T-CONTROL
9
51
9.10.10
External requirement
The external requirement module provides an interface to an external foreign control loop (e.g. central
building control system). The requirement, which can be digital or analogue, is registered as a required
temperature (e.g. boiler must temperature by the boiler or buffer top temperature by the buffer) in the heat
supplier (e.g. boiler or buffer).
Navigation:
→
→
External requirement
Screen:
By pressing the button:
the „external requirement status“ menu will be displayed
the menu for the "settings" will be displayed
the „requirement curve“ menu will be displayed
the „barrier times“ menu will be displayed
External requirement
Indicates a digital input signal of the external control loop (requirement):
If the indicator lamp lights up, the external control loop sends a requirement to
the digital input.
Term
Description
Unit
Menu "Status"
Status 1
1
Demand active
Indicates the state of the external demand
-
Menu "Settings"
Settings
1
External must
temperature
Setting up the (digital) external set temperature (50-100):
The boiler will operate with the external set temperature (fixed) as long as
the analogue set temperature does not exceed the setup temperature
°C
Menu "Requirement curve"
Requirement curve
1
Summary of Contents for firematic CONDENSATION 30
Page 1: ...OPERATING INSTRUCTIONS Wood chips pellets heating system firematic CONDENSATION 30 40 ...
Page 83: ...Annex 15 83 15 ANNEX 15 1 Additional boiler module Hydraulic recommendation 1 ...
Page 84: ...15 Annex 84 Hydraulic recommendation 2 ...
Page 85: ...Annex 15 85 15 2 Solar module Program 1 ...
Page 86: ...15 Annex 86 Program 2 ...
Page 87: ...Annex 15 87 Program 3 ...
Page 88: ...15 Annex 88 Program 4 ...
Page 89: ...Annex 15 89 Program 5 ...
Page 90: ...15 Annex 90 Program 6 ...
Page 91: ...Notes 16 91 16 NOTES ...