background image

56

Heatilator  • ECLIPSE-32, ECLIPSE-36 Installation Manual  •  2297-984 Rev. B   •  6/15 

A.  Vent Components Diagrams 

(continued)

Figure 12.8  SLP Series Vent Components      

SLP-WT-BK

Wall Thimble-Black

SL-2DVP
Adapter

26 in.

660 mm

DVP-HSM-B

Extended Heat Shield

SLP-TRAP

Horizontal Termination Cap

15-1/8 in.

(384 mm)

Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm). The heat shield is designed to be 
used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick. If wall thickness is less than 4 in. (102 mm) 
the existing heat shields must be field trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a 
DVP-HSM-B will be required.

Heat

Shield

Term Cap

Minimum

Effective Length

Maximum

Effective Length

Trap1

3-1/8 in. 

4-3/4 in. 

79 mm

121 mm

Trap2

5-1/4 in. 

9-1/4  in.

133 mm

235 mm

8 in.

(203 mm)

12 in.

(305 mm)

Max

Effective

Length

14-7/16 in.

367 mm

14-7/16 in.

367 mm

2-5/16 in.

59 mm

3-15/16 in.

(101 mm)

6-11/16 in.

(169 mm)

8 in.

(203 mm)

3-15/16 in.

(101 mm)

3-13/16 in.

(97 mm)

5-1/16 in.

(128 mm)

6-3/8 in.
163 mm

4-3/16 in.

106 mm

4-5/8 in.
117 mm

5-1/16 in.

128 mm

8-1/8 in.
206 mm

DVP-2SL
Adapter

4 in.

102 mm

Summary of Contents for ECLIPSE-32

Page 1: ...AUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLASS A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be installed for the protection of children and other at risk individuals DO NOT store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance What to do if yo...

Page 2: ...ion and Vent Information A Vent Termination Minimum Clearances 11 B Chimney Diagram 12 C Approved Pipe 13 D Use of Elbows 14 E Measuring Standards 15 F Use of Flex Vent 15 G Vent Diagrams 15 5 Vent Clearances and Framing A Pipe Clearances to Combustibles 28 B Wall Penetration Framing Firestops 28 C Ceiling Firestop Floor Penetration Framing 29 D Install Attic Insulation Shield 29 6 Appliance Prepa...

Page 3: ... removed inside outside of appliance ___________________________ Refractories media stones and embers installed correctly ___________________________ Glass assembly installed and secured ___________________________ Accessories installed properly ___________________________ Mesh doors or decorative front properly installed ___________________________ Manual bag and all of its contents are removed f...

Page 4: ...al codes with National Electric Code ANSI NFPA 70 latest edition or the Canadian Electric Code CSA C22 1 A 110 120 VAC circuit for this product must be pro tected with ground fault circuit interrupter protection in compliance with the applicable electrical codes when it is installed in locations such as in bathrooms or near sinks NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE This appliance is test...

Page 5: ...ed gas fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizon tally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector ob serves carbon monoxide detectors and signage inst...

Page 6: ...onents Keep appliance dry B Tools and Supplies Needed Before beginning the installation be sure that the following tools and building supplies are available Tape measure Framing material Pliers Hammer Phillips screwdriver Manometer Gloves Framing square Voltmeter Electric drill and bits 1 4 in Plumb line Safety glasses Level Reciprocating saw Flat blade screwdriver Non corrosive leak check solutio...

Page 7: ...Q GAS LINE ACCESS ECLIPSE 32 ECLIPSE 36 Location Inches Millimeters Inches Millimeters A 36 914 41 1041 B 31 1 8 791 36 1 8 918 C 27 3 16 691 32 1 16 814 D 18 1 16 459 21 1 2 546 E 31 1 8 791 34 5 8 880 F 3 9 16 91 3 9 16 91 G 6 7 8 175 6 7 8 175 H 23 3 8 594 26 7 8 683 I 34 3 8 873 37 7 8 962 J 35 1 2 902 39 15 16 1014 K 8 203 8 203 L 8 13 16 224 8 13 16 224 M 16 5 16 414 16 5 16 414 N 1 2 13 1 2...

Page 8: ...ive Front Dimensions SIMON DECORATIVE FRONTS Figure 3 2 Simon Decorative Front Dimensions CLEAN FACE DECORATIVE FRONTS Figure 3 3 Clean Face Decorative Front Dimensions 23 3 4 IN 30 13 16 IN CF 32 27 1 4 IN 35 13 16 IN CF 36 32 1 16 IN SIM 36 35 13 16 IN 28 9 16 IN 30 13 16 IN SIM 32 ...

Page 9: ...awn to scale Actual installation may vary due to individual design preference Figure 3 4 Appliance Locations K C A L F I B G E D J J G A F C A H M N Refer to Section 10 B for mantel and wall projection information Consider the mantel or cabinet system to be installed and comply with the necessary requirements for elevated hearth Refer to instructions included with cabinet system Models A B C D E M...

Page 10: ...tact The chase must be properly blocked to prevent blown insulation or other combustibles from entering and making contact with fireplace or chimney Failure to maintain airspace may cause overheating and a fire To further prevent drafts the wall shield and ceiling fire stops should be caulked with caulk with a minimum of 300ºF continuous exposure rating to seal gaps Gas line holes and other openin...

Page 11: ...HES MIN H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING 4 4 Termination Location and Vent Information Fire Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with insulation or other materials Failure to keep insulation or other materials away from vent pipe could cause overheating and fire WARNING Figure 4 2 Staggered Termination Caps Gas Wood or Fuel Oil T...

Page 12: ...ctrical Service V K V K V L C V N 6 inches non vinyl sidewalls 12 inches vinyl sidewalls O 18 inches non vinyl soffit and overhang 42 inches vinyl soffit and overhang P 8 ft QMIN RMAX 1 cap 3 feet 2 x Q ACTUAL 2 caps 6 feet 1 x Q ACTUAL 3 caps 9 feet 2 3 x Q ACTUAL 4 caps 12 feet 1 2 x Q ACTUAL QMIN termination caps x 3 RMAX 2 termination caps x QACTUAL Covered Alcove Applications Spaces open only...

Page 13: ...12 A for vent component information and dimensions DO NOT mix pipe fittings or joining methods from differ ent manufacturers The pipe is tested to be run inside an enclosed wall There is no requirement for inspection openings at each joint within the wall WARNING Risk of Fire or Asphyxiation This appli ance requires a separate vent DO NOT vent to a pipe serving a separate solid fuel burning applia...

Page 14: ... F E C T I V E L E N G T H Y X X X DVP Pipe Effective Length Rise Run Inches Millimeters Inches Millimeters DVP4 4 102 2 3 4 70 DVP6 6 152 4 1 4 108 DVP12 12 305 8 1 2 216 DVP24 24 610 17 432 DVP36 36 914 25 1 2 648 DVP48 48 1219 34 864 DVP6A 3 to 6 76 to 152 2 1 8 4 1 4 54 108 DVP12A 3 to 12 76 to 305 2 1 8 8 1 2 54 216 Vent Type X Inches Millimeters DVP 16 1 4 413 SLP 11 1 4 286 Figure 4 5 Verti...

Page 15: ...ge in venting direction and in any location where it is necessary to maintain the necessary clearance to combustibles A simple up and out installation Figure 4 6 requires only enough sup port to maintain the necessary clearance to combustibles However the vent attachment point and the firestop loca tion are considered to be supports Figure 4 6 3 in CLEARANCE TERMINATION CAP FLEX VENT 1 in CLEARANC...

Page 16: ...orizontal Termination One Elbow Note There MUST be a 25 reduction in total H when using flex vent except when using the simple up and out installation see Figure 4 6 Fire Risk When using SLP HRC SS and SLP HRC ZC SS termination caps on top vented fireplaces a one foot minimum vertical vent section is required before installing first elbow When using DVP TB1 termination cap on top vented fireplaces...

Page 17: ...1 2 ft 152 mm 1 ft 305 mm 1 1 2 ft 457 mm 2 ft 610 mm 2 1 2 ft 762 mm 4 ft 1 2 m 3 1 2 ft 1 1 m 6 ft 1 8 m 4 1 2 ft 1 4 m 14 ft 4 3 m H1 H2 MAX 14 ft 4 3 m V1 H1 H2 MAX 40 ft 12 2 m See Warning Below Fire Risk When using SLP HRC SS and SLP HRC ZC SS termination caps on top vented fireplaces a one foot minimum vertical vent section is required before installing first elbow When using DVP TB1 termin...

Page 18: ...14 ft 4 3 m 4 1 2 ft 1 4 m 14 ft 4 3 m 14 ft 4 3 m H1 H2 MAX 14 ft 4 3 m V1 V2 H1 H2 MAX 40 ft 12 2 m See Warning Below Note There MUST be a 25 reduction in total H when using flex vent except when using the simple up and out installation see Figure 4 6 Fire Risk When using SLP HRC SS and SLP HRC ZC SS termination caps on top vented fireplaces a one foot minimum vertical vent section is required b...

Page 19: ... appliance manual bag Note Be sure to rein stall the exhaust baffle after exhaust restrictor installation Exhaust restrictor Exhaust restrictor Exhaust restrictor Instructions 1 Install the exhaust restrictor over the center of the ex haust outlet in the firebox See Figure 4 12 2 Center the exhaust restrictor in the open end of the exhaust outlet and secure through the slots on the ex haust restri...

Page 20: ... V2 H1 MAX 40 ft 12 2 m V1 Minimum H1 H2 Maximum 90 Elbow Only 1 2 ft 152 mm 1 2 ft 152 mm 1 ft 305 mm 1 1 2 ft 457 mm 2 ft 610 mm 2 1 2 ft 762 mm 4 ft 1 2 m 3 1 2 ft 1 1 m 6 ft 1 8 m 4 1 2 ft 1 4 m 14 ft 4 3 m H1 H2 MAX 14 ft 4 3 m V1 V2 H1 H2 MAX 40 ft 12 2 m Note There MUST be a 25 reduction in total H when using flex vent except when using the simple up and out installation see Figure 4 6 Note...

Page 21: ... Figure 4 15 V1 MIN H1 MAX V2 MIN H2 MAX V3 MIN 1 1 2 ft 457 mm 4 ft 1 2 m 4 ft 1 2 m 4 ft 1 2 m 3 1 2 ft 1 1 m V1 V2 V3 H1 H2 Maximum 40 ft 12 2 m Note Use SLP Series components only V1 H1 V2 V3 H2 Note There MUST be a 25 reduction in total H when using flex vent except when using the simple up and out installation see Figure 4 6 ...

Page 22: ...l 2297 984 Rev B 6 15 Rear Vent Horizontal Termination Figure 4 17 Figure 4 16 No Elbows H1 9 in 229 mm Maximum Rear Vent Horizontal Termination One 45º Elbow Note Use DVP Series components only Note Use DVP Series components only H1 H1 H1 24 in Max 610 mm ...

Page 23: ... H1 H2 MAX 14 ft 4 3 m V1 H1 H2 MAX 40 ft 12 2 m Figure 4 18 H1 MAX V1 MIN H2 H3 MAX H1 H2 H3 MAX 1 1 2 ft 457 mm Back to back elbows 1 ft 305 mm 2 1 2 ft 762 mm 3 1 2 ft 1 1 m 1 ft 305 mm 2 ft 610 mm 5 1 2 ft 1 7 m 5 1 2 ft 1 7 m 2 ft 610 mm 4 ft 1 2 m 9 1 2 ft 2 9 m 7 1 2 ft 2 3 m 3 ft 914 mm 6 ft 1 8 m 13 1 2 ft 4 1 m H1 MAX 7 1 2 ft 2 3 m H1 H2 H3 MAX 13 1 2 ft 4 1 m V1 H1 H2 H3 MAX 40 ft 12 2...

Page 24: ...m 3 1 2 ft 1 1 m 2 ft 610 mm 5 1 2 ft 1 7 m 3 ft 914 mm 7 1 2 ft 2 3 m H MAX 7 1 2 ft 2 3 m V1 H1 MAX 40 ft 12 2 m H1 H2 MAX V1 MIN Back to back elbows 1 2 ft 152 mm 2 1 2 ft 762 mm 1 ft 305 mm 4 1 2 ft 1 4 m 2 ft 610 mm 6 1 2 ft 2 0 m 3 ft 914 mm H MAX 6 1 2 ft 2 m V H H1 MAX 40 ft 12 2 m Note Use DVP Series components only Note Use DVP Series components only H1 V1 Two Elbows One Elbow ...

Page 25: ...ft 762 mm 1 ft 305 mm 3 1 2 ft 1 1 m 3 ft 914 mm 6 1 2 ft 2 0 m 2 ft 610 mm 5 1 2 ft 1 7 m 5 ft 1 5 m 10 1 2 ft 3 2 m 3 ft 914 mm 7 1 2 ft 2 3 m 7 ft 2 1 m 14 1 2 ft 4 4 m H1 MAX 7 1 2 ft 2 3 m H1 H2 MAX 14 1 2 ft 4 4 m V1 V2 H1 H2 MAX 40 ft 12 2 m Figure 4 22 Three Elbows Note Use DVP Series components only V2 V1 H2 H1 Rear Vent Vertical Termination continued ...

Page 26: ...Risk of Fire Coaxial to colinear venting con figuration may only be used in existing non combustible chimney Installation in any other venting application could cause fire Prior to installing the gas appliance Have the chimney and adjacent structure inspected and cleaned by qualified professionals Hearth Home Technologies recommends that NFI or CSIA certified professionals or technicians under the...

Page 27: ...ded with DVP 2SL kit Attach the DV 46DVA GCL adapter to the appliance starting collar with 3 1 2 in self tapping screws See Figure 4 25 Rear Vent Remove the rear seal cap and insulation if equipped Connect the DVP 2SL adapter to the vertically positioned elbow Follow installation instructions included with DVP 2SLkit Secure DV 46DVA GCLadapter to DVP 2SLwith 3 1 2 in self tapping screws See Figure...

Page 28: ...t Shield Wall Shield Firestop Heat Shield WALL 3 in 76 mm top clearance 1 in 25 mm clearance around vertical sections B Wall Penetration Framing Firestops Combustible Wall Penetration Whenever a combustible wall is penetrated you must frame a hole for the wall shield firestop s The wall shield firestop maintains minimum clearances and prevents cold air infiltration The opening must be framed on al...

Page 29: ...on around the vent Insulation must be kept back from the pipe to prevent overheating Figure 5 3 Installing Ceiling Firestop Figure 5 4 Installing the Attic Shield INSTALL ATTIC INSULATION SHIELDS BEFORE OR AFTER INSTALLATION OF VENT SYSTEM CEILING FIRESTOP INSTALLED BELOW CEILING CEILING FIRESTOP INSTALLED ABOVE CEILING ATTIC ABOVE A PIPE DVP SLP A 10 in 254 mm 9 in 229 mm A D Install Attic Insula...

Page 30: ...d to the vertical position as shown above The heat shield must remain in the vertical position Figure 6 4 Remove the seal cap Figure 6 5 Remove the insulation basket and white insula tion from the center vent pipe Figure 6 1 For top vent remove the two screws holding the top heat shield in place For rear vent see next page Note Actual appliance may look different than the appliance shown in this s...

Page 31: ...ion gasket Figure 6 9 Fold the center parts of the retaining band toward the center as shown Remove the seal cap Figure 6 10 Discard the seal cap remove and discard the insulation basket Note Once the seal cap has been removed it CANNOT be reattached Figure 6 11 Attach the first vent section it will snap into place Slide the insulation gasket onto the vent section up against the appliance and over...

Page 32: ...fire The diagram shows how to properly position and secure the appliance See Figure 6 12 Nailing tabs are provided to secure the appliance to the framing members Bend out nailing tabs on each side Place the appliance into position Keep nailing tabs flush with the framing Level the appliance from side to side and front to back Shim the appliance as necessary It is acceptable to use wood shims under...

Page 33: ...e For 90º and 45º elbows that are changing the vent direction from horizontal to vertical one screw minimum should be put in the outer flue at the horizontal elbow joint to prevent the elbow from rotating Use screws no longer than 1 2 in 13 mm If predrilling screw holes DO NOT penetrate inner pipe Required Commercial Multi family Multi level exceeding two stories or High Rise Applications All oute...

Page 34: ...e slip section elbow and cap outer flues shall be sealed in this manner unless otherwise stated Figure 7 5 Adding Venting Components WARNING Risk of Fire or Explosion DO NOT break silicone seals on slip sections Use care when remov ing termination cap from slip pipe If slip section seals are broken during removal of the termination cap vent could leak Note Align seams to engage pipe then rotate co...

Page 35: ...orted every 8 ft 2 44 m after the maximum allowed 25 ft 7 62 m of unsupported rise Vertical runs originating off the rear of the appliance or after any elbow must be supported every 8 ft 2 44 m Horizontal runs must be supported every 5 feet 1 52 m Vent supports or plumbers strap spaced 120º apart may be used to support vent sections See Figures 7 8 and 7 9 Wall shield firestops may be used to prov...

Page 36: ...ES MIN H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING NOTICE Failure to properly caulk the roof flashing and pipe seams could permit entry of water Caulk the gap between the roof flashing and the outside diameter of the pipe Caulk the perimeter of the flashing where it contacts the roof surface See Figure 7 13 Caulk the overlap seam of any exposed pipe sections that are located above t...

Page 37: ...lap 1 1 2 in 38 mm mini mum There are two sections of the heat shield One section is factory attached to the wall shield firestop The other section is factory attached to the cap See Figure 7 16 If the wall thickness does not allow the required 1 1 2 in 38 mm heat shield overlap when installed an extended heat shield must be used If the wall thickness is less than 4 in 102 mm DVP or 4 3 8 in 111 m...

Page 38: ...ate for siding material at outside edges of cap When installing a horizontal termination cap follow the cap location guidelines as prescribed by current ANSI Z223 1 and CAN CGA B149 installation codes and refer to Section 6 of this manual CAUTION Risk of Burns Local codes may require in stallation of a cap shield to prevent anything or anyone from touching the hot cap NOTICE For certain exposures ...

Page 39: ... box receptacle and reattach the junction box receptacle to the outer shell Electrical Service and Repair WARNING Risk of Shock Label all wires prior to dis connection when servicing controls Wiring errors could cause improper and dangerous operation Verify proper operation after servicing WARNING Risk of Shock Replace damaged wire with type 105º C rated wire Wire must have high temperature insula...

Page 40: ... Rev B 6 15 Figure 8 2 Intellifire Pilot Ignition IPI Wiring Diagram TRANSFORMER WALL SWITCH 3 VAC PLUG IN BLACK RED BATTERY PACK ORANGE TO BROWN TO BROWN GREEN GROUND TO FIREPLACE CHASSIS WHITE ORANGE IGNITION MODULE 3 VAC INTERMITTENT PILOT IGNITOR HOT NEUTRAL I S ...

Page 41: ... box and connect to the top fan switch connector 1 4 in male as shown Red Switch Switch Box Red Black Black Green Green White Power Supply Wires White Red Black Green White Minimum 14 3 AWG with Ground Junction Box Knockout Figure 8 3 Junction Box Wired to Wall Switch or BC10 RHEOSTAT SWITCH TEMPERATURE SENSOR Figure 8 4 Fan Wiring with Rheostat BLUE RHEOSTAT SWITCH TEMPERATURE SENSOR SWITCH JUNCT...

Page 42: ...ipping and handling WARNING Risk of Fire DO NOT change valve settings This valve has been preset at the factory WARNING Risk of Fire or Explosion High pressure will damage valve Low pressure could cause explosion Verify inlet pressures Verify minimum pressures when other household gas appliances are operating Install regulator upstream of valve if line pressure is greater than 1 2 psig 9 9 Gas Inf...

Page 43: ...ll be opening the air shutter To adjust loosen the wing nut Care should be taken when adjusting the air shutter so as not to cause the appliance to soot If sooting occurs the air shutter will need to be opened by sliding the air shutter to the right When finished tighten the wing nut See Figure 9 1 NOTICE If sooting occurs provide more air by opening the air shutter Air Shutter Settings Models NG ...

Page 44: ... this manual Overlapping materials could ignite and will interfere with proper operation of doors and louvers 0 IN 0 IN 0 IN SHEETROCK FINISH WALL MATERIAL UP TO 1 2 IN THICK MAY BE COMBUSTIBLE TOP AND SIDES HIGH TEMPERATURE SEALANT 300 F 149 C MIN TOP AND SIDE SEAL JOINT Figure 10 1 Noncombustible Facing Diagram Stop finishing material flush with fireplace surround opening NON COMBUSTIBLE FINISHI...

Page 45: ...le on both sides of opening 5 6 7 8 9 10 3 4 5 12 11 10 9 8 7 6 TOP OF HOOD OR FIREPLACE OPENING 4 12 13 11 32 CEILING MEASUREMENTS FROM TOP EDGE OF THE OPENING See Dimension V on Appliance Dimension Diagram Figure 3 1 3 FT MAXIMUM TOP VIEW 2 7 8 IN MINIMUM 1 2 IN MINIMUM Note Clearance from opening to perpendicular wall FIREPLACE OPENING See Dimension B on Appliance Dimension Diagram Figure 3 1 5...

Page 46: ...e 11 1 Fixed Glass Assembly B Remove the Shipping Materials Remove shipping materials from inside or underneath the firebox The splatter guard is a piece of corrugated material used to protect the appliance during the installation process before finishing work on the whole hearth is complete Splatter guards may be factory installed or accompany the door of the unit depending on the fireplace model...

Page 47: ... pins and jig FLANGE WARNING RISK OF EXPLOSION Place stones according to instructions Do NOT place stones on burner top Do NOT place stones in a position that they may fall into area in front of pilot Do NOT use more than 30 stones per fireplace Do NOT stack stones Place in single layer Use ONLY Hearth Home Technologies approved optional media with this appliance Improperly placed stones interfere...

Page 48: ...ce Pull out and latch the four glass assembly latches into the groove on the glass frame See Figure 11 1 F Install Decorative Front WARNING Risk of Fire Install ONLY decorative fronts approved by Hearth Home Technologies Unapproved fronts could cause fireplace to overheat This fireplace has been supplied with an integral barrier to prevent direct contact with the fixed glass panel DO NOT operate t...

Page 49: ...25 mm 12 in 305 mm 14 in 356 mm 1 in 25 mm 8 in 203 mm 6 in 152 mm 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm UP DVP HVS Vent Support DVP WS Wall Shield Firestop DVP FS Ceiling Firestop DVP45 45º Elbow DVP Pipe see chart Effective Height Length 4 7 8 in 124 mm 13 mm Finished Height 19 3 4 in 502 mm UNIV AS2 Attic Insulation Shield Tab 1 in 25 4 mm 20 3 4 in 527 mm Pipe Effective Length I...

Page 50: ...1 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield A Vent Components Diagrams continued Figure 12 2 DVP vent components Term Cap Minimum Effective Length Maximum Effec...

Page 51: ...m RF12M Roof Flashing Multi pak Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm 11 7 8 in 302 mm DVP TRAPFL Flashing 26 in 660 mm DVP HSM B Extended Heat Shield A Vent Components Diagrams continued Figure 12 3 DVP vent componen...

Page 52: ...in 314 mm 7 1 8 in 181 mm 8 3 4 in 222 mm 1 5 8 in 41 mm 16 7 8 in 429 mm DVP HPC High Performance Cap 1 in 25 mm 14 in 356 mm 3 8 in 10 mm 1 in 25 mm 7 1 4 in 184 mm 7 3 4 to 10 3 8 in 197 to 264 mm DVP FBHT FireBrickTermination Cap DVP TB1 Basement Vent Cap 12 in 305 mm 1 1 2 in 38 mm 7 3 8 in 187 mm 14 in 356 mm 17 3 4 in 451 mm 6 in 152 mm A Vent Components Diagrams continued Figure 12 4 DVP V...

Page 53: ...ZC SS termination caps on top vented fireplaces a one foot minimum vertical vent section is required before installing first elbow WARNING 13 in 330 mm 15 in 381 mm 8 1 8 in 206 mm 10 7 8 in 276 mm 10 1 2 in 267 mm 3 87 Effective Length 5 3 4 to 8 3 8 in 146 to 213 mm 5 1 2 in 140 mm 8 3 8 in 213 mm SLP HRC SS SLP HRC ZC SS HORIZONTAL TERMINATION CAP When using DVP TB1 termination cap on top vente...

Page 54: ...y from PVLP SLP Contact your dealer to order Note The PVLP SLP requires a PVLP CK be installed on this appliance The PVLP CK is ordered separately from the PVLP SLP Contact your dealer to order Figure 12 6 PVLP SLP Vent Components PVLP HS Heat Shield 14 IN 356 mm 15 1 2 IN 394 mm 11 1 2 IN 292 mm 8 IN 203 mm 4 3 8 IN 112 mm 10 IN 254 mm 5 1 4 IN 135 mm 2 1 4 IN 57 mm 9 1 2 IN 241 mm 4 3 4 IN 121 m...

Page 55: ...lbow SLP90 90 Elbow Effective Height Length SLP PIPE SLP HVS Horizontal Pipe Support SLP FS Ceiling Firestop SLP WS Wall Shield Firestop 10 7 8 in 276 mm 8 7 8 in 225 mm 1 1 2 in 38 mm 8 11 16 in 220 mm 8 11 16 in 220 mm 1 1 2 in 38 mm 12 in 305 mm 12 in 305 mm 5 1 2 in 146 mm Effective Height Length Pipe inches mm SLP4 4 102 SLP6 6 152 SLP12 12 305 SLP24 24 610 SLP36 36 914 SLP48 48 1219 SLP6A 2 ...

Page 56: ...84 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield Term Cap Minimum Effective Length Maximum Effective Length Trap1 3 1 8 in 4 3 4 in 79 mm 121mm Trap2 5 1 4 in 9 1 4 in 133 mm 235 mm 8 in 203 mm 12 in 305 mm Max Effective Length 14 7 16 in 367 mm 14 7 16 i...

Page 57: ...P Horizontal Termination Kit 14 in 356 mm 14 1 16 in 357 mm 7 1 2 in 192 mm 10 3 4 in 273 mm SLP CCS BK Cathedral Ceiling Support Box Black SLP DCF BK Ceiling Firestop Black SLK SNKD Snorkel Termination Cap SLP TVHW Vertical Termination Cap DVP FBHT Horizontal Termination Cap 13 1 2 in 343 mm 28 1 2 in 724 mm 10 11 16 in 271mm 17 7 8 IN 454 mm 7 3 8 IN 187 mm 14 IN 356 mm 12 IN 305 mm SLP TB1 Base...

Page 58: ...tallation Manual 2297 984 Rev B 6 15 LINK DV30B Flex Liner Kit DV 46DVA GCL Coaxial Colinear Appliance Connector 768 380A Stainless Steel Flex Pipe DVP 2SL Adapter COAXIAL to COLINEAR VENTING Figure 12 10 Coaxial to Colinear Vent Components ...

Page 59: ...plied with the fan kit to operate your fan See your dealer if you have questions Printed in U S A Copyright 2015 Heatliator a brand of Hearth Home Technologies 7571 215th Street West Lakeville MN 55044 www heatilator com Please contact your Heatilator dealer with any questions or concerns For the location of your nearest Heatilator dealer please visit www heatilator com Install approved accessorie...

Reviews: