059705–00 REV. B
|
59
18
SETTINGS—BASIC HEAT MENU
AUTO DLS
Selections:
Enable, Disable
Default:
Enable
Description:
This setting is found under the SCHEDULES/SPACE TGT menu selection.
This setting allows the Genesis Heat-Timer
®
control to automatically adjust the Time
settings of the Schedule to the Day Light Savings Schedule.
DAYLIGHT SAVINGS
BACK SAVE
Disabled
Enabled
Saturday:
•
No Boost
is activated because the Wake Time period is not programmed. To start the Day Heating level without a Boost begin
the period as Return.
•
Return
period begins with a Day heating level and a building space temperature target of 72°F. This building space
temperature is maintained from 8 AM to 4 PM.
•
Early Shutdown
starts before 4 PM and ends at 4 PM.
•
Sleep
period begins with a Night heating level and a building space temperature target of 62°F. This building space
temperature is maintained from 10 PM to 8 AM when the next Day heating level begins.
Sunday:
•
Night
—The Night Heating level and desired building space temperature of 62°F is maintained all day Sunday, ending at the
Boost Monday morning at 6:00 AM.