059705–00 REV. B
|
65
21
SETTINGS—MAINTENANCE MENU
MAINTENANCE
OUTDOOR SENSOR TRIM
Selections:
(–)5°F–5°F
Default:
0
SYSTEM SENSOR TRIM
Selections:
(–)5°F–5°F
Default:
0
Description:
The Heat-Timer thermistor type sensors are very accurate and
normally require no calibration. However, sometimes it may be desirable to make
small adjustments to the display valve for either Outdoor temperature of System
temperature. The Trim setting can adjust the display value by (–)5°F to 5°F.
Do not use the Trim setting to make the Outdoor temperature sensor match the
temperature reported on the radio or TV. Outdoor temperatures can vary widely over a
broadcast range. Only trim the outdoor sensor based on accurate thermometer reading
taken where the sensor is located.
PASSWORD
Selections:
Disable—Enable
Default:
Disable
Description:
The Password is a security measure to prevent unauthorized local control
users from making changes to the Genesis Heat-Timer
®
settings. It consist of 4 letters.
•
It does not protect against any remote changes. Remote Internet changes have a
web login screen with a different password for each user.
•
On the web, only the Internet account Owner can view and change the Password.
•
Setting up the Password feature makes servicing more difficult and can disable
the system if management or ownership should change.
•
The Password feature is not active unless a user enables it. If you choose to
enable the Password, DO NOT forget the Password. Write it down and store
it in a safe location known to at least one other authorized user.
•
When you set the Password Enabled to Yes, none of the settings, except,
Auto/Bypass switch, and Schedules can be changed without entering
the Password.
•
When you try to change a protected control setting, the login screen will show
upon trying to change a setting.
•
To enter the Password, toggle up or down to the desired letter. Then, press the
NEXT to move on to the next letter. Once the Password is complete, you can
make multiple changes. The Password will expire after 5 minutes of no activity.
OUTDOOR SENSOR TRIM
BACK SAVE
F
SYSTEM SENSOR TRIM
BACK SAVE
F
PASSWORD ENABLE
BACK SAVE
Disabled
Enabled