059705–00 REV. B
|
61
19
SETTINGS—ADVANCED HEAT MENU
MAXIMUM WATER TEMPERATURE
Selections:
170°F–240°F
Default:
200°F
Description:
See page 50
for a full description.
MINIMUM WATER TEMPERATURE
Selections:
70°F–170°F
Default:
70°F
PUMP RUN-ON
Selections:
0–360 minutes
Default:
2 minutes
Description:
The System Pump relay will energize whenever the Outdoor temperature
is below the Outdoor start setting. When the outdoor temperature increases 2°F above
the Outdoor start after Genesis Heat-Timer
®
has either shutdown the boiler or closed
the valve, the System Pump relay will stay on for a period of time set by the Pump
Run-On. This allows the system pump to dissipate the residual heat within the system
back into the building.
The Pump Run-On time should be set based on the size and type of the boiler or
system. A boiler or system with low water content will require a longer Pump Run-On
than a boiler or system with larger water content.
MAX WATER TEMP
BACK SAVE
F
MIN WATER TEMP
BACK SAVE
F
PUMP RUN-ON
BACK SAVE
m