Fault reports and their corrections
68
No. Fault report
Cause of fault
Fault correction
039
SERVICE
when exceeding the set inspection
interval
Carry out boiler system
maintenance by authorised
personnel
040
OVERHEAT ADD.BOILER
add. boiler temperature over 92 °C
increase
Check add. boiler pump
Check settings
041
HEATING OFF
Boiler operation mode “HEATING
O
FF” is activated
-
042
BLOCKING
PROTECTION
every Monday at 12 o´clock
-
043
TIMEOUT ADD. BOILER
Additional boiler minimum flue gas
temperature wasn´t reached within
1 hour
Check flue gas sensor additional
boiler
check add. boiler settings
044
LEGIONELLA
PROTECTION
Tank thermal disinfection active;
Tank will be heated up to setted
legionella protection temperature
(weekly)
-
045
CHIMNEY SWEEP.
MODE
when starting Chimney clean mode
(see chapter Chimney)
046
MOD.ERR EXT.
CAN communication to the external
module is interrupted
Check module CAN connection
Check module
✆
- contracting party
047
MOD.ERR INT.
CAN communication to the internal
module is interrupted
Check module CAN connection
Check module
✆
- contracting party
048
MOD.ERR BOILER
CAN communication to the power
unit is interrupted
Check module CAN connection
Check module
✆
- contracting party
049
DATAERROR MEMORY
EXTERNAL
Data adjustment error at external
module
✆
- contracting party
050
DATAERROR MEMORY
INTERNAL
Data adjustment error at external
module
✆
- contracting party
051
DATAERROR MEMORY
BOILER
in the event of an error in the
adjustment data of the power unit
(when starting the system)
✆
- contracting party
053
ADDITIONAL FLUE GAS
SENSOR
Sensor break; Value outside the
measuring range (-10 - 600°C)
Check sensor, replace as renew
Check plug, replace as renew
Check wiring incl. connections,
replace as renew
054
EXTERNAL SET POINT
Signal from external control does
not provide a valid value (signal less
than 1.2 volts)
Check external control signal
Check plug, replace as renew
Check wiring incl. connections,
replace as renew
055
BACK FLOW SET
The return temperature has not
risen above 53 °C within 2 hours
Function check mixer with mixer
motor
Function check pump
Check sensor position
056
SCREED BAKE OUT
Set flow temperature does not
reach the desired flow setpoint
temperature for 3 hours
Function check mixer with mixer
motor
Function check pump
Check sensor position
Required heat output to high
057
CHECK DATA MODUL
Setting value is not within the valid
range when switching on the boiler
Restart T-Control
Check boiler parameter
Summary of Contents for firematic CONDENSATION 30
Page 1: ...OPERATING INSTRUCTIONS Wood chips pellets heating system firematic CONDENSATION 30 40 ...
Page 83: ...Annex 15 83 15 ANNEX 15 1 Additional boiler module Hydraulic recommendation 1 ...
Page 84: ...15 Annex 84 Hydraulic recommendation 2 ...
Page 85: ...Annex 15 85 15 2 Solar module Program 1 ...
Page 86: ...15 Annex 86 Program 2 ...
Page 87: ...Annex 15 87 Program 3 ...
Page 88: ...15 Annex 88 Program 4 ...
Page 89: ...Annex 15 89 Program 5 ...
Page 90: ...15 Annex 90 Program 6 ...
Page 91: ...Notes 16 91 16 NOTES ...