffer size in byte
max. values
Setting up the maximum values of the servers.
Accept
Changes
Save changes
the network configuration page will be displayed again.
Note:
Modbus is an application protocol to exchange messages between intelligent Modbus controllers in the
building management system. The Modbus protocol “TCP” is used in the HERZ control. This protocol
transmits the encoded data via LAN cable. Modbus ensures that connected controllers in the building
management system receive the transmitted data from the boiler, so they can continue processing.
Summary of Contents for firematic CONDENSATION 30
Page 1: ...OPERATING INSTRUCTIONS Wood chips pellets heating system firematic CONDENSATION 30 40 ...
Page 83: ...Annex 15 83 15 ANNEX 15 1 Additional boiler module Hydraulic recommendation 1 ...
Page 84: ...15 Annex 84 Hydraulic recommendation 2 ...
Page 85: ...Annex 15 85 15 2 Solar module Program 1 ...
Page 86: ...15 Annex 86 Program 2 ...
Page 87: ...Annex 15 87 Program 3 ...
Page 88: ...15 Annex 88 Program 4 ...
Page 89: ...Annex 15 89 Program 5 ...
Page 90: ...15 Annex 90 Program 6 ...
Page 91: ...Notes 16 91 16 NOTES ...