NANOV TOP DV GAS APPLIANCE INSTALLATION INSTRUCTIONS
Figure1 5
Vertical Termination Clearances
Figure 16
Vertical Termination Vent lengths
Figure 17
Vertical Termination Vent Lengths
WARNING - RISK OF FIRE!
Always maintain minimum air space clearances
or greater around the chimney system. Do not pack
air space with insulation or other material.
WARNING!
The horizontal run of vent must have a ¼ rise for
every 1 ft. of run towards the termination. Never
allow the vent to run downward. This could cause
high temperatures and may present a fire hazard.
c. Assembling Vent Sections
Use only pipe supplied and listed for use with
this appliance. See page 4 for a description of
listed components. See Section 3 on page 13 for
instructions on assembling vent sections.
2. VERTICAL TERMINATION
a. Clearances
See Figure 15 for clearance information.
b. Vent Lengths
Various venting configurations are shown in
Figures 16 and 17 from which maximum vent
runs can be determined.