Heat Controller H 006 Installation, Operation And Maintenance Manual Download Page 11

10

Duct System Installation

The duct system should be sized to handle the design 
airflow quietly. Refer to Figure  for horizontal duct 
system details or figure 8 for vertical duct system details. 
A flexible connector is recommended for both discharge 
and return air duct connections on metal duct systems to 
eliminate the transfer of vibration to the duct system. To 
maximize sound attenuation of the unit blower, the supply 
and return plenums should include internal fiberglass 
duct liner or be constructed from ductboard for the first 
few feet. Application of the unit to uninsulated ductwork 
in an unconditioned space is not recommended, as the 
unit’s performance will be adversely affected.

At least one 0° elbow should be included in the supply 
duct to reduce air noise. If air noise or excessive air flow 
is a problem, the blower speed can be changed. For 
airflow charts, consult submittal data for the series and 
model of the specific unit.

If the unit is connected to existing ductwork, a previous 
check should have been made to insure that the ductwork 
has the capacity to handle the airflow required for the 
unit. If ducting is too small, as in the replacement of a 
heating only system, larger ductwork should be installed. 
All existing ductwork should be checked for leaks and 
repaired as necessary.

��������

����������

�����������

��������

������

�������������

���������������

�����������

�����������

����������������

����������������

������������������

�����������

Figure 6: Horizontal Condensate Connection

HORIZONTAL INSTALLATION

CAUTION! 

 Ensure condensate line is 

pitched toward drain 1/4” per foot [10mm per 
46cm] of run.

Condensate Piping – Horizontal Units

Units are typically installed directly above each other on 
successive floors with condensate drains located near 
the units.  Attach the unit condensate drain connection 
to the building condensate drain with a flexible, non-
pressure-rated /4 inch [1mm] ID plastic hose. Insure 
that the hose is without kinks to maintain unobstructed 
flow of condensate from the unit to the drain. Verify that 
condensate line is pitched towards the drain 1/4” per foot 
(10mm per 46cm) of run.

Pitch the unit toward the drain as shown in Figure  to 
improve the condensate drainage. On small units (less 
than .5 tons/8.8 kW), insure that unit pitch does not 
cause condensate leaks inside the cabinet.

The horizontal run of a condensate hose is usually 
too short to cause drainage problems. However, the 
horizontal run of the condensate line should be pitched 
at least 1 inch for every 10 feet [10mm per 116cm] of run 
in the direction of flow to insure that the connection will 
not slip off due to excessive weight or piping expansion/
contraction. Avoid low points and non-pitched piping 
since dirt collects in low or level areas and may cause 
stoppage and overflow.

Install condensate trap at each unit with the top of the trap 
positioned below the unit condensate drain connection as 
shown in Figure 6.  Design the depth of the trap (water-
seal) based upon the amount of ESP capability of the 
blower (where  inches [51mm] of ESP capability requires 
 inches [51mm] of trap depth). As a general rule, 1-1/ 
inch [8mm] trap depth is the minimum.

Each unit must be installed with its own individual trap 
and connection to the condensate line (main) or riser.  
Provide a means to flush or blow out the condensate line. 
DO NOT install units with a common trap and/or vent.

� 

CAUTION! 

Always vent the condensate line when dirt or air 
can collect in the line or a long horizontal drain line 
is required. Also vent when large units are working 
against higher external static pressure than other units 
connected to the same condensate main since this may 
cause poor drainage for all units on the line. WHEN A 
VENT IS INSTALLED IN THE DRAIN LINE, IT MUST BE 
LOCATED AFTER THE TRAP IN THE DIRECTION OF 
THE CONDENSATE FLOW.

DUCT SYSTEM INSTALLATION

Summary of Contents for H 006

Page 1: ...ns Commercial Water Source Heat Pumps HEAT CONTROLLER INC 1900 Wellworth Ave Jackson Michigan 49203 Ph 517 787 2100 Fax 517 787 9341 www heatcontroller com THE QUALITY LEADER IN CONDITIONING AIR Insta...

Page 2: ...and High Static Z Straight and High Static Y Back and High Static 1 2 3 456 7 8 9 10 11 12 13 14 Table of Contents Model Nomenclature 1 Storage 3 Pre Installation 3 Physical Data 4 Dimensional Data 5...

Page 3: ...ts as a source of heating or cooling during the construction process The mechanical components and filters will quickly become clogged with construction dirt and debris which may cause system damage W...

Page 4: ...the unit and its operation Thoroughly check the system before operation Prepare units for installation as follows 1 Compare the electrical data on the unit nameplate with ordering and shipping inform...

Page 5: ...x 24 610 x 610 24 x 24 610 x 610 1 14 x 24 1 18 x 24 Weight Operating lbs kg 103 47 105 48 114 52 181 82 189 86 197 89 203 92 218 99 263 119 278 126 Weight Packaged lbs kg 113 51 115 52 124 56 186 84...

Page 6: ...0 8 1 8 0 8 1 2 8 1 5 1 2 1 0 8 8 9 6 7 5 2 1 3 16 1 9 8 1 1 0 6 cm 48 5 86 6 27 9 24 4 2 0 4 4 2 0 20 6 13 0 5 4 1 9 22 7 17 0 13 3 3 3 41 0 25 0 2 7 1 5 018 in 20 1 43 1 17 1 15 3 2 4 1 9 2 1 1 2 12...

Page 7: ...5 55 9 3 6 7 1 24 0 7 1 15 6 5 9 7 3 14 9 22 5 22 7 12 9 22 9 22 9 14 0 5 3 41 1 25 1 1 9 018 in 21 5 21 5 39 0 1 8 3 8 15 2 3 6 8 1 2 3 1 2 4 1 7 1 10 1 6 4 3 8 14 0 14 0 5 3 2 3 18 3 20 2 0 7 cm 54...

Page 8: ...electrical cables and other items that prohibit future removal of components or the unit itself 4 Use a manual portable jack lift to lift and support the weight of the unit during installation and se...

Page 9: ...ower Disconnect Power Wiring Insulated supply duct with at least one 90 deg elbow to reduce air noise Return Air Supply Air Unit Hanger 3 8 10mm threaded rods Unit Power Flexible Duct Connector Figure...

Page 10: ...position as shown being careful with the blower wiring 3 Check blower wire routing and connections for tension or contact with sheet metal edges Reroute if necessary 4 Check refrigerant tubing for con...

Page 11: ...19mm ID plastic hose Insure that the hose is without kinks to maintain unobstructed flow of condensate from the unit to the drain Verify that condensate line is pitched towards the drain 1 4 per foot...

Page 12: ...eyond all four edges of the unit 2 Provide adequate clearance for filter replacement and drain pan cleaning Do not block filter access with piping conduit or other materials Refer to unit submittal da...

Page 13: ...r neoprene isolation pad to minimize vibration transmission to the building structure Figure 9 Vertical Sound Attenuation Condensate Piping Vertical Units Vertical units utilize a condensate hose insi...

Page 14: ...compound is preferred use compound only in small amounts on the external pipe threads of the fitting adapters Prevent sealant from reaching the flared surfaces of the joint Note When anti freeze is us...

Page 15: ...ed pumping systems may also be included in the external piping The piping system should be flushed to remove dirt piping chips and other foreign material prior to operation see Piping System Cleaning...

Page 16: ...s are OK to 0 5 ppm Ammonia ion All 0 5 ppm as hydroxide chloride nitrate and sulfate compounds Maximum Maximum Allowable at maximum water temperature Chloride Levels 50 F 10 C 75 F 24 C 100 F 38 C Co...

Page 17: ...0 1 80 7 5 8 9 15 5 575 60 3 518 633 1 4 7 39 0 1 40 6 1 7 2 15 1 208 230 60 1 197 254 1 25 6 170 0 4 30 29 9 36 4 60 V H060 3 208 230 60 3 197 254 1 14 7 124 0 4 30 19 0 22 7 35 4 460 60 3 414 506 1...

Page 18: ...size Grnd Rev 5 17 01 B Capacitor WARNING Disconnect electrical power source to prevent injury or death from electrical shock 208 Volt Operation All commercial 208 230 Volt units are factory wired fo...

Page 19: ...mostat should be wired directly to the CXM board Figure 19 Low Voltage Field Wiring Low Water Temperature Cutout The CXM control senses low water temperature utilizing thermistor FP1 Note that the FP1...

Page 20: ...60 seconds to open very little water will flow before 45 seconds Once fully open an end switch allows the compressor to be energized Only relay or triac based electronic thermostats should be used wit...

Page 21: ...ermostat wires protrude through the middle of the back plate Mark the position of the back plate mounting holes and drill holes with a 3 16 5mm bit Install supplied anchors and secure plate to the wal...

Page 22: ...21 TYPICAL WIRING DIAGRAM HCH HCV UNITS WITH CXM BOARD SINGLE PHASE...

Page 23: ...Description of Operation LED Alarm Relay Normal Mode On Open Normal Mode with UPS Warning On Cycle closed 5 sec Open 5 sec CXM is non functional Off Open Fault Retry Slow Flash Open Lockout Fast Flash...

Page 24: ...ds normal operation is restored This is not considered a fault or lockout If the CXM is in over under voltage shutdown for 15 minutes the alarm relay will close Over under voltage shut down code 7 Uni...

Page 25: ...gle most important step to insure proper start up and continued efficient operation of the system Follow the instructions below to properly clean and flush the system 1 Insure that electrical power to...

Page 26: ...and adjust water pH if necessary to maintain a level between 6 and 8 5 Proper pH promotes longevity of hoses and fittings see table 3 System flushing Verify that all hoses are connected end to end wh...

Page 27: ...thermostat to the lowest setting Place the thermostat mode switch in the HEAT position b Slowly raise the thermostat to a higher temperature until the compressor activates c Check for warm air deliver...

Page 28: ...27 Table 8e HCH_HCV Coax Water Pressure UNIT OPERATING CONDITIONS Table 9 Water Temperature Change Through Heat Exchanger...

Page 29: ...per Sub Temp Temp Pressure Pressure Super Sub Temp Temp Temp F GPM ton PSIG PSIG heat cooling Rise F Drop F DB PSIG PSIG heat cooling Drop F DB Rise F 1 5 66 75 160 1 0 10 0 6 16 0 0 5 60 70 05 0 10 1...

Page 30: ...produce a slimy substance in the drain pan it may be necessary to treat the drain pan chemically with an algaecide approximately every three months to minimize the problem The condensate pan may also...

Page 31: ...heck static vs blower table X Air Temperature out of range Too much cold vent air Bring entering air temp within design parameters X Improper temperature limit setting 30 F vs 10 F Normal airside appl...

Page 32: ...X X Inlet Water too Hot or Cold Check load loop sizing loop backfill ground moisture High Head Pressure X Reduced or no Air flow Check for dirty air filter and clean or replace in heating Check fan m...

Page 33: ..._______ flow rate diff factor _____________ Btu hr Superheat Subcooling Suction temperature suction saturation temp Discharge saturation temp liquid line temp deg F deg F Look up pressure drop in I O...

Page 34: ...4006 1900 WELLWORTH AVENUE JACKSON MICHIGAN 49203 THE QUALITY LEADER IN CONDITIONING AIR visit us at www heatcontroller com Specifications and performance data subject to change without notice 97B0016...

Reviews: