68
|
059705–00 REV. B
21
SETTINGS—MAINTENANCE MENU
MAINTENANCE—
BOILER SETTINGS MENU
MODE
Selections:
Auto, Manual, Off
Default:
Auto
Description:
for MANUAL OP menu description.
IGNITION START
Selections:
0% to 100%
Default:
0%
Description:
The Ignition % is the minimum modulation percent for the boiler to
be activated. The Ignition % is maintained during the Purge Delay of the boiler.
For most modern power draft boilers, the Ignition % can be set to 1%. Other units
or atmospheric units may require their modulating to be from 20–50% before the
stage can be active Check with the equipment manufacturer for the minimum firing
rate required.
SOFT-OFF DELAY
Selections:
0 to 60 seconds
Default:
45 seconds
Description:
When the boiler is no longer needed for heat, the Soft-Off Delay
keeps that boiler at low fire prior to turning it off. This helps reduce the boiler from
short cycling.
If during the Soft-Off Delay period, the control needs the boiler to fire, the boiler is
released from the Soft-Delay and will resume normal operation.
The Genesis Heat-Timer
®
control will display a blinking Ignition % to indicate that the
boiler is in Soft-Off Delay.
NOTE
This section applies to applications where the Heating System selection is HOT WATER Curr Volt Boiler.
SOFT-OFF DELAY
BACK SAVE
sec
IGNITION START
BACK SAVE
MANUAL OPERATION
BACK SELECT
Auto
Open/On
Close/Off
Manual