5 OPERATING CONDITIONS
If the heat pump is in “heating operation” or “cooling operation” mode but there is no request from the
consumer, the operating condition "ready" also appears
In this condition, the source and condenser pump start up and run for a pre
up circulation in both circuits.
In this condition, the heat pump run
In this condition, the heat pump is switched off but the source and condenser pump are still running in so
called pump stoppage to transport any residual heat / cold to the
continues according to the fixed set pump
A serious fault has occurred. The heat pump and all outputs are switched off too.
In an air / water heat pump, the evaporator, on which ice can form, is defrosted. This function may have
been triggered by the button "manual defrost" or by the automatic defrost process.
This condition indicates that the heat
taking heat and diverts this to the source, for example.
This condition serves as compressor protection. If the compressor is switched off and switched on again
straight afterwards, the compressor only starts after minimal downtime, which may be, for example, 10
minutes. The “wait” condition is then displayed. The compressor may also only be started 6 times per
hour. If the compressor is started more frequently, it also re
This condition is reached when the flow temperature of the heat pump is greater than the set maxim
temperature (usually 55°C). To lower the flow temperature the condenser pump is switched on.
continues running until the maximum temperature is undershot.
Operating conditions
OPERATING CONDITIONS
Ready
If the heat pump is in “heating operation” or “cooling operation” mode but there is no request from the
condition "ready" also appears
Pump flow
In this condition, the source and condenser pump start up and run for a pre-set time.
Compressor
and heat or cooling consumer sends a request to the heat pump.
Stop
In this condition, the heat pump is switched off but the source and condenser pump are still running in so
called pump stoppage to transport any residual heat / cold to the heat consumer. The pump stoppage
continues according to the fixed set pump stopping time.
Fault
A serious fault has occurred. The heat pump and all outputs are switched off too.
Defrost
In an air / water heat pump, the evaporator, on which ice can form, is defrosted. This function may have
been triggered by the button "manual defrost" or by the automatic defrost process.
Cooling mode
This condition indicates that the heat pump is cooling, i.e. the process is reversed and the system is
taking heat and diverts this to the source, for example.
Waiting
This condition serves as compressor protection. If the compressor is switched off and switched on again
afterwards, the compressor only starts after minimal downtime, which may be, for example, 10
minutes. The “wait” condition is then displayed. The compressor may also only be started 6 times per
hour. If the compressor is started more frequently, it also remains in “wait” operating condition.
Max. temp.
This condition is reached when the flow temperature of the heat pump is greater than the set maxim
temperature (usually 55°C). To lower the flow temperature the condenser pump is switched on.
continues running until the maximum temperature is undershot.
Operating conditions
5
15
Status 0
If the heat pump is in “heating operation” or “cooling operation” mode but there is no request from the
Status: 1
set time. This serves to build
Status: 2
and heat or cooling consumer sends a request to the heat pump.
Status: 3
In this condition, the heat pump is switched off but the source and condenser pump are still running in so-
heat consumer. The pump stoppage
Status: 4
Status: 5
In an air / water heat pump, the evaporator, on which ice can form, is defrosted. This function may have
Status: 6
pump is cooling, i.e. the process is reversed and the system is
Status: 7
This condition serves as compressor protection. If the compressor is switched off and switched on again
afterwards, the compressor only starts after minimal downtime, which may be, for example, 10
minutes. The “wait” condition is then displayed. The compressor may also only be started 6 times per
mains in “wait” operating condition.
Status: 8
This condition is reached when the flow temperature of the heat pump is greater than the set maxim
temperature (usually 55°C). To lower the flow temperature the condenser pump is switched on. The pump