ERS COMPACT
30 kW
Model 380/400/480 V
ERSC 360-240/30
ERSC 500-180/30
ERSC 750-120/30
AC supply
Voltage range (L-L)
380 / 400 / 480 V, ±10%
Frequency
45 - 66 Hz
Connection
3ph, PE
Leak current
≤ 10 mA
Phase current / Inrush current
< 56 A
Efficiency of energy recovery
≤ 94.6%
≤ 95.3%
≤ 95.5%
Power factor
≈
0.99
Power consumption at no load
At 400 V AC: ca. 120 W (true) plus ca. 1200 VA (apparent)
DC terminal
Max. voltage U
Max
360 V
500 V
750 V
Max. current I
Max
240 A
180 A
120 A
Max. power P
Max
30000 W
30000 W
30000 W
Overvoltage protection range
0...396 V
0...550 V
0...825 V
Overcurrent protection range
0...264 A
0...198 A
0...132 A
Overpower protection range
0…33000 W
0…33000 W
0…33000 W
Temperature coefficient (Δ/K)
Voltage set values / current set values: 100 ppm
Capacitance (approx.)
1800 μF
675 μF
450 μF
Voltage regulation (general)
Adjustment range
0...376.2 V
0...510 V
0...765 V
Accuracy
(1
(at 23 ± 5 °C / 73
±
9 °F) ≤ 0.05% U
Nom
≤ 0.05% U
Nom
≤ 0.05% U
Nom
Line regulation at ±10% ΔU
AC
≤ 0.02% U
Nom
≤ 0.02% U
Nom
≤ 0.02% U
Nom
Display: Resolution
See section
“1.9.6.4. Resolution of the displayed values”
Display: Accuracy
(3
≤ 0.2% U
Nom
≤ 0.2% U
Nom
≤ 0.2% U
Nom
Remote sensing compensation
Max. 5% U
Nom
Max. 5% U
Nom
Max. 5% U
Nom
Voltage regulation (power supply)
Load regulation at 0...100% ΔI
OUT
≤ 0.05% U
Nom
≤ 0.05% U
Nom
≤ 0.05% U
Nom
Rise time 10...90% ΔU
OUT
Max. 30 ms
Max. 30 ms
Max. 30 ms
Transient time after ΔI
OUT
≤ 1.5 ms
≤ 1.5 ms
≤ 1.5 ms
Ripple
(2
≤ 320 mV
PP
≤ 55 mV
RMS
≤ 350 mV
PP
≤ 70 mV
RMS
≤ 800 mV
PP
≤ 200 mV
RMS
Fall time at no load after switching
DC terminal off
Down from 100% to <60 V: less than 10 s
Voltage regulation (el. load)
Load regulation at 0...100% ΔU
≤ 0.05% U
Nom
≤ 0.05% U
Nom
≤ 0.05% U
Nom
Current regulation (general)
Adjustment range
0...244.8 A
0...183.6 A
0...122.4 A
Accuracy
(1
(at 23 ± 5 °C / 73
±
9 °F) ≤ 0.1% I
Nom
≤ 0.1% I
Nom
≤ 0.1% I
Nom
Line regulation at ±10% ΔU
AC
≤ 0.05% I
Nom
≤ 0.05% I
Nom
≤ 0.05% I
Nom
Display: Resolution
See section
“1.9.6.4. Resolution of the displayed values”
Display: Accuracy
(3
≤ 0.2% I
Nom
≤ 0.2% I
Nom
≤ 0.2% I
Nom
Current regulation (power supply)
Load regulation at 0...100% ΔU
OUT
≤ 0.15% I
Nom
≤ 0.15% I
Nom
≤ 0.15% I
Nom
Current regulation (el. load)
Load regulation at 0...100% ΔU
IN
≤ 0.15% I
Nom
≤ 0.15% I
Nom
≤ 0.15% I
Nom
Ripple
(2
≤ 50 mA
RMS
≤ 48 mA
RMS
≤ 48 mA
RMS
(1 Related to the nominal values, the accuracy defines the maximum deviation between an adjusted values and the true (actual) value.
Example: a 1000 A model has min. 0.2% current accuracy, that is 2 A. When adjusting the current to 300 A, the actual current on the DC terminal is allowed to
differ max. 2 A from the set value, which means it could be between 298 A and 302 A.
(2 RMS value: LF 0...300 kHz, PP value: HF 0...20MHz
(3 The display error adds to the error of the related actual value on the DC terminal