Heat Controller H 006 Installation, Operation And Maintenance Manual Download Page 25

4

UNIT STARTING AND OPERATING CONDITIONS

Operating Limits

Environment – Units are designed for indoor installation 
only. Never install units in areas subject to freezing or where 
humidity levels could cause cabinet condensation (such as 
unconditioned spaces subject to 100% outside air). 
Power Supply – A voltage variation of +/– 10% of 
nameplate utilization voltage is acceptable.

Starting Conditions

Consult Table 7 for starting conditions. vary depending 
upon model number and are based upon the following 
notes:   

Notes:

1.  Conditions in Table 7 are not normal or continuous 

operating conditions. Minimum/maximum limits are 

start-up conditions to bring the building space up to 
occupancy temperatures.  Units are not designed to 
operate under these conditions on a regular basis.

.   Voltage utilization range complies with ARI  

Standard 110.

Determination of operating limits is dependent primarily 
upon three factors: 1) return air temperature. ) water 
temperature, and ) ambient temperature. When any 
one of these factors is at minimum or maximum levels, 
the other two factors should be at normal levels to insure 
proper unit operation.

Extreme variations in temperature and humidity 
and/or corrosive water or air will adversely affect unit 
performance, reliability, and service life.

Cooling

Heating

Air Limits

Min. ambient air, DB

45ºF [7ºC]

39ºF [4ºC]

Rated ambient air, DB

80.6ºF [27ºC]

68ºF [20ºC]

Max. ambient air, DB

110ºF [43ºC]

85ºF [29ºC]

Min. entering air, DB/WB

70/61ºF [21/16ºC]

50ºF [10ºC]

Rated entering air, DB/WB

80.6/66.2ºF [27/19ºC]

68ºF [20ºC]

Max. entering air, DB/WB

95/76ºF [35/24ºC]

80ºF [27ºC]

Water Limits

Min. entering water

50ºF [10ºC]

50ºF [10ºC]

Normal entering water

60-90ºF [15-32ºC]

60-70ºF [15-21ºC]

Max. entering water

110ºF [43ºC]

90ºF [32ºC]

HCH/HCV

Operating Limits

Normal Water Flow

[3.2 to 3.9 l/m per kW]

2.5 to 3.0 gpm / ton

Table 7: Operating Limits

Piping System Cleaning and Flushing

Cleaning and flushing the WLHP piping system is the 
single most important step to insure proper start-up and 
continued efficient operation of the system.
Follow the instructions below to properly clean and flush 
the system:
1.   Insure that electrical power to the unit is disconnected.
.   Install the system with the supply hose connected 

directly to the return riser valve. Use a single length of 
flexible hose.

.   Open all air vents. Fill the system with water. DO 

NOT allow system to overflow. Bleed all air from the 
system. Pressurize and check the system for leaks 
and repair as appropriate.

4.   Verify that all strainers are in place (Heat Controller 

recommends a strainer with a #0 stainless steel wire 
mesh). Start the pumps, and systematically check each 
vent to ensure that all air is bled from the system.

5.   Verify that make-up water is available. Adjust make-up 

water as required to replace the air which was bled 
from the system. Check and adjust the water/air level 
in the expansion tank.

6.   Set the boiler to raise the loop temperature to 

approximately 86°F [0°C]. Open a drain at the 
lowest point in the system. Adjust the make-up water 
replacement rate to equal the rate of bleed.

7.   Refill the system and add trisodium phosphate in 

a proportion of approximately one pound per 150 
gallons [1/ kg per 750 l] of water (or other equivalent 
approved cleaning agent). Reset the boiler to raise 
the loop temperature to 100°F [8°C]. Circulate the 
solution for a minimum of 8 to 4 hours. At the end of 
this period, shut off the circulating pump and drain the 
solution. Repeat system cleaning if desired.

8.   When the cleaning process is complete, remove the 

short-circuited hoses. Reconnect the hoses to the 
proper supply, and return the connections to each of 
the units. Refill the system and bleed off all air.

.   Test the system pH with litmus paper. The system 

water should be in the range of pH 6.0 - 8.5 (see table 
). Add chemicals, as appropriate to maintain neutral 
pH levels.

10. When the system is successfully cleaned, flushed, 

refilled and bled, check the main system panels, 
safety cutouts and alarms. Set the controls to properly 
maintain loop temperatures.

PIPING SYSTEM CLEANING AND FLUSHING

Summary of Contents for H 006

Page 1: ...ns Commercial Water Source Heat Pumps HEAT CONTROLLER INC 1900 Wellworth Ave Jackson Michigan 49203 Ph 517 787 2100 Fax 517 787 9341 www heatcontroller com THE QUALITY LEADER IN CONDITIONING AIR Insta...

Page 2: ...and High Static Z Straight and High Static Y Back and High Static 1 2 3 456 7 8 9 10 11 12 13 14 Table of Contents Model Nomenclature 1 Storage 3 Pre Installation 3 Physical Data 4 Dimensional Data 5...

Page 3: ...ts as a source of heating or cooling during the construction process The mechanical components and filters will quickly become clogged with construction dirt and debris which may cause system damage W...

Page 4: ...the unit and its operation Thoroughly check the system before operation Prepare units for installation as follows 1 Compare the electrical data on the unit nameplate with ordering and shipping inform...

Page 5: ...x 24 610 x 610 24 x 24 610 x 610 1 14 x 24 1 18 x 24 Weight Operating lbs kg 103 47 105 48 114 52 181 82 189 86 197 89 203 92 218 99 263 119 278 126 Weight Packaged lbs kg 113 51 115 52 124 56 186 84...

Page 6: ...0 8 1 8 0 8 1 2 8 1 5 1 2 1 0 8 8 9 6 7 5 2 1 3 16 1 9 8 1 1 0 6 cm 48 5 86 6 27 9 24 4 2 0 4 4 2 0 20 6 13 0 5 4 1 9 22 7 17 0 13 3 3 3 41 0 25 0 2 7 1 5 018 in 20 1 43 1 17 1 15 3 2 4 1 9 2 1 1 2 12...

Page 7: ...5 55 9 3 6 7 1 24 0 7 1 15 6 5 9 7 3 14 9 22 5 22 7 12 9 22 9 22 9 14 0 5 3 41 1 25 1 1 9 018 in 21 5 21 5 39 0 1 8 3 8 15 2 3 6 8 1 2 3 1 2 4 1 7 1 10 1 6 4 3 8 14 0 14 0 5 3 2 3 18 3 20 2 0 7 cm 54...

Page 8: ...electrical cables and other items that prohibit future removal of components or the unit itself 4 Use a manual portable jack lift to lift and support the weight of the unit during installation and se...

Page 9: ...ower Disconnect Power Wiring Insulated supply duct with at least one 90 deg elbow to reduce air noise Return Air Supply Air Unit Hanger 3 8 10mm threaded rods Unit Power Flexible Duct Connector Figure...

Page 10: ...position as shown being careful with the blower wiring 3 Check blower wire routing and connections for tension or contact with sheet metal edges Reroute if necessary 4 Check refrigerant tubing for con...

Page 11: ...19mm ID plastic hose Insure that the hose is without kinks to maintain unobstructed flow of condensate from the unit to the drain Verify that condensate line is pitched towards the drain 1 4 per foot...

Page 12: ...eyond all four edges of the unit 2 Provide adequate clearance for filter replacement and drain pan cleaning Do not block filter access with piping conduit or other materials Refer to unit submittal da...

Page 13: ...r neoprene isolation pad to minimize vibration transmission to the building structure Figure 9 Vertical Sound Attenuation Condensate Piping Vertical Units Vertical units utilize a condensate hose insi...

Page 14: ...compound is preferred use compound only in small amounts on the external pipe threads of the fitting adapters Prevent sealant from reaching the flared surfaces of the joint Note When anti freeze is us...

Page 15: ...ed pumping systems may also be included in the external piping The piping system should be flushed to remove dirt piping chips and other foreign material prior to operation see Piping System Cleaning...

Page 16: ...s are OK to 0 5 ppm Ammonia ion All 0 5 ppm as hydroxide chloride nitrate and sulfate compounds Maximum Maximum Allowable at maximum water temperature Chloride Levels 50 F 10 C 75 F 24 C 100 F 38 C Co...

Page 17: ...0 1 80 7 5 8 9 15 5 575 60 3 518 633 1 4 7 39 0 1 40 6 1 7 2 15 1 208 230 60 1 197 254 1 25 6 170 0 4 30 29 9 36 4 60 V H060 3 208 230 60 3 197 254 1 14 7 124 0 4 30 19 0 22 7 35 4 460 60 3 414 506 1...

Page 18: ...size Grnd Rev 5 17 01 B Capacitor WARNING Disconnect electrical power source to prevent injury or death from electrical shock 208 Volt Operation All commercial 208 230 Volt units are factory wired fo...

Page 19: ...mostat should be wired directly to the CXM board Figure 19 Low Voltage Field Wiring Low Water Temperature Cutout The CXM control senses low water temperature utilizing thermistor FP1 Note that the FP1...

Page 20: ...60 seconds to open very little water will flow before 45 seconds Once fully open an end switch allows the compressor to be energized Only relay or triac based electronic thermostats should be used wit...

Page 21: ...ermostat wires protrude through the middle of the back plate Mark the position of the back plate mounting holes and drill holes with a 3 16 5mm bit Install supplied anchors and secure plate to the wal...

Page 22: ...21 TYPICAL WIRING DIAGRAM HCH HCV UNITS WITH CXM BOARD SINGLE PHASE...

Page 23: ...Description of Operation LED Alarm Relay Normal Mode On Open Normal Mode with UPS Warning On Cycle closed 5 sec Open 5 sec CXM is non functional Off Open Fault Retry Slow Flash Open Lockout Fast Flash...

Page 24: ...ds normal operation is restored This is not considered a fault or lockout If the CXM is in over under voltage shutdown for 15 minutes the alarm relay will close Over under voltage shut down code 7 Uni...

Page 25: ...gle most important step to insure proper start up and continued efficient operation of the system Follow the instructions below to properly clean and flush the system 1 Insure that electrical power to...

Page 26: ...and adjust water pH if necessary to maintain a level between 6 and 8 5 Proper pH promotes longevity of hoses and fittings see table 3 System flushing Verify that all hoses are connected end to end wh...

Page 27: ...thermostat to the lowest setting Place the thermostat mode switch in the HEAT position b Slowly raise the thermostat to a higher temperature until the compressor activates c Check for warm air deliver...

Page 28: ...27 Table 8e HCH_HCV Coax Water Pressure UNIT OPERATING CONDITIONS Table 9 Water Temperature Change Through Heat Exchanger...

Page 29: ...per Sub Temp Temp Pressure Pressure Super Sub Temp Temp Temp F GPM ton PSIG PSIG heat cooling Rise F Drop F DB PSIG PSIG heat cooling Drop F DB Rise F 1 5 66 75 160 1 0 10 0 6 16 0 0 5 60 70 05 0 10 1...

Page 30: ...produce a slimy substance in the drain pan it may be necessary to treat the drain pan chemically with an algaecide approximately every three months to minimize the problem The condensate pan may also...

Page 31: ...heck static vs blower table X Air Temperature out of range Too much cold vent air Bring entering air temp within design parameters X Improper temperature limit setting 30 F vs 10 F Normal airside appl...

Page 32: ...X X Inlet Water too Hot or Cold Check load loop sizing loop backfill ground moisture High Head Pressure X Reduced or no Air flow Check for dirty air filter and clean or replace in heating Check fan m...

Page 33: ..._______ flow rate diff factor _____________ Btu hr Superheat Subcooling Suction temperature suction saturation temp Discharge saturation temp liquid line temp deg F deg F Look up pressure drop in I O...

Page 34: ...4006 1900 WELLWORTH AVENUE JACKSON MICHIGAN 49203 THE QUALITY LEADER IN CONDITIONING AIR visit us at www heatcontroller com Specifications and performance data subject to change without notice 97B0016...

Reviews: