Heat Controller H 006 Installation, Operation And Maintenance Manual Download Page 14

1

CAUTION! 

 Corrosive system water requires 

corrosion resistant fittings and hoses, and 
may require water treatment.

PIPING INSTALLATION

Installation of Supply and Return Piping

Follow these piping guidelines.
1.   Install a drain valve at the base of each supply and 

return riser to facilitate system flushing.

.   Install shut-off / balancing valves and unions at each 

unit to permit unit removal for servicing.

.   Place strainers at the inlet of each system 

circulating pump.

4.   Select the proper hose length to allow slack between 

connection points. Hoses may vary in length by +% 
to -4% under pressure.

5.   Refer to Table 1. Do not exceed the minimum bend 

radius for the hose selected. Exceeding the minimum 
bend radius may cause the hose to collapse, which 
reduces water flow rate. Install an angle adapter to 
avoid sharp bends in the hose when the radius falls 
below the required minimum.

Insulation is not required on loop water piping except 
where the piping runs through unheated areas, outside 
the building or when the loop water temperature is below 
the minimum expected dew point of the pipe ambient 
conditions. Insulation is required if loop water temperature 
drops below the dew point (insulation is required for 
ground loop applications in most climates).

Pipe joint compound is not necessary when Teflon® 
thread tape is pre-applied to hose assemblies or when 
flared-end connections are used. If pipe joint compound 
is preferred, use compound only in small amounts on 
the external pipe threads of the fitting adapters. Prevent 
sealant from reaching the flared surfaces of the joint. 

Note: When anti-freeze is used in the loop, insure that it 
is compatible with the Teflon tape or pipe joint compound 
that is applied.

Maximum allowable torque for brass fittings is 0 ft-lbs 
[41 N-m]. If a torque wrench is not available, tighten 
finger-tight plus one quarter turn. Tighten steel fittings  
as necessary.

Optional pressure-rated hose assemblies designed 
specifically for use with Heat Controller units are available. 
Similar hoses can be obtained from alternate suppliers. 
Supply and return hoses are fitted with swivel-joint fittings 
at one end to prevent kinking during installation. 

Refer to Figure 11 for an illustration of a typical supply/
return hose kit. Adapters secure hose assemblies to 
the unit and risers. Install hose assemblies properly and 
check regularly to avoid system failure and reduced 
service life. 

A backup wrench is required when tightening water 
connections to prevent water line damage.

Table 1: Metal Hose Minimum Bend Radii

Hose Diameter

Minimum Bend Radii

1/2" [12.7mm]

2-1/2" [6.4cm]

3/4" [19.1mm]

4" [10.2cm]

1" [25.4mm]

5-1/2" [14cm]

1-1/4" [31.8mm]

6-3/4" [17.1cm]

CAUTION!  

Do not bend or kink supply lines  

or hoses.

NOTICE!

  Do not allow hoses to rest against 

structural building components. Compressor 
vibration may be transmitted through the 
hoses to the structure, causing unnecessary 
noise complaints.

CAUTION!

  Piping must comply with all 

applicable codes.

Figure 11: Supply/Return Hose Kit

�����������

������

�����������������������������

������

�����

�������

������

�������

���

�����������������

��������

���������� ���������������

���������

���������

���������

���������

���������

���

� 

CAUTION! 

� 

CAUTION! 

� 

CAUTION! 

Summary of Contents for H 006

Page 1: ...ns Commercial Water Source Heat Pumps HEAT CONTROLLER INC 1900 Wellworth Ave Jackson Michigan 49203 Ph 517 787 2100 Fax 517 787 9341 www heatcontroller com THE QUALITY LEADER IN CONDITIONING AIR Insta...

Page 2: ...and High Static Z Straight and High Static Y Back and High Static 1 2 3 456 7 8 9 10 11 12 13 14 Table of Contents Model Nomenclature 1 Storage 3 Pre Installation 3 Physical Data 4 Dimensional Data 5...

Page 3: ...ts as a source of heating or cooling during the construction process The mechanical components and filters will quickly become clogged with construction dirt and debris which may cause system damage W...

Page 4: ...the unit and its operation Thoroughly check the system before operation Prepare units for installation as follows 1 Compare the electrical data on the unit nameplate with ordering and shipping inform...

Page 5: ...x 24 610 x 610 24 x 24 610 x 610 1 14 x 24 1 18 x 24 Weight Operating lbs kg 103 47 105 48 114 52 181 82 189 86 197 89 203 92 218 99 263 119 278 126 Weight Packaged lbs kg 113 51 115 52 124 56 186 84...

Page 6: ...0 8 1 8 0 8 1 2 8 1 5 1 2 1 0 8 8 9 6 7 5 2 1 3 16 1 9 8 1 1 0 6 cm 48 5 86 6 27 9 24 4 2 0 4 4 2 0 20 6 13 0 5 4 1 9 22 7 17 0 13 3 3 3 41 0 25 0 2 7 1 5 018 in 20 1 43 1 17 1 15 3 2 4 1 9 2 1 1 2 12...

Page 7: ...5 55 9 3 6 7 1 24 0 7 1 15 6 5 9 7 3 14 9 22 5 22 7 12 9 22 9 22 9 14 0 5 3 41 1 25 1 1 9 018 in 21 5 21 5 39 0 1 8 3 8 15 2 3 6 8 1 2 3 1 2 4 1 7 1 10 1 6 4 3 8 14 0 14 0 5 3 2 3 18 3 20 2 0 7 cm 54...

Page 8: ...electrical cables and other items that prohibit future removal of components or the unit itself 4 Use a manual portable jack lift to lift and support the weight of the unit during installation and se...

Page 9: ...ower Disconnect Power Wiring Insulated supply duct with at least one 90 deg elbow to reduce air noise Return Air Supply Air Unit Hanger 3 8 10mm threaded rods Unit Power Flexible Duct Connector Figure...

Page 10: ...position as shown being careful with the blower wiring 3 Check blower wire routing and connections for tension or contact with sheet metal edges Reroute if necessary 4 Check refrigerant tubing for con...

Page 11: ...19mm ID plastic hose Insure that the hose is without kinks to maintain unobstructed flow of condensate from the unit to the drain Verify that condensate line is pitched towards the drain 1 4 per foot...

Page 12: ...eyond all four edges of the unit 2 Provide adequate clearance for filter replacement and drain pan cleaning Do not block filter access with piping conduit or other materials Refer to unit submittal da...

Page 13: ...r neoprene isolation pad to minimize vibration transmission to the building structure Figure 9 Vertical Sound Attenuation Condensate Piping Vertical Units Vertical units utilize a condensate hose insi...

Page 14: ...compound is preferred use compound only in small amounts on the external pipe threads of the fitting adapters Prevent sealant from reaching the flared surfaces of the joint Note When anti freeze is us...

Page 15: ...ed pumping systems may also be included in the external piping The piping system should be flushed to remove dirt piping chips and other foreign material prior to operation see Piping System Cleaning...

Page 16: ...s are OK to 0 5 ppm Ammonia ion All 0 5 ppm as hydroxide chloride nitrate and sulfate compounds Maximum Maximum Allowable at maximum water temperature Chloride Levels 50 F 10 C 75 F 24 C 100 F 38 C Co...

Page 17: ...0 1 80 7 5 8 9 15 5 575 60 3 518 633 1 4 7 39 0 1 40 6 1 7 2 15 1 208 230 60 1 197 254 1 25 6 170 0 4 30 29 9 36 4 60 V H060 3 208 230 60 3 197 254 1 14 7 124 0 4 30 19 0 22 7 35 4 460 60 3 414 506 1...

Page 18: ...size Grnd Rev 5 17 01 B Capacitor WARNING Disconnect electrical power source to prevent injury or death from electrical shock 208 Volt Operation All commercial 208 230 Volt units are factory wired fo...

Page 19: ...mostat should be wired directly to the CXM board Figure 19 Low Voltage Field Wiring Low Water Temperature Cutout The CXM control senses low water temperature utilizing thermistor FP1 Note that the FP1...

Page 20: ...60 seconds to open very little water will flow before 45 seconds Once fully open an end switch allows the compressor to be energized Only relay or triac based electronic thermostats should be used wit...

Page 21: ...ermostat wires protrude through the middle of the back plate Mark the position of the back plate mounting holes and drill holes with a 3 16 5mm bit Install supplied anchors and secure plate to the wal...

Page 22: ...21 TYPICAL WIRING DIAGRAM HCH HCV UNITS WITH CXM BOARD SINGLE PHASE...

Page 23: ...Description of Operation LED Alarm Relay Normal Mode On Open Normal Mode with UPS Warning On Cycle closed 5 sec Open 5 sec CXM is non functional Off Open Fault Retry Slow Flash Open Lockout Fast Flash...

Page 24: ...ds normal operation is restored This is not considered a fault or lockout If the CXM is in over under voltage shutdown for 15 minutes the alarm relay will close Over under voltage shut down code 7 Uni...

Page 25: ...gle most important step to insure proper start up and continued efficient operation of the system Follow the instructions below to properly clean and flush the system 1 Insure that electrical power to...

Page 26: ...and adjust water pH if necessary to maintain a level between 6 and 8 5 Proper pH promotes longevity of hoses and fittings see table 3 System flushing Verify that all hoses are connected end to end wh...

Page 27: ...thermostat to the lowest setting Place the thermostat mode switch in the HEAT position b Slowly raise the thermostat to a higher temperature until the compressor activates c Check for warm air deliver...

Page 28: ...27 Table 8e HCH_HCV Coax Water Pressure UNIT OPERATING CONDITIONS Table 9 Water Temperature Change Through Heat Exchanger...

Page 29: ...per Sub Temp Temp Pressure Pressure Super Sub Temp Temp Temp F GPM ton PSIG PSIG heat cooling Rise F Drop F DB PSIG PSIG heat cooling Drop F DB Rise F 1 5 66 75 160 1 0 10 0 6 16 0 0 5 60 70 05 0 10 1...

Page 30: ...produce a slimy substance in the drain pan it may be necessary to treat the drain pan chemically with an algaecide approximately every three months to minimize the problem The condensate pan may also...

Page 31: ...heck static vs blower table X Air Temperature out of range Too much cold vent air Bring entering air temp within design parameters X Improper temperature limit setting 30 F vs 10 F Normal airside appl...

Page 32: ...X X Inlet Water too Hot or Cold Check load loop sizing loop backfill ground moisture High Head Pressure X Reduced or no Air flow Check for dirty air filter and clean or replace in heating Check fan m...

Page 33: ..._______ flow rate diff factor _____________ Btu hr Superheat Subcooling Suction temperature suction saturation temp Discharge saturation temp liquid line temp deg F deg F Look up pressure drop in I O...

Page 34: ...4006 1900 WELLWORTH AVENUE JACKSON MICHIGAN 49203 THE QUALITY LEADER IN CONDITIONING AIR visit us at www heatcontroller com Specifications and performance data subject to change without notice 97B0016...

Reviews: