Heat Controller H 006 Installation, Operation And Maintenance Manual Download Page 26

5

DO NOT use “Stop Leak” or similar chemical agent in this 
system. Addition of chemicals of this type to the loop water 
will foul the heat exchanger and inhibit unit operation.

CAUTION!

  To avoid possible damage to a 

plastic (PVC) piping system, do not allow 
temperatures to exceed 11°F [45°C].

Unit and System Checkout

BEFORE POWERING SYSTEM, please check the following:

UNIT CHECKOUT

  Balancing/shutoff valves: Insure that all isolation 

valves are open and water control valves are wired.  

  Line voltage and wiring: Verify that voltage is within an 

acceptable range for the unit and wiring and fuses/
breakers are properly sized. Verify that low voltage 
wiring is complete.

  Unit control transformer: Insure that transformer 

has the properly selected voltage tap. Commercial 
08-0V units are factory wired for 08V operation 
unless specified otherwise.

  Entering water and air: Insure that entering water and 

air temperatures are within operating limits of Table 7.

  Unit fan: Manually rotate fan to verify free rotation and 

insure that blower wheel is secured to the motor shaft. 
Be sure to remove any shipping supports if needed. 
DO NOT oil motors upon start-up. Fan motors are 
pre-oiled at the factory. Check unit fan speed selection 
and compare to design requirements.

  Condensate line: Verify that condensate line is open 

and properly pitched toward drain.

  Water flow balancing: Record inlet and outlet water 

temperatures for each heat pump upon startup. This 
check can eliminate nuisance trip outs and high 
velocity water flow that could erode heat exchangers.

  Unit air coil and filters: Insure that filter is clean and 

accessible. Clean air coil of all manufacturing oils.

  Unit controls: Verify that CXM field selection options 

are properly set.

SYSTEM CHECKOUT

  System water temperature: Check water temperature 

for proper range and also verify heating and cooling 
set points for proper operation.

  System pH: Check and adjust water pH if necessary 

to maintain a level between 6 and 8.5. Proper pH 
promotes longevity of hoses and fittings (see table ).

  System flushing: Verify that all hoses are connected 

end to end when flushing to insure that debris 
bypasses the unit heat exchanger, water valves and 
other components. Water used in the system must be 
potable quality initially and clean of dirt, piping slag, 
and strong chemical cleaning agents. Verify that all 

air is purged from the system. Air in the system can 
cause poor operation or system corrosion.

  Cooling tower/boiler: Check equipment for proper set 

points and operation.

  Standby pumps: Verify that the standby pump is 

properly installed and in operating condition.

  System controls: Verify that system controls function 

and operate in the proper sequence.

  Low water temperature cutout: Verify that low water 

temperature cut-out controls are provided for the 
outdoor portion of the loop.  Otherwise, operating 
problems may occur.

  System control center: Verify that the control center 

and alarm panel have appropriate set points and are 
operating as designed.

  Miscellaneous: Note any questionable aspects of  

the installation.

CAUTION!

  Verify that ALL water control 

valves are open and allow water flow prior 
to engaging the compressor. Freezing of the 
coax or water lines can permanently dam-
age the heat pump.

CAUTION!

  To avoid equipment damage, DO 

NOT leave system filled in a building without 
heat during the winter unless antifreeze is 
added to the water loop. Heat exchangers 
never fully drain by themselves and will 
freeze unless winterized with antifreeze.

UNIT AND SYSTEM CHECKOUT

Unit Start-up Procedure

1.   Turn the thermostat fan position to “ON.” Blower 

should start.

.   Balance air flow at registers.
.   Adjust all valves to their full open position. Turn on the 

line power to all heat pump units.

4.   Room temperature should be within the minimum-

maximum ranges of table 7. During start-up checks, 
loop water temperature entering the heat pump 
should be between 60°F [16°C] and 5°F [5°C].

UNIT START-UP

UNIT STARTING AND OPERATING CONDITIONS

� 

CAUTION! 

� 

CAUTION! 

� 

CAUTION! 

Summary of Contents for H 006

Page 1: ...ns Commercial Water Source Heat Pumps HEAT CONTROLLER INC 1900 Wellworth Ave Jackson Michigan 49203 Ph 517 787 2100 Fax 517 787 9341 www heatcontroller com THE QUALITY LEADER IN CONDITIONING AIR Insta...

Page 2: ...and High Static Z Straight and High Static Y Back and High Static 1 2 3 456 7 8 9 10 11 12 13 14 Table of Contents Model Nomenclature 1 Storage 3 Pre Installation 3 Physical Data 4 Dimensional Data 5...

Page 3: ...ts as a source of heating or cooling during the construction process The mechanical components and filters will quickly become clogged with construction dirt and debris which may cause system damage W...

Page 4: ...the unit and its operation Thoroughly check the system before operation Prepare units for installation as follows 1 Compare the electrical data on the unit nameplate with ordering and shipping inform...

Page 5: ...x 24 610 x 610 24 x 24 610 x 610 1 14 x 24 1 18 x 24 Weight Operating lbs kg 103 47 105 48 114 52 181 82 189 86 197 89 203 92 218 99 263 119 278 126 Weight Packaged lbs kg 113 51 115 52 124 56 186 84...

Page 6: ...0 8 1 8 0 8 1 2 8 1 5 1 2 1 0 8 8 9 6 7 5 2 1 3 16 1 9 8 1 1 0 6 cm 48 5 86 6 27 9 24 4 2 0 4 4 2 0 20 6 13 0 5 4 1 9 22 7 17 0 13 3 3 3 41 0 25 0 2 7 1 5 018 in 20 1 43 1 17 1 15 3 2 4 1 9 2 1 1 2 12...

Page 7: ...5 55 9 3 6 7 1 24 0 7 1 15 6 5 9 7 3 14 9 22 5 22 7 12 9 22 9 22 9 14 0 5 3 41 1 25 1 1 9 018 in 21 5 21 5 39 0 1 8 3 8 15 2 3 6 8 1 2 3 1 2 4 1 7 1 10 1 6 4 3 8 14 0 14 0 5 3 2 3 18 3 20 2 0 7 cm 54...

Page 8: ...electrical cables and other items that prohibit future removal of components or the unit itself 4 Use a manual portable jack lift to lift and support the weight of the unit during installation and se...

Page 9: ...ower Disconnect Power Wiring Insulated supply duct with at least one 90 deg elbow to reduce air noise Return Air Supply Air Unit Hanger 3 8 10mm threaded rods Unit Power Flexible Duct Connector Figure...

Page 10: ...position as shown being careful with the blower wiring 3 Check blower wire routing and connections for tension or contact with sheet metal edges Reroute if necessary 4 Check refrigerant tubing for con...

Page 11: ...19mm ID plastic hose Insure that the hose is without kinks to maintain unobstructed flow of condensate from the unit to the drain Verify that condensate line is pitched towards the drain 1 4 per foot...

Page 12: ...eyond all four edges of the unit 2 Provide adequate clearance for filter replacement and drain pan cleaning Do not block filter access with piping conduit or other materials Refer to unit submittal da...

Page 13: ...r neoprene isolation pad to minimize vibration transmission to the building structure Figure 9 Vertical Sound Attenuation Condensate Piping Vertical Units Vertical units utilize a condensate hose insi...

Page 14: ...compound is preferred use compound only in small amounts on the external pipe threads of the fitting adapters Prevent sealant from reaching the flared surfaces of the joint Note When anti freeze is us...

Page 15: ...ed pumping systems may also be included in the external piping The piping system should be flushed to remove dirt piping chips and other foreign material prior to operation see Piping System Cleaning...

Page 16: ...s are OK to 0 5 ppm Ammonia ion All 0 5 ppm as hydroxide chloride nitrate and sulfate compounds Maximum Maximum Allowable at maximum water temperature Chloride Levels 50 F 10 C 75 F 24 C 100 F 38 C Co...

Page 17: ...0 1 80 7 5 8 9 15 5 575 60 3 518 633 1 4 7 39 0 1 40 6 1 7 2 15 1 208 230 60 1 197 254 1 25 6 170 0 4 30 29 9 36 4 60 V H060 3 208 230 60 3 197 254 1 14 7 124 0 4 30 19 0 22 7 35 4 460 60 3 414 506 1...

Page 18: ...size Grnd Rev 5 17 01 B Capacitor WARNING Disconnect electrical power source to prevent injury or death from electrical shock 208 Volt Operation All commercial 208 230 Volt units are factory wired fo...

Page 19: ...mostat should be wired directly to the CXM board Figure 19 Low Voltage Field Wiring Low Water Temperature Cutout The CXM control senses low water temperature utilizing thermistor FP1 Note that the FP1...

Page 20: ...60 seconds to open very little water will flow before 45 seconds Once fully open an end switch allows the compressor to be energized Only relay or triac based electronic thermostats should be used wit...

Page 21: ...ermostat wires protrude through the middle of the back plate Mark the position of the back plate mounting holes and drill holes with a 3 16 5mm bit Install supplied anchors and secure plate to the wal...

Page 22: ...21 TYPICAL WIRING DIAGRAM HCH HCV UNITS WITH CXM BOARD SINGLE PHASE...

Page 23: ...Description of Operation LED Alarm Relay Normal Mode On Open Normal Mode with UPS Warning On Cycle closed 5 sec Open 5 sec CXM is non functional Off Open Fault Retry Slow Flash Open Lockout Fast Flash...

Page 24: ...ds normal operation is restored This is not considered a fault or lockout If the CXM is in over under voltage shutdown for 15 minutes the alarm relay will close Over under voltage shut down code 7 Uni...

Page 25: ...gle most important step to insure proper start up and continued efficient operation of the system Follow the instructions below to properly clean and flush the system 1 Insure that electrical power to...

Page 26: ...and adjust water pH if necessary to maintain a level between 6 and 8 5 Proper pH promotes longevity of hoses and fittings see table 3 System flushing Verify that all hoses are connected end to end wh...

Page 27: ...thermostat to the lowest setting Place the thermostat mode switch in the HEAT position b Slowly raise the thermostat to a higher temperature until the compressor activates c Check for warm air deliver...

Page 28: ...27 Table 8e HCH_HCV Coax Water Pressure UNIT OPERATING CONDITIONS Table 9 Water Temperature Change Through Heat Exchanger...

Page 29: ...per Sub Temp Temp Pressure Pressure Super Sub Temp Temp Temp F GPM ton PSIG PSIG heat cooling Rise F Drop F DB PSIG PSIG heat cooling Drop F DB Rise F 1 5 66 75 160 1 0 10 0 6 16 0 0 5 60 70 05 0 10 1...

Page 30: ...produce a slimy substance in the drain pan it may be necessary to treat the drain pan chemically with an algaecide approximately every three months to minimize the problem The condensate pan may also...

Page 31: ...heck static vs blower table X Air Temperature out of range Too much cold vent air Bring entering air temp within design parameters X Improper temperature limit setting 30 F vs 10 F Normal airside appl...

Page 32: ...X X Inlet Water too Hot or Cold Check load loop sizing loop backfill ground moisture High Head Pressure X Reduced or no Air flow Check for dirty air filter and clean or replace in heating Check fan m...

Page 33: ..._______ flow rate diff factor _____________ Btu hr Superheat Subcooling Suction temperature suction saturation temp Discharge saturation temp liquid line temp deg F deg F Look up pressure drop in I O...

Page 34: ...4006 1900 WELLWORTH AVENUE JACKSON MICHIGAN 49203 THE QUALITY LEADER IN CONDITIONING AIR visit us at www heatcontroller com Specifications and performance data subject to change without notice 97B0016...

Reviews: