Heat Controller H 006 Installation, Operation And Maintenance Manual Download Page 27

6

5.   Two factors determine the operating limits of Heat 

Controller heat pumps, (a) return air temperature, 
and (b) water temperature. When any one of these 
factors is at a minimum or maximum level, the other 
factor must be at normal level to insure proper unit 
operation.

a.   Adjust the unit thermostat to the warmest setting. 

Place the thermostat mode switch in the “COOL” 
position.  Slowly reduce thermostat setting until the 
compressor activates.

b.   Check for cool air delivery at the unit grille within a 

few minutes after the unit has begun to operate.

 

Note: Units have a five minute time delay in the 
control circuit that can be eliminated on the CXM 
control board as shown below in Figure 7. See 
controls description for details.

c.   Verify that the compressor is on and that the water 

flow rate is correct by measuring pressure drop 
through the heat exchanger using the P/T plugs 
and comparing to tables 8a through 8e.

d.   Check the elevation and cleanliness of the 

condensate lines. Dripping may be a sign of a 
blocked line. Check that the condensate trap is 
filled to provide a water seal.

e.   Refer to table . Check the temperature of both 

entering and leaving water. If temperature is within 
range, proceed with the test. If temperature is 
outside of the operating range, check refrigerant 
pressures and compare to table1. Verify correct 
water flow by comparing unit pressure drop 
across the heat exchanger versus the data in 
tables 8a through 8e. Heat of rejection (HR) can 
be calculated and compared to submittal data 
capacity pages.  The formula for HR for systems 
with water is as follows: 
HR = TD x GPM x 500, where TD is the 
temperature difference between the entering and 
leaving water, and GPM is the flow rate in U.S. 
GPM, determined by comparing the pressure drop 
across the heat exchanger to table 8.

f.   Check air temperature drop across the air coil when 

compressor is operating. Air temperature drop 
should be between 15°F and 5°F [8°C and 14°C].

g.   Turn thermostat to “OFF” position. A hissing noise 

indicates proper functioning of the reversing valve.

6.  Allow five (5) minutes between tests for pressure to 

equalize before beginning heating test.

a.   Adjust the thermostat to the lowest setting. Place 

the thermostat mode switch in the “HEAT” position.

b.   Slowly raise the thermostat to a higher 

temperature until the compressor activates.

c.   Check for warm air delivery within a few minutes 

after the unit has begun to operate.

d.   Refer to table . Check the temperature of both 

entering and leaving water. If temperature is within 
range, proceed with the test. If temperature is 
outside of the operating range, check refrigerant 
pressures and compare to table 1. Verify correct 

water flow by comparing unit pressure drop across 
the heat exchanger versus the data in table 8. 
Heat of extraction (HE) can be calculated and 
compared to submittal data capacity pages.  The 
formula for HE for systems with water is as follows: 

 

HE = TD x GPM x 500, where TD is the 
temperature difference between the entering and 
leaving water, and GPM is the flow rate in U.S. 
GPM, determined by comparing the pressure drop 
across the heat exchanger to table 8.

e.   Check air temperature rise across the air coil when 

compressor is operating. Air temperature rise should 
be between 0°F and 0°F [11°C and 17°C]. 

f.   Check for vibration, noise, and water leaks.

7.   If unit fails to operate, perform troubleshooting 

analysis (see troubleshooting section). If the check 
described fails to reveal the problem and the unit 
still does not operate, contact a trained service 
technician to insure proper diagnosis and repair of 
the equipment.

8.   When testing is complete, set system to maintain 

desired comfort level.

.   BE CERTAIN TO FILL OUT AND FORWARD ALL 

WARRANTY REGISTRATION PAPERS TO HEAT 
CONTROLLER.

Note: If performance during any mode appears abnormal, 
refer to the CXM section or troubleshooting section of 
this manual. To obtain maximum performance, the air 
coil should be cleaned before start-up. A 10% solution of 
dishwasher detergent and water is recommended.

WARNING!

  When the disconnect switch is 

closed, high voltage is present in some areas 
of the electrical panel. Exercise caution when 
working with energized equipment.

UNIT START-UP PROCEDURE

CAUTION!

  Verify that ALL water control 

valves are open and allow water flow prior 
to engaging the compressor. Freezing of the 
coax or water lines can permanently damage 
the heat pump.

Short test pins 
together to enter Test 
Mode and speed-up 
timing and delays for 
0 minutes.

Figure 27: Test Mode Pins

� 

WARNING! 

� 

CAUTION! 

Summary of Contents for H 006

Page 1: ...ns Commercial Water Source Heat Pumps HEAT CONTROLLER INC 1900 Wellworth Ave Jackson Michigan 49203 Ph 517 787 2100 Fax 517 787 9341 www heatcontroller com THE QUALITY LEADER IN CONDITIONING AIR Insta...

Page 2: ...and High Static Z Straight and High Static Y Back and High Static 1 2 3 456 7 8 9 10 11 12 13 14 Table of Contents Model Nomenclature 1 Storage 3 Pre Installation 3 Physical Data 4 Dimensional Data 5...

Page 3: ...ts as a source of heating or cooling during the construction process The mechanical components and filters will quickly become clogged with construction dirt and debris which may cause system damage W...

Page 4: ...the unit and its operation Thoroughly check the system before operation Prepare units for installation as follows 1 Compare the electrical data on the unit nameplate with ordering and shipping inform...

Page 5: ...x 24 610 x 610 24 x 24 610 x 610 1 14 x 24 1 18 x 24 Weight Operating lbs kg 103 47 105 48 114 52 181 82 189 86 197 89 203 92 218 99 263 119 278 126 Weight Packaged lbs kg 113 51 115 52 124 56 186 84...

Page 6: ...0 8 1 8 0 8 1 2 8 1 5 1 2 1 0 8 8 9 6 7 5 2 1 3 16 1 9 8 1 1 0 6 cm 48 5 86 6 27 9 24 4 2 0 4 4 2 0 20 6 13 0 5 4 1 9 22 7 17 0 13 3 3 3 41 0 25 0 2 7 1 5 018 in 20 1 43 1 17 1 15 3 2 4 1 9 2 1 1 2 12...

Page 7: ...5 55 9 3 6 7 1 24 0 7 1 15 6 5 9 7 3 14 9 22 5 22 7 12 9 22 9 22 9 14 0 5 3 41 1 25 1 1 9 018 in 21 5 21 5 39 0 1 8 3 8 15 2 3 6 8 1 2 3 1 2 4 1 7 1 10 1 6 4 3 8 14 0 14 0 5 3 2 3 18 3 20 2 0 7 cm 54...

Page 8: ...electrical cables and other items that prohibit future removal of components or the unit itself 4 Use a manual portable jack lift to lift and support the weight of the unit during installation and se...

Page 9: ...ower Disconnect Power Wiring Insulated supply duct with at least one 90 deg elbow to reduce air noise Return Air Supply Air Unit Hanger 3 8 10mm threaded rods Unit Power Flexible Duct Connector Figure...

Page 10: ...position as shown being careful with the blower wiring 3 Check blower wire routing and connections for tension or contact with sheet metal edges Reroute if necessary 4 Check refrigerant tubing for con...

Page 11: ...19mm ID plastic hose Insure that the hose is without kinks to maintain unobstructed flow of condensate from the unit to the drain Verify that condensate line is pitched towards the drain 1 4 per foot...

Page 12: ...eyond all four edges of the unit 2 Provide adequate clearance for filter replacement and drain pan cleaning Do not block filter access with piping conduit or other materials Refer to unit submittal da...

Page 13: ...r neoprene isolation pad to minimize vibration transmission to the building structure Figure 9 Vertical Sound Attenuation Condensate Piping Vertical Units Vertical units utilize a condensate hose insi...

Page 14: ...compound is preferred use compound only in small amounts on the external pipe threads of the fitting adapters Prevent sealant from reaching the flared surfaces of the joint Note When anti freeze is us...

Page 15: ...ed pumping systems may also be included in the external piping The piping system should be flushed to remove dirt piping chips and other foreign material prior to operation see Piping System Cleaning...

Page 16: ...s are OK to 0 5 ppm Ammonia ion All 0 5 ppm as hydroxide chloride nitrate and sulfate compounds Maximum Maximum Allowable at maximum water temperature Chloride Levels 50 F 10 C 75 F 24 C 100 F 38 C Co...

Page 17: ...0 1 80 7 5 8 9 15 5 575 60 3 518 633 1 4 7 39 0 1 40 6 1 7 2 15 1 208 230 60 1 197 254 1 25 6 170 0 4 30 29 9 36 4 60 V H060 3 208 230 60 3 197 254 1 14 7 124 0 4 30 19 0 22 7 35 4 460 60 3 414 506 1...

Page 18: ...size Grnd Rev 5 17 01 B Capacitor WARNING Disconnect electrical power source to prevent injury or death from electrical shock 208 Volt Operation All commercial 208 230 Volt units are factory wired fo...

Page 19: ...mostat should be wired directly to the CXM board Figure 19 Low Voltage Field Wiring Low Water Temperature Cutout The CXM control senses low water temperature utilizing thermistor FP1 Note that the FP1...

Page 20: ...60 seconds to open very little water will flow before 45 seconds Once fully open an end switch allows the compressor to be energized Only relay or triac based electronic thermostats should be used wit...

Page 21: ...ermostat wires protrude through the middle of the back plate Mark the position of the back plate mounting holes and drill holes with a 3 16 5mm bit Install supplied anchors and secure plate to the wal...

Page 22: ...21 TYPICAL WIRING DIAGRAM HCH HCV UNITS WITH CXM BOARD SINGLE PHASE...

Page 23: ...Description of Operation LED Alarm Relay Normal Mode On Open Normal Mode with UPS Warning On Cycle closed 5 sec Open 5 sec CXM is non functional Off Open Fault Retry Slow Flash Open Lockout Fast Flash...

Page 24: ...ds normal operation is restored This is not considered a fault or lockout If the CXM is in over under voltage shutdown for 15 minutes the alarm relay will close Over under voltage shut down code 7 Uni...

Page 25: ...gle most important step to insure proper start up and continued efficient operation of the system Follow the instructions below to properly clean and flush the system 1 Insure that electrical power to...

Page 26: ...and adjust water pH if necessary to maintain a level between 6 and 8 5 Proper pH promotes longevity of hoses and fittings see table 3 System flushing Verify that all hoses are connected end to end wh...

Page 27: ...thermostat to the lowest setting Place the thermostat mode switch in the HEAT position b Slowly raise the thermostat to a higher temperature until the compressor activates c Check for warm air deliver...

Page 28: ...27 Table 8e HCH_HCV Coax Water Pressure UNIT OPERATING CONDITIONS Table 9 Water Temperature Change Through Heat Exchanger...

Page 29: ...per Sub Temp Temp Pressure Pressure Super Sub Temp Temp Temp F GPM ton PSIG PSIG heat cooling Rise F Drop F DB PSIG PSIG heat cooling Drop F DB Rise F 1 5 66 75 160 1 0 10 0 6 16 0 0 5 60 70 05 0 10 1...

Page 30: ...produce a slimy substance in the drain pan it may be necessary to treat the drain pan chemically with an algaecide approximately every three months to minimize the problem The condensate pan may also...

Page 31: ...heck static vs blower table X Air Temperature out of range Too much cold vent air Bring entering air temp within design parameters X Improper temperature limit setting 30 F vs 10 F Normal airside appl...

Page 32: ...X X Inlet Water too Hot or Cold Check load loop sizing loop backfill ground moisture High Head Pressure X Reduced or no Air flow Check for dirty air filter and clean or replace in heating Check fan m...

Page 33: ..._______ flow rate diff factor _____________ Btu hr Superheat Subcooling Suction temperature suction saturation temp Discharge saturation temp liquid line temp deg F deg F Look up pressure drop in I O...

Page 34: ...4006 1900 WELLWORTH AVENUE JACKSON MICHIGAN 49203 THE QUALITY LEADER IN CONDITIONING AIR visit us at www heatcontroller com Specifications and performance data subject to change without notice 97B0016...

Reviews: