Temperature manager
8
17
If there is no buffer in the system, then the MUST-temperature from the individual modules is determined and
to that an adjustable temp. increase is added. The highest of these temperatures is the boiler-MUST-
temperature. To this an adjustable hysteresis is added and the result is the boiler-END-temperature (see
Figure 8.4). Caution: Consider the set minimum requirement.
Figure 8.4: Example temperature manager when operation without buffer
If a time mode is applied directly on the buffer, then the required buffer-top-temperature is set directly in the
time mode module. Now it must be distinguished again if the buffer-top-temperature is higher than the
adjusted buffer-bottom-MUST-temperature. In this case the required boiler temperature is the result of the
required buffer-bottom-MUST-temperature + the adjusted temp. increase + the adjusted difference (see
Figure 8.5). In this is not the case, the required boiler temperature is the result of the required tempe
the adjusted temp. increase (see Figure 8.6). Caution: Consider the set minimum requirement.
Figure 8.5: Example temperature manager when time mode with difference
Summary of Contents for BioFire 1000
Page 1: ...OPERATING INSTRUCTIONS Wood chips pellets heating system BioFire 500 600 800 1000 1250 1500 ...
Page 89: ...Annex 14 89 14 ANNEX 14 1 Additional boiler module Hydraulic recommendation 1 ...
Page 90: ...14 Annex 90 Hydraulic recommendation 2 ...
Page 91: ...Annex 14 91 14 2 Solar module Program 1 ...
Page 92: ...14 Annex 92 Program 2 ...
Page 93: ...Annex 14 93 Program 3 ...
Page 94: ...14 Annex 94 Program 4 ...
Page 95: ...Annex 14 95 Program 5 ...
Page 96: ...14 Annex 96 Program 6 ...
Page 97: ...Notes 15 97 15 NOTES ...