HORIZONTAL INSTALLATION
(by others)
(by others)
Cableado
del termostato
Válvula compensadora opcional
Salida de agua
Entrada de agua
Válvula invertida opcional para
control de baja presión de agua
(puede montarse en forma interna)
Válvula a bola con tapón
P/T integrado opcional
Manguera trenzada de
acero inoxidable con accesorio
giratorio en “J”
Circuito
de edificación
Disyuntor de
energía de la unidad
(fabricado por terceros)
Alimentación
de energía de
la unidad
Conducto de alimentación
aislado con un codo (mínimo)
de 90 grados para reducir el
ruido del aire
Retorno de
aire
Aire de alimentación
Cableado de
alimentación
de energía
Varillas Roscadas de 3/8"
(fabricadas por terceros)
Colgador
de la unidad
Thermostat
Wiring
Optional Balancing Valve
Water In
Water Out
Optional Low Pressure Drop Water
Control Valve
Ball Valve with optional
integral P/T plug
Stainless steel braid hose
Building
Loop
Unit Power
Disconnect
Power Wiring
Insulated supply duct with
at least one 90 deg elbow
to reduce air noise
Return Air
Supply Air
Unit Hanger
3/8" [10mm] threaded rods
Unit Power
Flexible Duct
Connector
Figure 3: Typical Horizontal Unit Installation
Air Coil
To obtain maximum performance, the air coil should be
cleaned before start-up. A 10% solution of dishwasher
detergent and water is recommended for both sides of
the coil. A thorough water rinse should follow.
UV based
anti-bacterial systems will damage e-coated air coils.
NOTICE!
Installation Note - Ducted Return:
Many horizontal WSHPs are installed in a
return air ceiling plenum application (above
ceiling). Vertical WSHPs are commonly installed
in a mechanical room with free return (e.g.
louvered door). Therefore, filter rails are the
industry standard and are included on HC
Series commercial heat pumps for the purposes
of holding the filter only. For ducted return
applications, the filter rail must be removed and
replaced with a duct flange or filter rack. Canvas
or flexible connectors should also be used to
minimize vibration between the unit and ductwork.