Heat & Glo • HE36CLX-S • 2183-900 Rev. H • 1/14
30
120º
Figure 10.5 Securing Vertical Pipe Sections
120º
Figure 10.6 Securing Horizontal Pipe Sections
D. Disassemble Vent Sections
• Remove three screws that secure the pipe sections
together.
• Pull carefully but
fi
rmly to separate the pieces of pipe.
C. Secure the Vent Sections
• Vertical runs of CVP pipe originating off the top of the
appliance, with no offsets, must be supported every 8
ft. (2.44 m) after the maximum allowed 25 ft. (7.62 m) of
unsupported rise.
• Horizontal runs must be supported every 4 feet (1.2
m).
• Vent supports or plumbers strap (spaced 120º apart)
may be used to support vent sections. See Figures
10.5 and 10.6.
• Wall shield
fi
restops may be used to provide horizontal
support to vent sections.
• Vent pipe must slope upward 1/2 inch for every foot
of horizontal vent run to allow for proper drainage of
condensate.
WARNING! Risk of Fire, Explosion or Asphyxiation!
Improper support may allow vent to sag and separate.
Use vent run supports and connect vent sections per in-
stallation instructions.
DO NOT
allow vent to sag below
connection point to appliance.
Figure 10.7 Securing Horizontal Pipe Sections